Other characteristics of a circuit-breaker: Difference between revisions

From Electrical Installation Guide
Home > LV switchgear: functions and selection > Circuit-breaker > Other characteristics of a circuit-breaker
(modified footnote syntax (cleanup_2016))
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "")
 
(21 intermediate revisions by 5 users not shown)
Line 1: Line 1:
{{Menu_LV_switchgear_functions_and_selection}}
{{Menu_LV_switchgear_functions_and_selection}}__TOC__
 
__TOC__
 
 
{| class="wikitable" style="width: 65%; height: 17px"
|-
! Familiarity with the following characteristics of LV circuit-breakers is often necessary when making a final choice.
|}
 
 
 
== Rated insulation voltage (Ui)==
== Rated insulation voltage (Ui)==


This is the value of voltage to which the dielectric tests voltage (generally greater than 2 Ui) and creepage distances are referred to.<br>The maximum value of rated operational voltage must never exceed that of the rated insulation voltage, i.e. Ue ≤ Ui.  
This is the value of voltage to which the dielectric tests voltage (generally greater than 2 Ui) and creepage distances are referred to.


The maximum value of rated operational voltage must never exceed that of the rated insulation voltage, i.e. Ue ≤ Ui.


== Rated impulse-withstand voltage (Uimp)  ==
== Rated impulse-withstand voltage (Uimp)  ==


This characteristic expresses, in kV peak (of a prescribed form and polarity) the value of voltage which the equipment is capable of withstanding without failure, under test conditions. <br>Generally, for industrial circuit-breakers, Uimp = 8 kV and for domestic types, Uimp = 6 kV.
This characteristic expresses, in kV peak (of a prescribed form and polarity) the value of voltage which the equipment is capable of withstanding without failure, under test conditions.  
 
 
== Category (A or B) and rated short-time withstand current (Icw)  ==
 
As already briefly mentioned there are two categories of LV&nbsp;industrial switchgear, A and B, according to IEC 60947-2:
 
*Those of category A, for which there is no deliberate delay in the operation of the “instantaneous” short-circuit magnetic tripping device (see '''Fig. H35'''), are generally moulded-case type circuit-breakers, and
 


[[File:FigH35.jpg|none]]
Generally, for industrial circuit-breakers, Uimp = 8 kV and for domestic types, Uimp = 6 kV.  


'''''Fig. H35: '''Category A circuit-breaker''
== Selectivity categories and rated short-time withstand current (Icw)  ==


IEC 60947-2 defines two types of circuit breaker defined by their “selectivity category”:


*Those of category B for which, in order to discriminate with other circuit-breakers on a time basis, it is possible to delay the tripping of the CB, where the fault-current level is lower than that of the short-time withstand current rating (Icw) of the CB (see '''Fig. H36'''). This is generally applied to large open-type circuit-breakers and to certain heavy-duty moulded-case types. Icw is the maximum current that the B category CB can withstand, thermally and electrodynamically, without sustaining damage, for a period of time given by the manufacturer.
* '''Selectivity category B''' comprises circuit breakers providing selectivity by having a short-time withstand current rating and an associated short-time delay. For this category of circuit breaker, manufacturer shall provide the value of short-circuit current (Icw) that can be withstood for a specified time.


It is possible to delay the tripping of this type circuit breaker, where the fault-current level is lower than this short-time withstand current rating (Icw) (see {{FigureRef|H32}}).


[[File:FigH36.jpg|none]]
This is generally applied to power open type or “Air” circuit breakers and to certain heavy-duty molded-case types. Icw is the maximum current that the B category circuit breaker can withstand, thermally and electrodynamically, without sustaining damage, for a period of time given by the manufacturer.


'''''Fig. H36:''' Category B circuit-breaker''
{{FigImage|DB422411|svg|H32|Category B circuit-breaker}}


* '''Selectivity category A''' comprises all other circuit breakers. This category of circuit breaker has no deliberate delay in the operation of the “instantaneous” short-circuit magnetic tripping device (see {{FigureRef|H33}}). Usually molded-case type circuit breakers or modular circuit breaker are category A These circuit breakers may provide selectivity under short-circuit conditions by other means. But manufacturer will not provide Icw value.


{{FigImage|DB422410|svg|H33|Category A circuit-breaker}}


== Rated making capacity (Icm)  ==
== Rated making capacity (Icm)  ==


Icm is the highest instantaneous value of current that the circuit-breaker can establish at rated voltage in specified conditions. In AC systems this instantaneous peak value is related to Icu (i.e. to the rated breaking current) by the factor k, which depends on the power factor (cos φ) of the short-circuit current loop (as shown in '''Figure H37 ''').  
Icm is the highest instantaneous value of current that the circuit-breaker can establish at rated voltage in specified conditions. In AC systems this instantaneous peak value is related to Icu (i.e. to the rated breaking current) by the factor k, which depends on the power factor (cos φ) of the short-circuit current loop (as shown in {{FigureRef|H34}} ).  
 


{| class="wikitable" style="width: 289px; height: 54px" width="289"
{{tb-start|id=Tab1269|num=H34|title=Relation between rated breaking capacity Icu and rated making capacity Icm at different power-factor values of short-circuit current, as standardized in IEC 60947-2|cols=3}}
{| class="wikitable"
|-
|-
! Icu  
! Icu  
Line 53: Line 39:
! Icm = kIcu
! Icm = kIcu
|-
|-
| 6 kA &lt; Icu ≤ 10 kA  
| 6 kA < Icu ≤ 10 kA  
| 0.5  
| 0.5  
| 1.7 x Icu
| 1.7 x Icu
|-
|-
| 10 kA &lt; Icu ≤ 20 kA  
| 10 kA < Icu ≤ 20 kA  
| 0.3  
| 0.3  
| 2 x Icu
| 2 x Icu
|-
|-
| 20 kA &lt; Icu ≤ 50 kA  
| 20 kA < Icu ≤ 50 kA  
| 0.25  
| 0.25  
| 2.1 x Icu
| 2.1 x Icu
Line 69: Line 55:
| 2.2 x Icu
| 2.2 x Icu
|}
|}
'''''Fig. H37:''' Relation between rated breaking capacity Icu and rated making capacity Icm at different power-factor values of short-circuit current, as standardized in IEC 60947-2''


'''Example:''' A Masterpact NW08H2 circuit-breaker has a rated breaking capacity Icu of 100 kA. The peak value of its rated making capacity Icm will be 100 x 2.2 = 220&nbsp;kA.  
'''Example:''' A Masterpact NW08H2 circuit-breaker has a rated breaking capacity Icu of 100 kA. The peak value of its rated making capacity Icm will be 100 x 2.2 = 220&nbsp;kA.  


== Rated service short-circuit breaking capacity (Ics)  ==
== Rated service short-circuit breaking capacity (Ics)  ==
{{Highlightbox|
In a correctly designed installation, a circuit-breaker is never required to operate at its maximum breaking current Icu. For this reason a new characteristic Ics has been introduced. <br>It is expressed in IEC 60947-2 as a percentage of Icu (25, 50, 75, 100%)
}}


The rated breaking capacity (Icu) or (Icn) is the maximum fault-current a circuit-breaker can successfully interrupt without being damaged. The probability of such a current occurring is extremely low, and in normal circumstances the fault-currents are considerably less than the rated breaking capacity (Icu) of the CB. On the other hand it is important that high currents (of low probability) be interrupted under good conditions, so that the CB is immediately available for reclosure, after the faulty circuit has been repaired. It is for these reasons that a new characteristic (Ics) has been created, expressed as a percentage of Icu, viz: 25, 50, 75, 100% for industrial circuit-breakers. The standard test sequence is as follows:  
The rated breaking capacity (Icu) or (Icn) is the maximum fault-current a circuit-breaker can successfully interrupt without being damaged. The probability of such a current occurring is extremely low, and in normal circumstances the fault-currents are considerably less than the rated breaking capacity (Icu) of the CB. On the other hand it is important that high currents (of low probability) be interrupted under good conditions, so that the CB is immediately available for reclosure, after the faulty circuit has been repaired. It is for these reasons that a new characteristic (Ics) has been created, expressed as a percentage of Icu, viz: 25, 50, 75, 100% for industrial circuit-breakers. The standard test sequence is as follows:  
*O - CO - CO{{fn|1}} (at Ics)  
*O - CO - CO{{fn|1}} (at Ics)  
*Tests carried out following this sequence are intended to verify that the CB is in a good state and available for normal service
*Tests carried out following this sequence are intended to verify that the CB is in a good state and available for normal service


For domestic CBs, Ics = k Icn. The factor k values are given in IEC 60898 table XIV.<br>In Europe it is the industrial practice to use a k factor of 100% so that Ics = Icu.  
For domestic CBs, Ics = k Icn. The factor k values are given in IEC 60898 table XIV.


In Europe it is the industrial practice to use a k factor of 100% so that Ics = Icu.


== Fault-current limitation  ==
== Fault-current limitation  ==


{{Highlightbox|
{{Highlightbox|
Many designs of LV circuit-breakers feature a short-circuit current limitation capability, whereby the current is reduced and prevented from reaching its (otherwise) maximum peak value (see Fig. H38). The current-limitation performance of these CBs is presented in the form of graphs, typified by that shown in Figure&nbsp;H39, diagram (a)
Many designs of LV circuit-breakers feature a short-circuit current limitation capability, whereby the current is reduced and prevented from reaching its (otherwise) maximum peak value (see {{FigureRef|H35}}). The current-limitation performance of these CBs is presented in the form of graphs, typified by that shown in {{FigureRef|H36}}, diagram (a)}}
}}
 
The fault-current limitation capacity of a CB concerns its ability, more or less effective, in preventing the passage of the maximum prospective fault-current, permitting only a limited amount of current to flow, as shown in '''Figure H38'''.
 


[[File:FigH38.jpg|none]]
The fault-current limitation capacity of a CB concerns its ability, more or less effective, in preventing the passage of the maximum prospective fault-current, permitting only a limited amount of current to flow, as shown in {{FigureRef|H35}}.  


'''''Fig. H38:''' Prospective and actual currents''
{{FigImage|DB422412_EN|svg|H35|Prospective and actual currents}}


 
The current-limitation performance is given by the CB manufacturer in the form of curves (see {{FigRef|H36}}).  
The current-limitation performance is given by the CB manufacturer in the form of curves (see '''Fig. H39''').  


*Diagram '''(a)''' shows the limited peak value of current plotted against the rms value of the AC component of the prospective fault current (“prospective” fault-current refers to the fault-current which would flow if the CB had no current-limiting capability)  
*Diagram '''(a)''' shows the limited peak value of current plotted against the rms value of the AC component of the prospective fault current (“prospective” fault-current refers to the fault-current which would flow if the CB had no current-limiting capability)  
*Limitation of the current greatly reduces the thermal stresses (proportional I<sup>2</sup>t) and this is shown by the curve of diagram '''(b)''' of Figure H39, again, versus the rms value of the AC component of the prospective fault current.
*Limitation of the current greatly reduces the thermal stresses (proportional I<sup>2</sup>t) and this is shown by the curve of diagram '''(b)''' of {{FigureRef|H36}}, again, versus the rms value of the AC component of the prospective fault current.


LV circuit-breakers for domestic and similar installations are classified in certain standards (notably European Standard EN 60 898). CBs belonging to one class (of current limiters) have standardized limiting I<sup>2</sup>t let-through characteristics defined by that class.<br>In these cases, manufacturers do not normally provide characteristic performance curves.  
LV circuit-breakers for domestic and similar installations are classified in certain standards (notably European Standard EN 60 898). CBs belonging to one class (of current limiters) have standardized limiting I<sup>2</sup>t let-through characteristics defined by that class.


In these cases, manufacturers do not normally provide characteristic performance curves.


 
{{Gallery|H36|Performance curves of a typical LV current-limiting circuit-breaker||
'''(a)''' &nbsp;&nbsp;&nbsp; [[File:FigH39a.jpg]] &nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; '''(b)''' &nbsp;&nbsp;&nbsp; [[File:FigH39b.jpg]]
|DB422413_EN.svg|a|
 
|DB422414_EN.svg|b|}}
'''''Fig. H39:''' Performance curves of a typical LV current-limiting circuit-breaker''
 


== The advantages of current limitation  ==
== The advantages of current limitation  ==


{{Highlightbox|
{{Highlightbox|
Current limitation reduces both thermal and electrodynamic stresses on all circuit elements through which the current passes, thereby prolonging the useful life of these elements. Furthermore, the limitation feature allows “cascading” techniques to be used (see [[Coordination between circuit-breakers]]) thereby significantly reducing design and installation costs
Current limitation reduces both thermal and electrodynamic stresses on all circuit elements through which the current passes, thereby prolonging the useful life of these elements. Furthermore, the limitation feature allows “cascading” techniques to be used (see [[Coordination between circuit-breakers]]) thereby significantly reducing design and installation costs}}
}}


The use of current-limiting CBs affords numerous advantages:  
The use of current-limiting CBs affords numerous advantages:  
*Better conservation of installation networks: current-limiting CBs strongly attenuate all harmful effects associated with short-circuit currents  
*Better conservation of installation networks: current-limiting CBs strongly attenuate all harmful effects associated with short-circuit currents  
*Reduction of thermal effects: Conductors (and therefore insulation) heating is significantly reduced, so that the life of cables is correspondingly increased  
*Reduction of thermal effects: Conductors (and therefore insulation) heating is significantly reduced, so that the life of cables is correspondingly increased  
*Reduction of mechanical effects: forces due to electromagnetic repulsion are lower, with less risk of deformation and possible rupture, excessive burning of contacts, etc.  
*Reduction of mechanical effects: forces due to electromagnetic repulsion are lower, with less risk of deformation and possible rupture, excessive burning of contacts, etc.  
*Reduction of electromagnetic-interference effects:<br>
*Reduction of electromagnetic-interference effects:
&nbsp;- &nbsp; Less influence on measuring instruments and associated circuits, telecommunication systems, etc.
**Less influence on measuring instruments and associated circuits, telecommunication systems, etc.


These circuit-breakers therefore contribute towards an improved exploitation of:  
These circuit-breakers therefore contribute towards an improved exploitation of:  
Line 137: Line 107:
*Switchgear, thereby reducing the ageing of the installation
*Switchgear, thereby reducing the ageing of the installation


'''Example'''
=== Example ===


On a system having a prospective shortcircuit current of 150 kA rms, a Compact L circuit-breaker limits the peak current to less than 10% of the calculated prospective peak value, and the thermal effects to less than 1% of those calculated.
On a system having a prospective shortcircuit current of 150 kA rms, a Compact L circuit-breaker limits the peak current to less than 10% of the calculated prospective peak value, and the thermal effects to less than 1% of those calculated.
Line 145: Line 115:
The technique of cascading allows, in fact, substantial savings on switchgear (lower performance permissible downstream of the limiting CB(s)) enclosures, and design studies, of up to 20% (overall).
The technique of cascading allows, in fact, substantial savings on switchgear (lower performance permissible downstream of the limiting CB(s)) enclosures, and design studies, of up to 20% (overall).


Discriminative protection schemes and cascading are compatible, in the Compact NSX range, up to the full short-circuit breaking capacity of the switchgear.  
Selective protection schemes and cascading are compatible, in the Compact NSX range, up to the full short-circuit breaking capacity of the switchgear.  
 


{{footnotes}}
{{footnotes}}
<references>
<references>
{{fn-detail|1|O represents an opening operation.<br>CO represents a closing operation followed by an opening operation.}}
{{fn-detail|1|O represents an opening operation.<br>
CO represents a closing operation followed by an opening operation.}}
</references>
</references>


{{Related-guides-intro}}
{{RelatedGuide
|image=Hp-highlight-selectivity-guide.png
|title=Selectivity, Cascading and Coordination Guide - new 2021 edition!
|text=Get all required information to verify your electrical distribution design's robustness, considering overloads and short circuits.


Combine the benefits of selectivity and cascading to maximize power availability of your LV design at optimized cost.


[[ru:Другие характеристики автоматического выключателя]]
Find Schneider Electric's coordination data for ACBs, MCCBs, MCBs, switches, busbar trunking (busways), motor starters and more.
[[zh:断路器的其他特性]]
|btn-text=Download the guide (.pdf)
|link=https://www.se.com/ww/en/download/document/LVPED318033EN/
}}

Latest revision as of 09:49, 22 June 2022

Rated insulation voltage (Ui)

This is the value of voltage to which the dielectric tests voltage (generally greater than 2 Ui) and creepage distances are referred to.

The maximum value of rated operational voltage must never exceed that of the rated insulation voltage, i.e. Ue ≤ Ui.

Rated impulse-withstand voltage (Uimp)

This characteristic expresses, in kV peak (of a prescribed form and polarity) the value of voltage which the equipment is capable of withstanding without failure, under test conditions.

Generally, for industrial circuit-breakers, Uimp = 8 kV and for domestic types, Uimp = 6 kV.

Selectivity categories and rated short-time withstand current (Icw)

IEC 60947-2 defines two types of circuit breaker defined by their “selectivity category”:

  • Selectivity category B comprises circuit breakers providing selectivity by having a short-time withstand current rating and an associated short-time delay. For this category of circuit breaker, manufacturer shall provide the value of short-circuit current (Icw) that can be withstood for a specified time.

It is possible to delay the tripping of this type circuit breaker, where the fault-current level is lower than this short-time withstand current rating (Icw) (see Figure H32).

This is generally applied to power open type or “Air” circuit breakers and to certain heavy-duty molded-case types. Icw is the maximum current that the B category circuit breaker can withstand, thermally and electrodynamically, without sustaining damage, for a period of time given by the manufacturer.

Fig. H32 – Category B circuit-breaker
  • Selectivity category A comprises all other circuit breakers. This category of circuit breaker has no deliberate delay in the operation of the “instantaneous” short-circuit magnetic tripping device (see Figure H33). Usually molded-case type circuit breakers or modular circuit breaker are category A These circuit breakers may provide selectivity under short-circuit conditions by other means. But manufacturer will not provide Icw value.
Fig. H33 – Category A circuit-breaker

Rated making capacity (Icm)

Icm is the highest instantaneous value of current that the circuit-breaker can establish at rated voltage in specified conditions. In AC systems this instantaneous peak value is related to Icu (i.e. to the rated breaking current) by the factor k, which depends on the power factor (cos φ) of the short-circuit current loop (as shown in Figure H34 ).

Fig. H34 – Relation between rated breaking capacity Icu and rated making capacity Icm at different power-factor values of short-circuit current, as standardized in IEC 60947-2
Icu cosφ Icm = kIcu
6 kA < Icu ≤ 10 kA 0.5 1.7 x Icu
10 kA < Icu ≤ 20 kA 0.3 2 x Icu
20 kA < Icu ≤ 50 kA 0.25 2.1 x Icu
50 kA ≤ Icu 0.2 2.2 x Icu

Example: A Masterpact NW08H2 circuit-breaker has a rated breaking capacity Icu of 100 kA. The peak value of its rated making capacity Icm will be 100 x 2.2 = 220 kA.

Rated service short-circuit breaking capacity (Ics)

The rated breaking capacity (Icu) or (Icn) is the maximum fault-current a circuit-breaker can successfully interrupt without being damaged. The probability of such a current occurring is extremely low, and in normal circumstances the fault-currents are considerably less than the rated breaking capacity (Icu) of the CB. On the other hand it is important that high currents (of low probability) be interrupted under good conditions, so that the CB is immediately available for reclosure, after the faulty circuit has been repaired. It is for these reasons that a new characteristic (Ics) has been created, expressed as a percentage of Icu, viz: 25, 50, 75, 100% for industrial circuit-breakers. The standard test sequence is as follows:

  • O - CO - CO[1] (at Ics)
  • Tests carried out following this sequence are intended to verify that the CB is in a good state and available for normal service

For domestic CBs, Ics = k Icn. The factor k values are given in IEC 60898 table XIV.

In Europe it is the industrial practice to use a k factor of 100% so that Ics = Icu.

Fault-current limitation

Many designs of LV circuit-breakers feature a short-circuit current limitation capability, whereby the current is reduced and prevented from reaching its (otherwise) maximum peak value (see Figure H35). The current-limitation performance of these CBs is presented in the form of graphs, typified by that shown in Figure H36, diagram (a)

The fault-current limitation capacity of a CB concerns its ability, more or less effective, in preventing the passage of the maximum prospective fault-current, permitting only a limited amount of current to flow, as shown in Figure H35.

Fig. H35 – Prospective and actual currents

The current-limitation performance is given by the CB manufacturer in the form of curves (see Fig. H36).

  • Diagram (a) shows the limited peak value of current plotted against the rms value of the AC component of the prospective fault current (“prospective” fault-current refers to the fault-current which would flow if the CB had no current-limiting capability)
  • Limitation of the current greatly reduces the thermal stresses (proportional I2t) and this is shown by the curve of diagram (b) of Figure H36, again, versus the rms value of the AC component of the prospective fault current.

LV circuit-breakers for domestic and similar installations are classified in certain standards (notably European Standard EN 60 898). CBs belonging to one class (of current limiters) have standardized limiting I2t let-through characteristics defined by that class.

In these cases, manufacturers do not normally provide characteristic performance curves.

The advantages of current limitation

Current limitation reduces both thermal and electrodynamic stresses on all circuit elements through which the current passes, thereby prolonging the useful life of these elements. Furthermore, the limitation feature allows “cascading” techniques to be used (see Coordination between circuit-breakers) thereby significantly reducing design and installation costs

The use of current-limiting CBs affords numerous advantages:

  • Better conservation of installation networks: current-limiting CBs strongly attenuate all harmful effects associated with short-circuit currents
  • Reduction of thermal effects: Conductors (and therefore insulation) heating is significantly reduced, so that the life of cables is correspondingly increased
  • Reduction of mechanical effects: forces due to electromagnetic repulsion are lower, with less risk of deformation and possible rupture, excessive burning of contacts, etc.
  • Reduction of electromagnetic-interference effects:
    • Less influence on measuring instruments and associated circuits, telecommunication systems, etc.

These circuit-breakers therefore contribute towards an improved exploitation of:

  • Cables and wiring
  • Prefabricated cable-trunking systems
  • Switchgear, thereby reducing the ageing of the installation

Example

On a system having a prospective shortcircuit current of 150 kA rms, a Compact L circuit-breaker limits the peak current to less than 10% of the calculated prospective peak value, and the thermal effects to less than 1% of those calculated.

Cascading of the several levels of distribution in an installation, downstream of a limiting CB, will also result in important savings.

The technique of cascading allows, in fact, substantial savings on switchgear (lower performance permissible downstream of the limiting CB(s)) enclosures, and design studies, of up to 20% (overall).

Selective protection schemes and cascading are compatible, in the Compact NSX range, up to the full short-circuit breaking capacity of the switchgear.

Notes

  1. ^ O represents an opening operation.
    CO represents a closing operation followed by an opening operation.
Share