Choice of MV/LV transformer: Difference between revisions

From Electrical Installation Guide
m (1 revision)
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "")
 
(18 intermediate revisions by 7 users not shown)
Line 1: Line 1:
{{Menu_Connection_to_the_MV_utility_distribution_network}}
{{Menu_Connection_to_the_MV_utility_distribution_network}}
<br>
The transformers shall comply with IEC 60076. A transformer is characterized by its electrical parameters, but also by its technology and its conditions of use.
 
== Characteristic parameters of a transformer ==
== Characteristic parameters of a transformer ==
{{Def
|Rated power|the apparent-power in kVA on which the values of the design parameters and the construction of the transformer are based. Manufacturing tests and guarantee refer to this rated power
|Frequency|for power distribution systems discussed in this guide, the frequency is either 50 Hz or 60 Hz
|Rated primary voltage|the service voltage of the electrical network on which the transformer in connected
|Rated secondary voltage|the voltage measured between the secondary terminals when the transformer is off load and energized at its rated primary voltage
|Transformer ratio|RMS value of the rated primary voltage divided by the RMS value of the rated secondary voltage
|Rated insulation levels|are defined by the values of the overvoltage power frequency withstand test, and high voltage lightning impulse tests. For the voltage levels considered in this guide, the encountered switching over voltages are generally lower than the expected lightning over voltages, so no over voltage switching tests are required for these voltages
|Off-load tap-Changer switch|allows to adjust the rated primary voltage and consequently the transformer ratio within the range ± 2.5 % and ± 5 %. The transformer must be de-energized before the operation of the switch
|Winding configurations|Star, Delta and Zigzag high and low voltage windings connections are defined by an alphanumeric code read from the left to the right. The first letter refers to the high voltage winding, the second letter to low voltage winding:}}
* Capital letters are used for the high voltage windings
**D = delta connection
**Y = star connection
**Z = zigzag connection
**N = neutral point brought out to a dedicated terminal
*Lower-case letters are used for the low voltage winding
**d = delta
**y = star
**z = interconnected-star (or zigzag)
**n = neutral point brought out to a dedicated terminal
* A number between 0 and 11 indicates the phase shifting between the primary and the secondary voltages.
* A common winding configuration used for distribution transformers is Dyn 11:
**High voltage primary windings connected in Delta
**Low voltage secondary windings connected in Star
**Low voltage neutral point brought out to a dedicated terminal.
**Phase shifting between the primary and the secondary voltage: 30°.


== Technology and utilization of the transformers ==


A transformer is characterized in part by its electrical parameters, but also by its technology and its conditions of use.<br>
There are two basic types of distribution transformer:
 
* Dry type (cast resin encapsulated) transformer
'''Electrical characteristics<br>'''
* Liquid filled (oil-immersed) transformer.
 
*Rated power (Pn): the conventional apparent-power in kVA on which other design-parameter values and the construction of the transformer are based. Manufacturing tests and guarantees are referred to this rating
*Frequency: for power distribution systems of the kind discussed in this guide, the frequency will be 50 Hz or 60 Hz
*Rated primary and secondary voltages: For a primary winding capable of operating at more than one voltage level, a kVA rating corresponding to each level must be given.
 
The secondary rated voltage is its open circuit value
 
*Rated insulation levels are given by overvoltage-withstand test values at power frequency, and by high voltage impulse tests values which simulate lightning discharges. At&nbsp;the voltage levels discussed in this guide, overvoltages caused by MV&nbsp;switching operations are generally less severe than those due to lightning, so that no separate tests for switching-surge withstand capability are made
*Off-circuit tap-selector switch generally allows a choice of up to ± 2.5% and ± 5% level about the rated voltage of the highest voltage winding. The transformer must be de-energized before this switch is operated
*Winding configurations are indicated in diagrammatic form by standard symbols for star, delta and inter-connected-star windings; (and combinations of these for special duty, e.g. six-or twelve-phase rectifier transformers, etc.) and in an IEC-recommended alphanumeric code. This code is read from left-to-right, the first letter refers to the highest voltage winding, the second letter to the next highest, and so on:
 
'''&nbsp; -''' Capital letters refer to the highest voltage winding<br>'''&nbsp; D''' = delta<br>'''&nbsp; Y''' = star<br>'''&nbsp; Z''' = interconnected-star (or zigzag)<br>'''&nbsp; N '''= neutral connection brought out to a terminal<br>&nbsp; '''-'''&nbsp;Lower-case letters are used for tertiary and secondary windings<br>'''&nbsp; d''' = delta<br>'''&nbsp; y''' = star<br>'''&nbsp; z''' = interconnected-star (or zigzag)<br>'''&nbsp; n''' = neutral connection brought out to a terminal<br>&nbsp; - A number from 0 to 11, corresponding to those, on a clock dial (“0” is used instead of “12”) follows any pair of letters to indicate the<br>&nbsp;&nbsp;&nbsp; phase change (if any) which occurs during the transformation.<br>A very common winding configuration used for distribution transformers is that of a Dyn 11 transformer, which has a delta MV&nbsp;winding with a star-connected secondary winding the neutral point of which is brought out to a terminal. The phase change through the transformer is +30&nbsp;degrees, i.e. phase 1 secondary voltage is at “11&nbsp;o’clock” when phase 1 of the primary voltage is at “12 o’clock”, as shown [[Media:FigB21.jpg|Figure B21]] which can be seen in the section [[The consumer substation with MV metering#Common winding arrangements|Common winding arrangements]]. All combinations of delta, star and zigzag windings produce a phase change which (if not zero) is either 30 degrees or a multiple of 30 degrees.<br>IEC 60076-4 describes the “clock code” in detail.  


'''Characteristics related to the technology and utilization of the transformer'''<br>This list is not exhaustive:  
According IEC 60076, the standard conditions of utilization of the transformers for outdoor and indoor installation are the following:
* Altitude ≤ 1000 m
* Maximum ambient temperature: 40 °C
* Monthly average temperature: 30 °C during the hottest month
* Annual average temperature: 20 °C.


*Choice of technology
=== For other service conditions ===
*For oil immersed transformer the IEC 60076-2 specifies the oil and winding temperature rise.
*For dry type transformer the IEC 60076-11 specifies the thermal class.


The insulating medium is:<br>&nbsp; - Liquid (mineral oil) or<br>&nbsp; - Solid (epoxy resin and air)
The temperature surrounding the transformer is linked to the outdoor service condition, its cooling mode and efficiency when installed in a room, and its load. Two loading guides can help to verify if the transformer is correctly defined according to the expected lifespan, which are respectively the IEC 60076-7 and IEC 60076-12.


*For indoor or outdoor installation
An annex within the HV/LV prefabricated substation standard IEC 62271-202 gives several examples of installation, based on these two guides.
*Altitude (&lt;= 1,000 m is standard)
*Temperature (IEC 60076-2)


&nbsp; - Maximum ambient air: 40 °C<br>&nbsp; - Daily maximum average ambient air: 30 °C<br>&nbsp; - Annual maximum average ambient air: 20 °C<br>For non-standard operating conditions, refer to “Influence of the Ambient temperature and altitude on the rated current”. <br>
==Dry type transformers==
(see {{FigRef|B38}})


== Description of insulation techniques ==
The dry type transformers shall comply with IEC 60076-11:


Each individual winding of these transformers is casted in resin according to a vacuum dedicated process.


There are two basic classes of distribution transformer presently available:
The high voltage winding, the low voltage winding and the frame are separate by air.


*Dry type (cast in resin)
The encapsulation of a winding uses three components:
*Liquid filled (oil-immersed)
* Epoxy-resin based on biphenol A with a viscosity that ensures complete impregnation of the windings
* Anhydride hardener modified to introduce a degree of resilience in the moulding, essential to avoid the development of cracks during the temperature cycles occurring in normal operation
* Pulverulent additive composed of trihydrated alumina Al (OH)3 and silica which enhances its mechanical and thermal properties, as well as giving exceptional intrinsic qualities to the insulation in the presence of heat.
* This three-component system of encapsulation gives insulation system temperature 155°C (F) with average winding temperature rise limit at rated current Δθ = 100 K which provides excellent fire-resisting qualities and immediate self-extinction. The moulding of the windings contain no halogen compounds (chlorine, bromine, etc.) and no other compounds capable of producing corrosive or toxic pollutants, thereby guaranteeing a high degree of safety to personnel in emergency situations, notably in the event of a fire.


'''Dry type transformers'''<br>The windings of these transformers are insulated by resin between turns and by resin and air to other windings and to frame. The resin is usually cast under vacuum process (which is patented by major manufacturers).<br>It is recommended that the transformer be chosen according to the IEC 60076-11, as follows:
These transformers are classified as nonflammable. Transformers exposed to fire risk with low flammability and self extinguishing in a given time.


*Environment class E2 (frequent condensation and/or high level of pollution)
They are also exceptionally well adapted for hostile industrial atmospheres and comply with the following class of environment:
*Climatic conditions class B2 (utilization, transport and stockage down to -25 °C)
* Class E3: up to 95 % of humidity and/or high level of pollution
*Fire resistance (transformers exposed to fire risk with low flammability and self extinguishing in a given time)
* Class C3: utilization, transport and storage down to -50 °C.


The following description refers to the process developed by a leading European manufacturer in this field.<br>The encapsulation of a winding uses three components:
{{FigImage|PB116700|jpg|B38|Dry type transformer}}


*Epoxy-resin based on biphenol A with a viscosity that ensures complete impregnation of the windings
==Liquid-filled transformers==
*Anhydride hardener modified to introduce a degree of resilience in the moulding, essential to avoid the development of cracks during the temperature cycles occurring in normal operation
*Pulverulent additive composed of trihydrated alumina Al (OH)3 and silica which enhances its mechanical and thermal properties, as well as giving exceptional intrinsic qualities to the insulation in the presence of heat.


This three-component system of encapsulation gives Class F insulation (Δθ&nbsp;=&nbsp;100&nbsp;K) with excellent fire-resisting qualities and immediate self-extinction. These transformers are therefore classified as nonflammable.<br>The mouldings of the windings contain no halogen compounds (chlorine, bromine, etc.) or other compounds capable of producing corrosive or toxic pollutants, thereby guaranteeing a high degree of safety to personnel in emergency situations, notably in the event of a fire.<br>It also performs exceptionally well in hostile industrial atmospheres of dust, humidity, etc. (see '''Fig.12'''). <br>
The most common insulating liquid used in these transformers is mineral oil, which also acts as a cooling medium.


----
Mineral oils are specified in IEC 60296, they must not contain PCB ('''P'''oly'''C'''hlorinated '''B'''iphenyl).


[[File:FigB12.jpg|none]]
Mineral oil can be replaced by an alternative insulating liquid such as high density hydrocarbons, esters, silicones, halogen liquids.
'''''Fig. B12:'''&nbsp;Dry-type transformer'' <br>


----
The oil being flammable, dedicated safety measures against fire are mandatory in many countries, especially for indoor substations.


'''Liquid-filled transformers'''<br>The most common insulating/cooling liquid used in transformers is mineral oil. Mineral oils are specified in IEC 60296. Being flammable, safety measures are obligatory in many countries, especially for indoor substations. The DGPT unit (Detection of Gas, Pressure and Temperature) ensures the protection of oil-filled transformers. In the event of an anomaly, the DGPT causes the MV supply to the transformer to be cut off very rapidly, before the situation becomes dangerous.<br>Mineral oil is bio-degradable and does not contain PCB (polychlorinated biphenyl), which was the reason for banning askerel, i.e. Pyralène, Pyrolio, Pyroline...<br>On request, mineral oil can be replaced by an alternative insulating liquid, by adapting the transformer, as required, and taking appropriate additional precautions if necessary.<br>The insulating fluid also acts as a cooling medium; it expands as the load and/or the ambient temperature increases, so that all liquid-filled transformers must be designed to accommodate the extra volume of liquid without the pressure in the tank becoming excessive.<br>There are two ways in which this pressure limitation is commonly achieved:
The dielectric liquids are classified in several categories according to their fire performance. This latter is assessed according to two criteria (see {{FigRef|B39}}):
* The flash-point temperature
* The minimum calorific power.


*Hermetically-sealed totally-filled tank (up to 10 MVA at the present time)
{{tb-start|id=Tab1036|num=B39|title=Categories of dielectric fluids|cols=3}}
 
{| class="wikitable"
Developed by a leading French manufacturer in 1963, this method was adopted by the national utility in 1972, and is now in world-wide service (see '''Fig. B13'''). <br>
 
----
 
[[File:FigB13.jpg|none]]
'''''Fig. B13:'''&nbsp;Hermetically-sealed totally-filled tank'' <br>
 
----
 
Expansion of the liquid is compensated by the elastic deformation of the oil-cooling passages attached to the tank.<br>The “total-fill” technique has many important advantages over other methods:<br>&nbsp; - Oxydation of the dielectric liquid (with atmospheric oxygen) is entirely precluded<br>&nbsp; - No need for an air-drying device, and so no consequent maintenance (inspection and changing of saturated dessicant)<br>&nbsp; - No need for dielectric-strength test of the liquid for at least 10 years<br>&nbsp; - Simplified protection against internal faults by means of a DGPT device is possible<br>&nbsp; - Simplicity of installation: lighter and lower profile (than tanks with a conservator) and access to the MV and LV terminals is unobstructed<br>&nbsp; - Immediate detection of (even small) oil leaks; water cannot enter the tank
 
*Air-breathing conservator-type tank at atmospheric pressure
 
Expansion of the insulating liquid is taken up by a change in the level of liquid in an expansion (conservator) tank, mounted above the transformer main tank, as shown in '''Figure B14'''. The space above the liquid in the conservator may be filled with air which is drawn in when the level of liquid falls, and is partially expelled when the level rises. When the air is drawn in from the surrounding atmosphere it is admitted through an oil seal, before passing through a dessicating device (generally containing silica-gel crystals) before entering the conservator. In some designs of larger transformers the space above the oil is occupied by an impermeable air bag so that the insulation liquid is never in contact with the atmosphere. The air enters and exits from the deformable bag through an oil seal and dessicator, as previously described. A conservator expansion tank is obligatory for transformers rated above 10 MVA (which is presently the upper limit for “total-fill” type transformers). <br>
 
----
 
[[File:FigB14.jpg|none]]
'''''Fig. B14:'''&nbsp;Air-breathing conservator-type tank at atmosphere pressure'' <br>
 
----
 
== Choice of technology  ==
 
As discussed above, the choice of transformer is between liquid-filled or dry type.<br>For ratings up to 10 MVA, totally-filled units are available as an alternative to conservator-type transformers.<br>A choice depends on a number of considerations, including:
 
*Safety of persons in proximity to the transformer. Local regulations and official recommendations may have to be respected
*Economic considerations, taking account of the relative advantages of each technique
 
The regulations affecting the choice are:
 
*Dry-type transformer:
 
&nbsp; - In some countries a dry-type transformer is obligatory in high apartment blocks<br>&nbsp; - Dry-type transformers impose no constraints in other situations
 
*Transformers with liquid insulation:
 
&nbsp; - This type of transformer is generally forbidden in high apartment blocks<br>&nbsp; - For different kinds of insulation liquids, installation restrictions, or minimum protection against fire risk, vary according to the class of&nbsp;<br>&nbsp;&nbsp;&nbsp;&nbsp;insulation used<br>&nbsp; - Some countries in which the use of liquid dielectrics is highly developed, classify the several categories of liquid according to their fire<br>&nbsp;&nbsp;&nbsp; performance. This latter is assessed according to two criteria: the flash-point temperature, and the minimum calorific power. The<br>&nbsp;&nbsp;&nbsp; principal categories are shown in Figure B15 in which a classification code is used for convenience.&nbsp;&nbsp;&nbsp;&nbsp; <br>
 
----
 
<br>
 
{| class="wikitable" width="803" style="width: 803px; height: 106px;"
|-
|-
! Code  
! Code  
Line 117: Line 96:
| O1  
| O1  
| Mineral oil  
| Mineral oil  
| &lt; 300  
| < 300  
| -
| -
|-
|-
| K1  
| K1  
| High-density hydrocarbons  
| High-density hydrocarbons  
| &gt; 300  
| > 300  
| 48
| 48
|-
|-
| K2  
| K2  
| Esters  
| Esters  
| &gt; 300  
| > 300  
| 34 - 37
| 34 - 37
|-
|-
| K3  
| K3 || Silicones || > 300 || 27 - 28
| Silicones  
| &gt; 300  
| 27 - 28
|-
|-
| L3  
| L3 || Insulating halogen liquids || - || 12
| Insulating halogen liquids  
| -  
| 12
|}
|}


'''''Fig. B15: '''Categories of dielectric fluids'' <br>
There are two types of liquid filled transformers: Hermetically-sealed totally-filled transformers and Air-breathing transformer.
 
===Hermetically-sealed totally-filled transformers up to 10 MVA===
(see {{FigRef|B40}})


----
For this type of transformers the expansion of the insulating liquid is compensated by the elastic deformation of the oil-cooling radiators attached to the tank.


== The determination of optimal power ==
The protection against internal faults is ensured by means of a DGPT device: Detection of Gas, Internal Over Pressure and Oil Over Temperature.


The "total-fill" technique has many advantages:
* Water cannot enter the tank
* Oxidation of the dielectric liquid with atmospheric oxygen is entirely precluded
* No need for an air-drying device, and so no consequent maintenance (inspection and changing of saturated desiccant)
* No need for dielectric-strength test of the liquid for at least 10 years


'''Oversizing a transformer'''<br>It results in:
{{FigImage|PB116701|jpg|B40|Hermetically-sealed  totally-filled oil transformer}}


*Excessive investment and unecessarily high no-load losses, but
===Air-breathing transformer===
*Lower on-load losses
(see {{FigRef|B41}})


'''Undersizing a transformer'''<br>It causes:
This type of transformer is equipped with an expansion tank or conservator mounted above the main tank. The expansion of the insulating liquid is compensated inside the conservator by the raising of the oil level.
 
A conservator is required for transformers rated above10 MVA which is presently the upper limit for "totally filled type transformers".
 
In the conservator the top of the oil is in contact with the air which must remain dry to avoid any oxidation. This is achieved by admitting the outside air in the conservator through a desiccating device containing silica-gel crystals.
 
The protection of breathing transformers against internal faults is ensured by means of a buchholz mounted on the pipe linking the main tank to the conservator.
 
The buchholz ensures the detection of gas emission and internal over pressure.
 
The over temperature of the oil is commonly detected by an additional thermostat.
 
{{FigImage|PB116686|jpg|B41|Air-breathing oil transformer}}
 
== Choice of technology  ==


*A reduced efficiency when fully loaded, (the highest efficiency is attained in the range 50% - 70% full load) so that the optimum loading is not achieved
As discussed above, the choice of transformer is between liquid-filled or dry type. For ratings up to 10 MVA, totally filled units are available as an alternative to conservator type transformers.
*On long-term overload, serious consequences for


&nbsp; - The transformer, owing to the premature ageing of the windings insulation, and in extreme cases, resulting in failure of insulation and<br>&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;loss of the transformer&nbsp;&nbsp;<br>&nbsp; - The installation, if overheating of the transformer causes protective relays to trip the controlling circuit-breaker.  
The choice depends on a number of considerations, including:
* Local regulations and recommendations. In some countries dry-type transformers are mandatory for specific buildings such as hospitals, commercial premises etc.
* Risk of fire
* Prices and technical considerations, taking account the relative advantages of each technology.


'''Definition of optimal power'''<br>In order to select an optimal power (kVA) rating for a transformer, the following factors must be taken into account:
== Determination of the optimal power ==


*List the power of installed power-consuming equipment as described in Chapter A
=== The over sizing of a transformer results in:===
*Decide the utilization (or demand) factor for each individual item of load
*Determine the load cycle of the installation, noting the duration of loads and overloads
*Arrange for power-factor correction, if justified, in order to:


&nbsp; - Reduce cost penalties in tariffs based, in part, on maximum kVA demand<br>&nbsp; - Reduce the value of declared load (P(kVA) = P (kW)/cos φ)
* Excessive investment
* Un necessarily high no-load losses
* Lower on-load losses.


*Select, among the range of standard transformer ratings available, taking into account all possible future extensions to the installation.
=== Under sizing a transformer causes:===


It is important to ensure that cooling arrangements for the transformer are adequate. <br>
* A reduced efficiency when fully loaded. The highest efficiency is attained in the range 50 % - 70 % of the full load,
* On long-term overload, serious consequences for the transformer, owing to the premature ageing of the windings insulation, and in extreme cases, resulting in failure of insulation and loss of the transformer.


----
=== Definition of optimal power ===


<br>
In order to select an optimal power rating for a transformer, the following factors must be taken into account:
* List the consumers and define the factor of utilization ku and the diversity factor ks for each load as described in chapter A
* Determine the load cycle of the installation, noting the duration of loads and overloads
* Take into account all possible future extensions of the installation.
* Arrange for power-factor correction, if justified, in order to:
**Reduce billing penalties in tariffs based, in part, on maximum kVA demand
**Reduce the value of the required apparent power: P(kVA) = P (kW)/cos φ
* Select the transformer, among the range of standard transformer ratings available.


[[File:FigB15a.jpg|left]] <br><br><br><br><br><br><br>[[File:FigB15b.jpg|left]] <br><br><br><br><br><br><br>
To avoid over heating and consequently premature ageing of the transformer, it is important to ensure that cooling arrangements and temperature rise of the transformer are adequate.
----


[[ru:Выбор понижающего трансформатора]]
'''Notes:'''
[[zh:中压 / 低压变压器的选择]]
*A wrong choice of the winding temperature rise or thermal class can be at the origin of a reduced lifespan.
*A wrong assessment of the service conditions linked to the load profile can be at the origin of a reduced lifespan. Ex: Photovoltaic production where the load is during the day and when a 70°C maximum ambient temperature gradient is met as in Russia between winter and summer.

Latest revision as of 09:48, 22 June 2022

The transformers shall comply with IEC 60076. A transformer is characterized by its electrical parameters, but also by its technology and its conditions of use.

Characteristic parameters of a transformer

Rated power = the apparent-power in kVA on which the values of the design parameters and the construction of the transformer are based. Manufacturing tests and guarantee refer to this rated power
Frequency = for power distribution systems discussed in this guide, the frequency is either 50 Hz or 60 Hz
Rated primary voltage = the service voltage of the electrical network on which the transformer in connected
Rated secondary voltage = the voltage measured between the secondary terminals when the transformer is off load and energized at its rated primary voltage
Transformer ratio = RMS value of the rated primary voltage divided by the RMS value of the rated secondary voltage
Rated insulation levels = are defined by the values of the overvoltage power frequency withstand test, and high voltage lightning impulse tests. For the voltage levels considered in this guide, the encountered switching over voltages are generally lower than the expected lightning over voltages, so no over voltage switching tests are required for these voltages
Off-load tap-Changer switch = allows to adjust the rated primary voltage and consequently the transformer ratio within the range ± 2.5 % and ± 5 %. The transformer must be de-energized before the operation of the switch
Winding configurations = Star, Delta and Zigzag high and low voltage windings connections are defined by an alphanumeric code read from the left to the right. The first letter refers to the high voltage winding, the second letter to low voltage winding:

  • Capital letters are used for the high voltage windings
    • D = delta connection
    • Y = star connection
    • Z = zigzag connection
    • N = neutral point brought out to a dedicated terminal
  • Lower-case letters are used for the low voltage winding
    • d = delta
    • y = star
    • z = interconnected-star (or zigzag)
    • n = neutral point brought out to a dedicated terminal
  • A number between 0 and 11 indicates the phase shifting between the primary and the secondary voltages.
  • A common winding configuration used for distribution transformers is Dyn 11:
    • High voltage primary windings connected in Delta
    • Low voltage secondary windings connected in Star
    • Low voltage neutral point brought out to a dedicated terminal.
    • Phase shifting between the primary and the secondary voltage: 30°.

Technology and utilization of the transformers

There are two basic types of distribution transformer:

  • Dry type (cast resin encapsulated) transformer
  • Liquid filled (oil-immersed) transformer.

According IEC 60076, the standard conditions of utilization of the transformers for outdoor and indoor installation are the following:

  • Altitude ≤ 1000 m
  • Maximum ambient temperature: 40 °C
  • Monthly average temperature: 30 °C during the hottest month
  • Annual average temperature: 20 °C.

For other service conditions

  • For oil immersed transformer the IEC 60076-2 specifies the oil and winding temperature rise.
  • For dry type transformer the IEC 60076-11 specifies the thermal class.

The temperature surrounding the transformer is linked to the outdoor service condition, its cooling mode and efficiency when installed in a room, and its load. Two loading guides can help to verify if the transformer is correctly defined according to the expected lifespan, which are respectively the IEC 60076-7 and IEC 60076-12.

An annex within the HV/LV prefabricated substation standard IEC 62271-202 gives several examples of installation, based on these two guides.

Dry type transformers

(see Fig. B38)

The dry type transformers shall comply with IEC 60076-11:

Each individual winding of these transformers is casted in resin according to a vacuum dedicated process.

The high voltage winding, the low voltage winding and the frame are separate by air.

The encapsulation of a winding uses three components:

  • Epoxy-resin based on biphenol A with a viscosity that ensures complete impregnation of the windings
  • Anhydride hardener modified to introduce a degree of resilience in the moulding, essential to avoid the development of cracks during the temperature cycles occurring in normal operation
  • Pulverulent additive composed of trihydrated alumina Al (OH)3 and silica which enhances its mechanical and thermal properties, as well as giving exceptional intrinsic qualities to the insulation in the presence of heat.
  • This three-component system of encapsulation gives insulation system temperature 155°C (F) with average winding temperature rise limit at rated current Δθ = 100 K which provides excellent fire-resisting qualities and immediate self-extinction. The moulding of the windings contain no halogen compounds (chlorine, bromine, etc.) and no other compounds capable of producing corrosive or toxic pollutants, thereby guaranteeing a high degree of safety to personnel in emergency situations, notably in the event of a fire.

These transformers are classified as nonflammable. Transformers exposed to fire risk with low flammability and self extinguishing in a given time.

They are also exceptionally well adapted for hostile industrial atmospheres and comply with the following class of environment:

  • Class E3: up to 95 % of humidity and/or high level of pollution
  • Class C3: utilization, transport and storage down to -50 °C.
Fig. B38 – Dry type transformer

Liquid-filled transformers

The most common insulating liquid used in these transformers is mineral oil, which also acts as a cooling medium.

Mineral oils are specified in IEC 60296, they must not contain PCB (PolyChlorinated Biphenyl).

Mineral oil can be replaced by an alternative insulating liquid such as high density hydrocarbons, esters, silicones, halogen liquids.

The oil being flammable, dedicated safety measures against fire are mandatory in many countries, especially for indoor substations.

The dielectric liquids are classified in several categories according to their fire performance. This latter is assessed according to two criteria (see Fig. B39):

  • The flash-point temperature
  • The minimum calorific power.
Fig. B39 – Categories of dielectric fluids
Code Dielectric fluid Flash-point (°C) Minimum calorific power (MJ/kg)
O1 Mineral oil < 300 -
K1 High-density hydrocarbons > 300 48
K2 Esters > 300 34 - 37
K3 Silicones > 300 27 - 28
L3 Insulating halogen liquids - 12

There are two types of liquid filled transformers: Hermetically-sealed totally-filled transformers and Air-breathing transformer.

Hermetically-sealed totally-filled transformers up to 10 MVA

(see Fig. B40)

For this type of transformers the expansion of the insulating liquid is compensated by the elastic deformation of the oil-cooling radiators attached to the tank.

The protection against internal faults is ensured by means of a DGPT device: Detection of Gas, Internal Over Pressure and Oil Over Temperature.

The "total-fill" technique has many advantages:

  • Water cannot enter the tank
  • Oxidation of the dielectric liquid with atmospheric oxygen is entirely precluded
  • No need for an air-drying device, and so no consequent maintenance (inspection and changing of saturated desiccant)
  • No need for dielectric-strength test of the liquid for at least 10 years
Fig. B40 – Hermetically-sealed totally-filled oil transformer

Air-breathing transformer

(see Fig. B41)

This type of transformer is equipped with an expansion tank or conservator mounted above the main tank. The expansion of the insulating liquid is compensated inside the conservator by the raising of the oil level.

A conservator is required for transformers rated above10 MVA which is presently the upper limit for "totally filled type transformers".

In the conservator the top of the oil is in contact with the air which must remain dry to avoid any oxidation. This is achieved by admitting the outside air in the conservator through a desiccating device containing silica-gel crystals.

The protection of breathing transformers against internal faults is ensured by means of a buchholz mounted on the pipe linking the main tank to the conservator.

The buchholz ensures the detection of gas emission and internal over pressure.

The over temperature of the oil is commonly detected by an additional thermostat.

Fig. B41 – Air-breathing oil transformer

Choice of technology

As discussed above, the choice of transformer is between liquid-filled or dry type. For ratings up to 10 MVA, totally filled units are available as an alternative to conservator type transformers.

The choice depends on a number of considerations, including:

  • Local regulations and recommendations. In some countries dry-type transformers are mandatory for specific buildings such as hospitals, commercial premises etc.
  • Risk of fire
  • Prices and technical considerations, taking account the relative advantages of each technology.

Determination of the optimal power

The over sizing of a transformer results in:

  • Excessive investment
  • Un necessarily high no-load losses
  • Lower on-load losses.

Under sizing a transformer causes:

  • A reduced efficiency when fully loaded. The highest efficiency is attained in the range 50 % - 70 % of the full load,
  • On long-term overload, serious consequences for the transformer, owing to the premature ageing of the windings insulation, and in extreme cases, resulting in failure of insulation and loss of the transformer.

Definition of optimal power

In order to select an optimal power rating for a transformer, the following factors must be taken into account:

  • List the consumers and define the factor of utilization ku and the diversity factor ks for each load as described in chapter A
  • Determine the load cycle of the installation, noting the duration of loads and overloads
  • Take into account all possible future extensions of the installation.
  • Arrange for power-factor correction, if justified, in order to:
    • Reduce billing penalties in tariffs based, in part, on maximum kVA demand
    • Reduce the value of the required apparent power: P(kVA) = P (kW)/cos φ
  • Select the transformer, among the range of standard transformer ratings available.

To avoid over heating and consequently premature ageing of the transformer, it is important to ensure that cooling arrangements and temperature rise of the transformer are adequate.

Notes:

  • A wrong choice of the winding temperature rise or thermal class can be at the origin of a reduced lifespan.
  • A wrong assessment of the service conditions linked to the load profile can be at the origin of a reduced lifespan. Ex: Photovoltaic production where the load is during the day and when a 70°C maximum ambient temperature gradient is met as in Russia between winter and summer.
Share