== Procedures for harmonic measurement==
== Procedures for harmonic measurement==


'''Harmonic measurements are carried out on industrial or commercial sites:'''
==== Harmonic measurements are carried out on industrial or commercial sites:====
* Preventively, to obtain an overall idea on distribution-network status (network mapping),
* Preventively, to obtain an overall idea on distribution-network status (network mapping),
* In view of corrective action, to determine the origin of a disturbance and determine the solutions required to eliminate it,
* In view of corrective action, to determine the origin of a disturbance and determine the solutions required to eliminate it,
* To check the validity of a solution (followed by modifications in the distribution network to check the reduction of harmonic disturbances)
* To check the validity of a solution (following modifications in the distribution network to check the reduction of harmonic disturbances)


'''The harmonic indicators can be measured:'''
==== The harmonic indicators can be measured:====
* By an expert present on the site for a limited period of time (one day), giving precise, but limited perception,
* By an expert present on the site for a limited period of time (one day), giving precise, but limited perception,
* By instrumentation devices installed and operating for a significant period of time (at least one week) giving a reliable overview of the situation,
* By instrumentation devices installed and operating for a significant period of time (at least one week) giving a reliable overview of the situation,
Line 46: Line 44:


The diagnosis may be improved by the use of additional dedicated equipment in case of specific problem.
The diagnosis may be improved by the use of additional dedicated equipment in case of specific problem.


== Harmonic measurement devices ==
== Harmonic measurement devices ==
Line 63: Line 60:
In order to meet the Power Quality objectives, 95% of the measured values should be less than specified values.
In order to meet the Power Quality objectives, 95% of the measured values should be less than specified values.


'''Fig. M10''' gives the maximum harmonic voltage in order to meet the requirements of standard EN50160: "Voltage characteristics of electricity supplied by public distribution networks", for Low and Medium Voltage.
{{FigRef|M10}} gives the maximum harmonic voltage in order to meet the requirements of standard EN50160: "Voltage characteristics of electricity supplied by public distribution networks", for Low and Medium Voltage.


{| style="width: 789px; height: 194px" cellspacing="1" cellpadding="1" width="789" border="1"
{{tb-start|id=Tab1350|num=M10|title=Values of individual harmonic voltages at the supply terminals for orders up to 25 given in percent of the fundamental voltage U<sub>1</sub>|cols=5}}
{| class="wikitable"
|-
|-
| valign="top" bgcolor="#0099cc" colspan="2" | '''Odd harmonic <br>non-multiples of 3'''
! colspan="2" | Odd harmonic  
| valign="top" bgcolor="#0099cc" colspan="2" | '''Odd harmonic <br> multiples of 3'''
non-multiples of 3  
| valign="top" bgcolor="#0099cc" colspan="2" | '''Even harmonic'''
! colspan="2" | Odd harmonic  
multiples of 3  
! colspan="2" | Even harmonic
|-
|-
| '''Order h'''
! '''Order h'''
| '''Relative amplitude <br> U<sub>h</sub>: %'''  
! '''Relative amplitude <br> U<sub>h</sub>: %'''  
| '''Order h'''  
! '''Order h'''  
| '''Relative amplitude <br> U<sub>h</sub>: %'''  
! '''Relative amplitude <br> U<sub>h</sub>: %'''  
| '''Order h'''  
! '''Order h'''  
| '''Relative amplitude <br> U<sub>h</sub>: %'''   
! '''Relative amplitude <br> U<sub>h</sub>: %'''   
|-
|-
| 5
| 5
Line 103: Line 103:
| 21
| 21
| 0.5  
| 0.5  
| &nbsp;
|  
| &nbsp;
|  
|-
|-
| 17
| 17
| 2
| 2
| &nbsp;
|  
| &nbsp;
|  
| &nbsp;
|  
| &nbsp;
|  
|-
|-
| 19
| 19
| 1.5
| 1.5
| &nbsp;
|  
| &nbsp;
|  
| &nbsp;
|  
| &nbsp;
|  
|-
|-
| 123
| 23
| 1.5
| 1.5
| &nbsp;
|  
| &nbsp;
|  
| &nbsp;
|  
| &nbsp;
|  
|-
|-
| 25
| 25
| 1.5
| 1.5
| &nbsp;
|  
| &nbsp;
|  
| &nbsp;
|  
| &nbsp;
|  
|}
|}
'''''Fig. M10 :''''' ''Values of individual harmonic voltages at the supply terminals for orders up to 25 given in percent of the fundamental voltage U<sub>1</sub>''


=== Portable instruments ===
=== Portable instruments ===
Line 141: Line 140:


==== Oscilloscope ====
==== Oscilloscope ====
An initial indication on the distortion affecting a signal can be obtained by viewing the current or the voltage on an oscilloscope.<br>
 
The waveform, when it diverges from a sinusoidal, clearly indicates the presence of harmonics. Current and voltage peaks can be observed.<br>
An initial indication on the distortion affecting a signal can be obtained by viewing the current or the voltage on an oscilloscope.
 
The waveform, when it diverges from a sinusoidal, clearly indicates the presence of harmonics. Current and voltage peaks can be observed.
 
Note, however, that this method does not offer precise quantification of the harmonic components.
Note, however, that this method does not offer precise quantification of the harmonic components.


==== Digital analyser ====
==== Digital analyser ====
Only recent digital analysers can determine the values of all the mentioned indicators with sufficient accuracy. <br>
 
They are using digital technology, specifically a high performance algorithm called Fast Fourier Transform (FFT). Current or voltage signals are digitized and the algorithm is applied on data relative to time windows of 10 (50Hz systems) or 12
Only recent digital analysers can determine the values of all the mentioned indicators with sufficient accuracy.  
periods (for 60Hz systems) of the power frequency.<br>
 
They are using digital technology, specifically a high performance algorithm called Fast Fourier Transform (FFT). Current or voltage signals are digitized and the algorithm is applied on data relative to time windows of 10 (50Hz systems) or 12 periods (for 60Hz systems) of the power frequency.
 
The amplitude and phase of harmonics up to the 40th or 50th order are calculated, depending on the class of measurement.
The amplitude and phase of harmonics up to the 40th or 50th order are calculated, depending on the class of measurement.


Processing of the successive values calculated using the FFT (smoothing, classification, statistics) can be carried out by the measurement device or by external software.
Processing of the successive values calculated using the FFT (smoothing, classification, statistics) can be carried out by the measurement device or by external software.


'''Functions of digital analysers'''
=== Functions of digital analysers ===
 
* Calculate the values of the harmonic indicators (power factor, crest factor, individual harmonic amplitude, THD)
* Calculate the values of the harmonic indicators (power factor, crest factor, individual harmonic amplitude, THD)
* In multi-channel analysers, supply virtually in real time the simultaneous spectral decomposition of the currents and voltages
* In multi-channel analysers, supply virtually in real time the simultaneous spectral decomposition of the currents and voltages
Line 159: Line 164:
* Storage of data
* Storage of data


[[Image:Fig_M11.jpg|none]]
{{FigImage|PB116800|jpg|M11|Implementation of a digital Power Quality recorder in a cabinet}}
'''''Fig. M11 :''''' ''Implementation of a digital Power Quality recorder in a cabinet''


=== Fixed instruments ===
=== Fixed instruments ===
Panel instrumentation provides continuous information to the Manager of the electrical installation. Data can be accessible through dedicated power monitoring devices or through the digital trip units of circuit breakers.
Panel instrumentation provides continuous information to the Manager of the electrical installation. Data can be accessible through dedicated power monitoring devices or through the digital trip units of circuit breakers.
[[Image:Fig_M12.jpg|none|150px]]
'''''Fig. M12 :''''' ''Example of Power and Energy meter''


[[Image:Fig_M13.jpg|none|500px]]
{{FigImage|PB116801|jpg|M12|Example of Power and Energy meter}}
'''''Fig. M13 :''''' ''Example of electronic trip units of circuit-breakers providing harmonic related information''


{{Gallery|M13|Example of electronic trip units of circuit-breakers providing harmonic related information||
|PB116184-45.jpg||
|PB116047-4.jpg||
|PB116804.jpg||
}}


== Which harmonic orders must be monitored and mitigated?==
== Which harmonic orders must be monitored and mitigated?==
Line 183: Line 189:


Harmonic amplitudes normally decrease as the frequency increases. Sufficiently accurate measurements are obtained by measuring harmonics up to order 30.
Harmonic amplitudes normally decrease as the frequency increases. Sufficiently accurate measurements are obtained by measuring harmonics up to order 30.
[[ru:Измерение показателей гармоник]]
[[zh:谐波指标的测量]]

Latest revision as of 09:48, 22 June 2022

Procedures for harmonic measurement

Harmonic measurements are carried out on industrial or commercial sites:

  • Preventively, to obtain an overall idea on distribution-network status (network mapping),
  • In view of corrective action, to determine the origin of a disturbance and determine the solutions required to eliminate it,
  • To check the validity of a solution (following modifications in the distribution network to check the reduction of harmonic disturbances)

The harmonic indicators can be measured:

  • By an expert present on the site for a limited period of time (one day), giving precise, but limited perception,
  • By instrumentation devices installed and operating for a significant period of time (at least one week) giving a reliable overview of the situation,
  • Or by devices permanently installed in the distribution network, allowing a follow-up of Power Quality.

One-shot or corrective actions

This kind of action is carried-out in case of observed disturbances, for which harmonics are suspected. In order to determine the origin of the disturbances, measurements of current and voltage are performed:

  • At the supply source level,
  • On the busbars of the main distribution switchboard (or on the MV busbars),
  • On each outgoing circuit in the main distribution switchboard (or on the MV busbars).

For accurate results, it is necessary to know the precise operating conditions of the installation and particularly the status of the capacitor banks (operating or not, number of connected steps).

The results of measurement will help the analysis in order to:

  • Determine any necessary derating of equipment in the installation, or
  • Quantify any necessary harmonic protection and filtering systems to be installed in the distribution network, or
  • Check the compliance of the electrical installation with the applicable standards or Utility regulations (maximum permissible harmonic emission).

Long-term or preventive actions

For a number of reasons, the installation of permanent measurement devices in the distribution network is very valuable.

  • The presence of an expert on site is limited in time and it is not always possible to observe all the possible situations. Only a number of measurements at different points in the installation and over a sufficiently long period (one week to a month) provide an overall view of operation and take into account all the situations that can occur following:
    • Fluctuations in the supply source,
    • Variations in the operation of the installation,
    • The addition of new equipment in the installation.
  • Measurement devices installed in the distribution network prepare and facilitate the diagnosis of the experts, thus reducing the number and duration of their visits.
  • Permanent measurement devices detect any new disturbances arising following the installation of new equipment, the implementation of new operating modes or fluctuations in the supply network.
  • For an overall evaluation of network status (preventive analysis), this avoids:
    • Renting of measurement equipment,
    • Calling in experts,
    • Having to connect and disconnect the measurement equipment. For the overall evaluation of network status, the analysis on the main low-voltage distribution switchboards (MLVS) can often be carried out by the incoming device and/or the measurement devices equipping each outgoing circuit,
  • For corrective actions, it is possible to:
    • Determine the operating conditions at the time of the incident,
    • Draw-up a map of the distribution network and evaluate the implemented solution.

The diagnosis may be improved by the use of additional dedicated equipment in case of specific problem.

Harmonic measurement devices

Measurement devices provide instantaneous and average information concerning harmonics. Instantaneous values are used for analysis of disturbances linked to harmonics. Average values are used for Power Quality assessment.

The most recent measurement devices are designed referring to IEC standard 61000-4-7: "Electromagnetic compatibility (EMC) – Part 4-7: Testing and measurement techniques – General guide on harmonics and interharmonics measurements and instrumentation, for power supply systems and equipment connected thereto".

The supplied values include:

  • The harmonic spectrum of currents and voltages (amplitudes and percentage of the fundamental),
  • The THD for current and voltage,
  • For specific analysis: the phase angle between harmonic voltage and current of the same order and the phase of the harmonics with respect to a common reference (e.g. the fundamental voltage).

Average values are indicators of the long-term Power Quality. Typical and relevant statistical data are for example measures averaged by periods of 10 minutes, during observation periods of 1 week.

In order to meet the Power Quality objectives, 95% of the measured values should be less than specified values.

Fig. M10 gives the maximum harmonic voltage in order to meet the requirements of standard EN50160: "Voltage characteristics of electricity supplied by public distribution networks", for Low and Medium Voltage.

Fig. M10 – Values of individual harmonic voltages at the supply terminals for orders up to 25 given in percent of the fundamental voltage U1
Odd harmonic

non-multiples of 3

Odd harmonic

multiples of 3

Even harmonic
Order h Relative amplitude
Uh: %
Order h Relative amplitude
Uh: %
Order h Relative amplitude
Uh: %
5 6 3 5 2 2
7 5 9 1.5 4 1
11 3.5 15 0.5 6...24 0.5
13 3 21 0.5
17 2
19 1.5
23 1.5
25 1.5

Portable instruments

The traditional observation and measurement methods include:

Oscilloscope

An initial indication on the distortion affecting a signal can be obtained by viewing the current or the voltage on an oscilloscope.

The waveform, when it diverges from a sinusoidal, clearly indicates the presence of harmonics. Current and voltage peaks can be observed.

Note, however, that this method does not offer precise quantification of the harmonic components.

Digital analyser

Only recent digital analysers can determine the values of all the mentioned indicators with sufficient accuracy.

They are using digital technology, specifically a high performance algorithm called Fast Fourier Transform (FFT). Current or voltage signals are digitized and the algorithm is applied on data relative to time windows of 10 (50Hz systems) or 12 periods (for 60Hz systems) of the power frequency.

The amplitude and phase of harmonics up to the 40th or 50th order are calculated, depending on the class of measurement.

Processing of the successive values calculated using the FFT (smoothing, classification, statistics) can be carried out by the measurement device or by external software.

Functions of digital analysers

  • Calculate the values of the harmonic indicators (power factor, crest factor, individual harmonic amplitude, THD)
  • In multi-channel analysers, supply virtually in real time the simultaneous spectral decomposition of the currents and voltages
  • Carry out various complementary functions (corrections, statistical detection, measurement management, display, communication, etc.)
  • Storage of data
Fig. M11 – Implementation of a digital Power Quality recorder in a cabinet

Fixed instruments

Panel instrumentation provides continuous information to the Manager of the electrical installation. Data can be accessible through dedicated power monitoring devices or through the digital trip units of circuit breakers.

Fig. M12 – Example of Power and Energy meter

Which harmonic orders must be monitored and mitigated?

The most significant harmonic orders in three-phase distribution networks are the odd orders (3, 5, 7, 9, 11, 13 ….)

Triplen harmonics (order multiple of 3) are present only in three-phase, four-wire systems, when single phase loads are connected between phase and neutral.

Utilities are mainly focusing on low harmonic orders (5, 7, 11, and 13).

Generally speaking, harmonic conditioning of the lowest orders (up to 13) is sufficient. More comprehensive conditioning takes into account harmonic orders up to 25.

Harmonic amplitudes normally decrease as the frequency increases. Sufficiently accurate measurements are obtained by measuring harmonics up to order 30.