If the impedance of the parallel earthing conductor PEC (Z sup) is very low compared to Z sign, most of the disturbing current flows via the PEC, i.e. not via the signal line as in the previous case.<br> | If the impedance of the parallel earthing conductor PEC (Z sup) is very low compared to Z sign, most of the disturbing current flows via the PEC, i.e. not via the signal line as in the previous case.<br> | ||
The difference in potential between devices 1 and 2 becomes very low and the disturbance acceptable. }} | The difference in potential between devices 1 and 2 becomes very low and the disturbance acceptable. }} | ||
Latest revision as of 09:49, 22 June 2022
Definition
Two or more devices are interconnected by the power supply and communication cables (see Fig. R30). When external currents (lightning, fault currents, disturbances) flow via these common-mode impedances, an undesirable voltage appears between points A and B which are supposed to be equipotential. This stray voltage can disturb low-level or fast electronic circuits.
All cables, including the protective conductors, have an impedance, particularly at high frequencies.
Examples
(see Fig. R31)
- Devices linked by a common reference conductor (e.g. PEN, PE) affected by fast or intense (di/dt) current variations (fault current, lightning strike, short-circuit, load changes, chopping circuits, harmonic currents, power factor correction capacitor banks, etc.)
- A common return path for a number of electrical sources
Counter-measures
(see Fig. R32)
If they cannot be eliminated, common-mode impedances must at least be as low as possible. To reduce the effects of common-mode impedances, it is necessary to:
- Reduce impedances:
- Mesh the common references,
- Use short cables or flat braids which, for equal sizes, have a lower impedance than round cables,
- Install functional equipotential bonding between devices.
- Reduce the level of the disturbing currents by adding common-mode filtering and differential-mode inductors