Talk:Definition of standardised earthing schemes/Archive 1: Difference between revisions
(Created page with 'Is the following sentence related to TN-C system correct with or without "OR"? This system is not permitted for conductors of less than 10 mm2 '''''OR''''' for portable eq…') |
(→IEC60343-5-54 PEN: new section) |
||
Line 2: | Line 2: | ||
This system is not permitted for conductors of less than 10 mm2 '''''OR''''' for portable equipment. | This system is not permitted for conductors of less than 10 mm2 '''''OR''''' for portable equipment. | ||
== IEC60343-5-54 PEN == | |||
To be precise, the IEC60364 states: | |||
411.4.3 In fixed installations, a single conductor may serve both as a protective conductor | |||
and as a neutral conductor (PEN conductor) provided that the requirements of 543.4 of | |||
IEC 60364-5-54 are satisfied. No switching or isolating device shall be inserted in the PEN | |||
conductor. | |||
543.4.1 A PEN conductor may only be used in fixed electrical installations and, for | |||
mechanical reasons, shall have a cross-sectional area not less than 10 mm2 in copper or | |||
16 mm² in aluminium. | |||
So TNC can not be used for portable equipment, and when used for fixed installation PEN shall have S>=10mm2 If active conductors' size is lower, it's usually cheaper to go to TNS. | |||
--[[User:Mathieu GUILLOT|Mathieu GUILLOT]] 08:42, 30 April 2010 (UTC) |
Revision as of 08:42, 30 April 2010
Is the following sentence related to TN-C system correct with or without "OR"?
This system is not permitted for conductors of less than 10 mm2 OR for portable equipment.
IEC60343-5-54 PEN
To be precise, the IEC60364 states:
411.4.3 In fixed installations, a single conductor may serve both as a protective conductor and as a neutral conductor (PEN conductor) provided that the requirements of 543.4 of IEC 60364-5-54 are satisfied. No switching or isolating device shall be inserted in the PEN conductor.
543.4.1 A PEN conductor may only be used in fixed electrical installations and, for mechanical reasons, shall have a cross-sectional area not less than 10 mm2 in copper or 16 mm² in aluminium.
So TNC can not be used for portable equipment, and when used for fixed installation PEN shall have S>=10mm2 If active conductors' size is lower, it's usually cheaper to go to TNS. --Mathieu GUILLOT 08:42, 30 April 2010 (UTC)