==== Sensors ====
==== Sensors ====


Sensors provide data to the monitoring systems and include:
Sensors provide data to the monitoring systems and include:  


*A sensor for measuring instantaneous luminous flux such as a pyranometer (heat flow sensor used to measure the quantity of solar energy in natural light (W/m<sup>2</sup>), see '''Fig. P20'''). This is the standard reference for the installation. It may be used to identify shifts over time and is recommended to all suppliers wishing to conduct comparative analyses and compile statistics for their installations.
*A sensor for measuring instantaneous luminous flux such as a pyranometer (heat flow sensor used to measure the quantity of solar energy in natural light (W/m<sup>2</sup>), see '''Fig. P20'''). This is the standard reference for the installation. It may be used to identify shifts over time and is recommended to all suppliers wishing to conduct comparative analyses and compile statistics for their installations.
Line 43: Line 43:
----
----


'''''Fig. P20:'''''<i>Pyranometer –&nbsp;Kipp &amp; Zonen</i>
<br>[[Image:Fig P20.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. P20:'''''<i>&nbsp;Pyranometer –&nbsp;Kipp &amp; Zonen</i>  


----
----


A temperature sensor – this is an important factor for photovoltaic power supply (see Paragraph 2.1). This sensor either serves as an external probe or is attached to the back of a module.
*A temperature sensor – this is an important factor for photovoltaic power supply. This sensor either serves as an external probe or is attached to the back of a module.  
*A kilowatt hour meter
*A kilowatt hour meter



Revision as of 09:19, 17 February 2010

Since the profitability of photovoltaic installations depends mainly on them being operational, it is essential to ensure that they are permanently functional. The best way of ensuring this is to acquire a monitoring system for the installation. This system should notify all faults immediately and be capable of detecting drifts in output.

Types of monitoring

Several types of monitoring are available for installations:

  • Systems which communicate with the inverters and are able to monitor all electrical values relating to output from the installation as well as the condition of the inverters
  • Systems without communication protocols for the inverters but fitted with measurement inputs capable of monitoring photovoltaic output
  • Hybrid systems supplementing information from the inverters with measurements which are external to the installation such as solar radiation and temperature. Information on the modules at the output of the inverters can only be correlated across the installation as a whole by systems capable of measuring solar radiation. Indeed, since output forecasts generally rely on meteorological statistics, it is quite difficult to interpret output data without correlating them to actual solar radiation. An abnormally low level of output may be caused by:

  - A low level of solar radiation over a certain period of time (and which is abnormal based on meteorological statistics)
  - A problem with the modules (clogging, shade, connection fault, etc.)
  - A functional problem with the inverter
It is only possible to identify these faults by equipping the installation with solar radiation and temperature sensors and comparing the output capacity with actual output.
Depending on the size of the installation, individual monitoring or monitoring by group of photovoltaic module strings may be possible in order to detect abnormal variations in output between strings.

Monitoring systems

These systems may be autonomous or include remote monitoring.

  • Autonomous systems (see Fig. P18)

Once data is collected locally, the system sends alerts directly to the maintenance operators as soon as they are generated.



Fig P18 GB.jpg




















Fig. P18: Example of an autonomous monitoring system


  • With remote monitoring (see Fig. P19)

Once the data is collected locally, the system sends output data and alerts as soon as they are generated to a remote monitoring system capable of managing stand-by periods for maintenance work. This enables the installation to be monitored closely, which is essential for multi-site installations or where operators of photovoltaic installations are not necessarily the site occupants.



Fig P19 GB.jpg

























Fig. P19: Example of a system for remote monitoring


Sensors

Sensors provide data to the monitoring systems and include:

  • A sensor for measuring instantaneous luminous flux such as a pyranometer (heat flow sensor used to measure the quantity of solar energy in natural light (W/m2), see Fig. P20). This is the standard reference for the installation. It may be used to identify shifts over time and is recommended to all suppliers wishing to conduct comparative analyses and compile statistics for their installations.


Fig P20.jpg













Fig. P20: Pyranometer – Kipp & Zonen


  • A temperature sensor – this is an important factor for photovoltaic power supply. This sensor either serves as an external probe or is attached to the back of a module.
  • A kilowatt hour meter

When selling power, only the kilowatt hour meter operated by the energy distributor purchasing the electricity may be used as a reference.
The other meters fitted within an installation (in the inverter or next to the official meter) are only indicators with their own specific levels of accuracy. Variations of more than 10% may occur between the values given by an installation’s devices and that given by the official meter. However, these variations are not only due to different levels of accuracy. They are also caused by energy lost in the cables and safety devices downstream from the inverter.
It is therefore important to use cables of minimal length and clearly identify:
  - The location where the installation will be connected to the network
  - The locations where the energy distributor’s meters will be connected

Monitoring the installation

Since modules are expensive and in some cases openly accessible, sites need to be monitored by security cameras.