The c.s.a. and the protection of the neutral conductor, apart from its current-carrying requirement, depend on several factors, namely:  
The c.s.a. and the protection of the neutral conductor, apart from its current-carrying requirement, depend on several factors, namely:  


Line 7: Line 6:
*The method of protection against indirect contact hazards according to the methods described below
*The method of protection against indirect contact hazards according to the methods described below


&nbsp;&nbsp;&nbsp;The color of the neutral conductor is statutorily blue. PEN conductor, when insulated, shall be marked by one of the following&nbsp;<br>&nbsp;&nbsp;&nbsp;methods:  
The color of the neutral conductor is statutorily blue. PEN conductor, when insulated, shall be marked by one of the following methods:  


*Green-and-yellow throughout its length with, in addition, light blue markings at the terminations, or  
*Green-and-yellow throughout its length with, in addition, light blue markings at the terminations, or  
*Light blue throughout its length with, in addition, green-and-yellow markings at the terminations
*Light blue throughout its length with, in addition, green-and-yellow markings at the terminations


 
{{Section-TOC}}
{| cellpadding="1" style="border: 1px solid #8888aa; background: #f7f8ff; padding: 5px; "
|
'''Contents:'''
* [[Sizing the neutral conductor|Sizing the neutral conductor]]
* [[Protection of the neutral conductor|Protection of the neutral conductor]]
* [[Breaking of the neutral conductor|Breaking of the neutral conductor]]
* [[Isolation of the neutral conductor|Isolation of the neutral conductor]]
|}
 
[[ru:Нейтральный провод]]

Latest revision as of 07:34, 4 August 2022

The c.s.a. and the protection of the neutral conductor, apart from its current-carrying requirement, depend on several factors, namely:

  • The type of earthing system, TT, TN, etc.
  • The harmonic currents
  • The method of protection against indirect contact hazards according to the methods described below

The color of the neutral conductor is statutorily blue. PEN conductor, when insulated, shall be marked by one of the following methods:

  • Green-and-yellow throughout its length with, in addition, light blue markings at the terminations, or
  • Light blue throughout its length with, in addition, green-and-yellow markings at the terminations