Worked example of cable calculation: Difference between revisions
(Created page with 'Worked example of cable calculation (see Fig. G65)<br>The installation is supplied through a 630 kVA transformer. The process requires a high degree of supply continuity and part…') |
mNo edit summary |
||
Line 1: | Line 1: | ||
Worked example of cable calculation (see Fig. G65)<br>The installation is supplied through a 630 kVA transformer. The process requires a high degree of supply continuity and part of the installation can be supplied by a 250 kVA standby generator. The global earthing system is TN-S, except for the most critical loads supplied by an isolation transformer with a downstream IT configuration.<br>The single-line diagram is shown in Figure G65 below. The results of a computer study for the circuit from transformer T1 down to the cable C7 is reproduced on Figure G66. This study was carried out with Ecodial 3.4 software (a Schneider Electric product).<br>This is followed by the same calculations carried out by the simplified method described in this guide. | Worked example of cable calculation (see '''Fig. G65''')<br>The installation is supplied through a 630 kVA transformer. The process requires a high degree of supply continuity and part of the installation can be supplied by a 250 kVA standby generator. The global earthing system is TN-S, except for the most critical loads supplied by an isolation transformer with a downstream IT configuration.<br>The single-line diagram is shown in Figure G65 below. The results of a computer study for the circuit from transformer T1 down to the cable C7 is reproduced on Figure G66. This study was carried out with Ecodial 3.4 software (a Schneider Electric product).<br>This is followed by the same calculations carried out by the simplified method described in this guide. | ||
---- | ---- | ||
'''''Fig. G65:'''''<i>Example of single-line diagram</i> | '''''Fig. G65:'''''<i>Example of single-line diagram</i> | ||
---- | ---- | ||
Line 11: | Line 11: | ||
---- | ---- | ||
'''''Fig. G66:'''''<i>Partial results of calculation carried out with Ecodial 3.4 software (Schneider Electric)</i> | '''''Fig. G66:'''''<i>Partial results of calculation carried out with Ecodial 3.4 software (Schneider Electric)</i> | ||
---- | ---- | ||
Line 19: | Line 19: | ||
*Dimensioning circuit C1 | *Dimensioning circuit C1 | ||
The MV/LV 630 kVA transformer has a rated no-load voltage of 420 V. Circuit C1 must be suitable for a current of:<br>Two single-core PVC-insulated copper cables in parallel will be used for each phase.These cables will be laid on cable trays according to method F.<br>Each conductor will therefore carry 433A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 240mm².<br>The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 5 metres, are: | The MV/LV 630 kVA transformer has a rated no-load voltage of 420 V. Circuit C1 must be suitable for a current of:<br>Two single-core PVC-insulated copper cables in parallel will be used for each phase.These cables will be laid on cable trays according to method F.<br>Each conductor will therefore carry 433A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 240mm².<br>The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 5 metres, are: | ||
(cable resistance: 22.5 mΩ.mm2/m) | (cable resistance: 22.5 mΩ.mm2/m) | ||
X = 0,08 x 5 = 0,4 mΩ (cable reactance: 0.08 mΩ/m) | X = 0,08 x 5 = 0,4 mΩ (cable reactance: 0.08 mΩ/m) | ||
*Dimensioning circuit C3 | |||
<br> | Circuit C3 supplies two 150kW loads with cos φ = 0.85, so the total load current is: | ||
Two single-core PVC-insulated copper cables in parallel will be used for each phase. These cables will be laid on cable trays according to method F.<br>Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm².<br>The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 20 metres, are: | |||
*Dimensioning circuit C7 | |||
Circuit C7 supplies one 150kW load with cos φ = 0.85, so the total load current is: | |||
One single-core PVC-insulated copper cable will be used for each phase. The cables will be laid on cable trays according to method F.<br>Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm².<br>The resistance and the inductive reactance for a length of 20 metres is:<br> | One single-core PVC-insulated copper cable will be used for each phase. The cables will be laid on cable trays according to method F.<br>Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm².<br>The resistance and the inductive reactance for a length of 20 metres is:<br> | ||
<br> | |||
(cable resistance: 22.5 mΩ.mm2/m) | |||
(cable reactance: 0.08 mΩ/m) | |||
(cable reactance: 0.08 mΩ/m) | |||
*Calculation of short-circuit currents for the selection of circuit-breakers Q1, Q3, Q7 (see Fig. G67) | |||
---- | ---- | ||
Line 104: | Line 112: | ||
|} | |} | ||
'''''Fig. G67:'''''<i>Example of short-circuit current evaluation</i> | |||
'''''Fig. G67:'''''<i>Example of short-circuit current evaluation</i> | |||
---- | ---- | ||
*The protective conductor | |||
When using the adiabatic method, the minimum c.s.a. for the protective earth conductor (PE) can be calculated by the formula given in Figure G58: | |||
For circuit C1, I = 20.2kA and k = 143.<br>t is the maximum operating time of the MV protection, e.g. 0.5s<br>This gives: | |||
A single 120 mm2 conductor is therefore largely sufficient, provided that it also satisfies the requirements for indirect contact protection (i.e. that its impedance is sufficiently low).<br>Generally, for circuits with phase conductor c.s.a. Sph ≥ 50 mm2, the PE conductor minimum c.s.a. will be Sph / 2. Then, for circuit C3, the PE conductor will be 95mm2, and for circuit C7, the PE conductor will be 50mm2. | |||
*Protection against indirect-contact hazards | |||
For circuit C3 of Figure G65, Figures F41 and F40, or the formula given page F25 may be used for a 3-phase 4-wire circuit.<br>The maximum permitted length of the circuit is given by: | |||
(The value in the denominator 630 x 11 is the maximum current level at which the instantaneous short-circuit magnetic trip of the 630 A circuit-breaker operates).<br>The length of 20 metres is therefore fully protected by “instantaneous” over-current devices. | (The value in the denominator 630 x 11 is the maximum current level at which the instantaneous short-circuit magnetic trip of the 630 A circuit-breaker operates).<br>The length of 20 metres is therefore fully protected by “instantaneous” over-current devices. | ||
*Voltage drop | |||
The voltage drop is calculated using the data given in Figure G28, for balanced three-phase circuits, motor power normal service (cos φ = 0.8).<br>The results are summarized on figure G68:<br> | |||
---- | |||
<br> | |||
<br> | |||
'''''Fig. G68:'''''<i>Voltage drop introduced by the different cables</i> | '''''Fig. G68:'''''<i>Voltage drop introduced by the different cables</i> | ||
---- | ---- | ||
The total voltage drop at the end of cable C7 is then: 0.77%. | The total voltage drop at the end of cable C7 is then: 0.77%. | ||
---- | ---- |
Revision as of 09:41, 27 January 2010
Worked example of cable calculation (see Fig. G65)
The installation is supplied through a 630 kVA transformer. The process requires a high degree of supply continuity and part of the installation can be supplied by a 250 kVA standby generator. The global earthing system is TN-S, except for the most critical loads supplied by an isolation transformer with a downstream IT configuration.
The single-line diagram is shown in Figure G65 below. The results of a computer study for the circuit from transformer T1 down to the cable C7 is reproduced on Figure G66. This study was carried out with Ecodial 3.4 software (a Schneider Electric product).
This is followed by the same calculations carried out by the simplified method described in this guide.
Fig. G65:Example of single-line diagram
Calculation using software Ecodial 3.3
Fig. G66:Partial results of calculation carried out with Ecodial 3.4 software (Schneider Electric)
The same calculation using the simplified method recommended in this guide
- Dimensioning circuit C1
The MV/LV 630 kVA transformer has a rated no-load voltage of 420 V. Circuit C1 must be suitable for a current of:
Two single-core PVC-insulated copper cables in parallel will be used for each phase.These cables will be laid on cable trays according to method F.
Each conductor will therefore carry 433A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 240mm².
The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 5 metres, are:
(cable resistance: 22.5 mΩ.mm2/m)
X = 0,08 x 5 = 0,4 mΩ (cable reactance: 0.08 mΩ/m)
- Dimensioning circuit C3
Circuit C3 supplies two 150kW loads with cos φ = 0.85, so the total load current is:
Two single-core PVC-insulated copper cables in parallel will be used for each phase. These cables will be laid on cable trays according to method F.
Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm².
The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 20 metres, are:
- Dimensioning circuit C7
Circuit C7 supplies one 150kW load with cos φ = 0.85, so the total load current is:
One single-core PVC-insulated copper cable will be used for each phase. The cables will be laid on cable trays according to method F.
Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm².
The resistance and the inductive reactance for a length of 20 metres is:
(cable resistance: 22.5 mΩ.mm2/m)
(cable reactance: 0.08 mΩ/m)
- Calculation of short-circuit currents for the selection of circuit-breakers Q1, Q3, Q7 (see Fig. G67)
Fig. G67:Example of short-circuit current evaluation
- The protective conductor
When using the adiabatic method, the minimum c.s.a. for the protective earth conductor (PE) can be calculated by the formula given in Figure G58:
For circuit C1, I = 20.2kA and k = 143.
t is the maximum operating time of the MV protection, e.g. 0.5s
This gives:
A single 120 mm2 conductor is therefore largely sufficient, provided that it also satisfies the requirements for indirect contact protection (i.e. that its impedance is sufficiently low).
Generally, for circuits with phase conductor c.s.a. Sph ≥ 50 mm2, the PE conductor minimum c.s.a. will be Sph / 2. Then, for circuit C3, the PE conductor will be 95mm2, and for circuit C7, the PE conductor will be 50mm2.
- Protection against indirect-contact hazards
For circuit C3 of Figure G65, Figures F41 and F40, or the formula given page F25 may be used for a 3-phase 4-wire circuit.
The maximum permitted length of the circuit is given by:
(The value in the denominator 630 x 11 is the maximum current level at which the instantaneous short-circuit magnetic trip of the 630 A circuit-breaker operates).
The length of 20 metres is therefore fully protected by “instantaneous” over-current devices.
- Voltage drop
The voltage drop is calculated using the data given in Figure G28, for balanced three-phase circuits, motor power normal service (cos φ = 0.8).
The results are summarized on figure G68:
Fig. G68:Voltage drop introduced by the different cables
The total voltage drop at the end of cable C7 is then: 0.77%.