Outdoor substations: Difference between revisions

From Electrical Installation Guide
m (1 revision)
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "")
 
(18 intermediate revisions by 7 users not shown)
Line 1: Line 1:
{{Menu_Connection_to_the_MV_utility_distribution_network}}
{{Menu_Connection_to_the_MV_utility_distribution_network}}__TOC__
<br>
== Outdoor substations with prefabricated enclosures ==
__TOC__
== Outdoor substation with prefabricated enclosures ==


The prefabricated outdoor MV/LV substations (see {{FigRef|B49}}) comply with IEC 62271-202 standard.
* A type tested prefabricated outdoor substation is subjected to tests and verifications dedicated to:
** Degree of protection
** Temperature class
** Non-flammable materials
** Mechanical resistance of the enclosure
** Sound level
** Insulation level
** Internal arc withstand
** Earthing circuit
** Retention of oil
** Operation of the substation.


A prefabricated MV/LV substation complying with IEC 62271-202 standard includes&nbsp;:  
=== Main benefits:===


*equipment in accordance with IEC standards
The prefabricated substations provide a particularly interesting and optimized solution regarding:
*a type tested enclosure, which means during its design, it has undergone a battery of tests (see '''Fig. B24'''):
* Delivery time
* Construction works
* Erection works
* Commissioning
* Total cost.


&nbsp; - Degree of protection<br>&nbsp; -&nbsp;Functional tests<br>&nbsp; - Temperature class&nbsp;<br>&nbsp; - Non-flammable materials<br>&nbsp; - Mechanical resistance of the enclosure<br>&nbsp; - Sound level<br>&nbsp; - Insulation level<br>&nbsp; - Internal arc withstand<br>&nbsp; - Earthing circuit test<br>&nbsp; - Oil retention,… <br>
{{FigImage|DB422043_EN|svg|B49|Type tested substation according to IEC 62271-202}}


IEC 62271-202 standard defines requirements for two types of outdoor prefabricated substations (see {{FigRef|B50}}:)
* Walk-in type substation
* Non walk-in type substation.


[[File:FigB24.jpg|none|500px]]
{{FigImage|DB422044_EN|svg|B50|Walk in and non-walk in type substations}}
'''''Fig. B24:'''''<i>&nbsp;Type tested substation according to IEC&nbsp;62271-202 standard</i> <br><br>


'''Main benefits are&nbsp;:<br>'''
The substations may be situated at ground level, half buried or completely buried (underground substation), resulting in three types of design (see {{FigRef|B51}} and {{FigRef|B52}}).


*Safety:
{{FigImage|DB422045_EN|svg|B51|Outdoor substations. The three type of design}}


&nbsp; - For public and operators thanks to a high reproducible quality level  
{{Gallery|B52|Two examples of outdoor substations||
|PB116704.jpg|a|Ground level walk-in type
|PB116705.jpg|b|Half buried non walk-in type
}}


*Cost effective:
== Outdoor substation without enclosure ==
(see {{FigRef|B53}})


&nbsp; - Manufactured, equipped and tested in the factory
This kind of outdoor substations based on weatherproof equipment is commonly used in countries such as UK and India for example.


*Delivery time
These substations are generally included in MV rings and include:
* Two functional units dedicated to the connection of the substation to the ring
* One functional unit for the supply and the protection of the MV/LV power transformer generally done by a circuit breaker unit
* One single MV/LV Power transformer
* One LV distribution panel.


&nbsp; - Delivered ready to be connected.<br>
The transformer and the LV panel can be installed in dedicated outdoor type housing.
<br>


'''IEC 62271-202 standard includes four main designs '''(see '''Fig. B25''')
{{FigImage|PB116706|jpg|B53|Outdoor substation without enclosure}}


*Walk-in type substation&nbsp;:
== Pole mounted substation ==


&nbsp; - Operation protected from bad weather conditions
=== Application ===


*Non walk-in substation
These substations are mainly used for the supply of isolated rural consumers from MV overhead lines.


&nbsp; - Ground space savings, and outdoors operations
=== Constitution ===


*Half buried substation
This type of substation includes (see {{FigRef|B54}}):


&nbsp; - Limited visual impact
* A single pole mounted MV/LV power transformer that is, according to the local rules associated or not with:
** A load break switch
** A set of three fuses
** A set of three surge arrestors
* A low voltage circuit breaker
* An earthing electrode realized at the bottom of the pole supporting the equipment.


*Underground substation
The location of the substation must allow easy access of the personnel and handling equipment.


&nbsp; - Blends completely into the environment.<br>
{{FigImage|DB422046_EN|svg|B54|Pole mounted MV/LV substation}}
 
 
<br>
[[File:FigB25a.jpg|none]]<br>
 
&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;'''[a]'''&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; '''[b]'''
[[File:FigB25b.jpg|left]]
[[File:FigB25c.jpg|none]]
 
<br>
'''''Fig. B25:'''''<i>&nbsp;The four designs according to IEC&nbsp;62271-202 standard and two pictures [a] walk-in type MV/LV substation; [b] half buried type MV/LV substation</i> <br>
<br>
 
== Outdoor substations without enclosures  ==
 
(see '''Fig. B26''')<br>
These kinds of outdoor substation are common in some countries, based on weatherproof equipment exposed to the elements.<br>These substations comprise a fenced area in which three or more concrete plinths are installed for:
 
*A ring-main unit, or one or more switch-fuse or circuit-breaker unit(s)
*One or more transformer(s), and
*One or more LV distribution panel(s).
 
[[File:FigB26.jpg|none]]
 
'''''Fig. B26:'''''<i>&nbsp;Outdoor substations without enclosures</i> <br>
 
== Pole mounted substations ==
 
 
'''Field of application'''<br>These substations are mainly used to supply isolated rural consumers from MV overhead line distribution systems.<br>
 
'''Constitution<br>'''In this type of substation, most often, the MV transformer protection is provided by fuses.<br>Lightning arresters are provided, however, to protect the transformer and consumers as shown in '''Figure B27'''.<br>
 
'''General arrangement of equipment'''<br>As previously noted the location of the substation must allow easy access, not only for personnel but for equipment handling (raising the transformer, for example) and the manœuvring of heavy vehicles. <br>
 
[[File:FigB27.jpg|none]]
'''''Fig. B27:'''&nbsp;Pole-mounted ransformer substation''
 
[[ru:Подстанция наружной установки]]
[[zh:户外型变电站]]

Latest revision as of 09:48, 22 June 2022

Outdoor substations with prefabricated enclosures

The prefabricated outdoor MV/LV substations (see Fig. B49) comply with IEC 62271-202 standard.

  • A type tested prefabricated outdoor substation is subjected to tests and verifications dedicated to:
    • Degree of protection
    • Temperature class
    • Non-flammable materials
    • Mechanical resistance of the enclosure
    • Sound level
    • Insulation level
    • Internal arc withstand
    • Earthing circuit
    • Retention of oil
    • Operation of the substation.

Main benefits:

The prefabricated substations provide a particularly interesting and optimized solution regarding:

  • Delivery time
  • Construction works
  • Erection works
  • Commissioning
  • Total cost.
Fig. B49 – Type tested substation according to IEC 62271-202

IEC 62271-202 standard defines requirements for two types of outdoor prefabricated substations (see Fig. B50:)

  • Walk-in type substation
  • Non walk-in type substation.
Fig. B50 – Walk in and non-walk in type substations

The substations may be situated at ground level, half buried or completely buried (underground substation), resulting in three types of design (see Fig. B51 and Fig. B52).

Fig. B51 – Outdoor substations. The three type of design

Outdoor substation without enclosure

(see Fig. B53)

This kind of outdoor substations based on weatherproof equipment is commonly used in countries such as UK and India for example.

These substations are generally included in MV rings and include:

  • Two functional units dedicated to the connection of the substation to the ring
  • One functional unit for the supply and the protection of the MV/LV power transformer generally done by a circuit breaker unit
  • One single MV/LV Power transformer
  • One LV distribution panel.

The transformer and the LV panel can be installed in dedicated outdoor type housing.

Fig. B53 – Outdoor substation without enclosure

Pole mounted substation

Application

These substations are mainly used for the supply of isolated rural consumers from MV overhead lines.

Constitution

This type of substation includes (see Fig. B54):

  • A single pole mounted MV/LV power transformer that is, according to the local rules associated or not with:
    • A load break switch
    • A set of three fuses
    • A set of three surge arrestors
  • A low voltage circuit breaker
  • An earthing electrode realized at the bottom of the pole supporting the equipment.

The location of the substation must allow easy access of the personnel and handling equipment.

Fig. B54 – Pole mounted MV/LV substation
Share