Sensitivity of RCDs to disturbances: Difference between revisions

From Electrical Installation Guide
(→‎Atmospheres with high concentrations of chemicals or dust: reviewed look&feel of table in figure F70 + updated some text)
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "")
 
(27 intermediate revisions by 4 users not shown)
Line 1: Line 1:
{{Menu_Protection_against_electric_shocks}}
{{Menu_Protection_against_electric_shocks}}__TOC__
<br>
In certain cases, aspects of the environment can disturb the correct operation of RCDs:
__TOC__
* '''“nuisance”''' tripping: Break in power supply without the situation being really hazardous. This type of tripping is often repetitive, causing major inconvenience and detrimental to the quality of the user’s electrical power supply.
 
* '''non-tripping''', in the event of a hazard. Less perceptible than nuisance tripping, these malfunctions must still be examined carefully since they undermine user safety.
In certain cases, aspects of the environment can disturb the correct operation of RCDs:  
 
*'''“nuisance” tripping:''' Break in power supply without the situation being really hazardous. This type of tripping is often repetitive, causing major inconvenience and detrimental to the quality of the user's electrical power supply.  
*'''non-tripping, in the event of a hazard.''' Less perceptible than nuisance tripping, these malfunctions must still be examined carefully since they undermine user safety. This is why international standards define 3 categories of RCDs according to their immunity to this type of disturbance (see below).<br>
 
 
== Main disturbance types  ==


== Main electrical disturbance types ==
=== Permanent earth leakage currents ===
=== Permanent earth leakage currents ===
Every LV installation has a permanent leakage current to earth, which is either due to:
* Unbalance of the intrinsic capacitance between live conductors and earth for three-phase circuits or
* Capacitance between live conductors and earth for single-phase circuits


Every LV installation has a permanent leakage current to earth, which is either due to:
The larger the installation, the greater its capacitance with consequently increased leakage current.
*Unbalance of the intrinsic capacitance between live conductors and earth for three-phase circuits or
*Capacitance between live conductors and earth for single-phase circuits
 
The larger the installation the greater its capacitance with consequently increased leakage current.  


The capacitive current to earth is sometimes increased significantly by filtering capacitors associated with electronic equipment (automation, IT and computer-based systems, etc.).  
The capacitive current to earth is sometimes increased significantly by filtering capacitors associated with electronic equipment (automation, IT and computer- based systems, etc.).


In the absence of more precise data, permanent leakage current in a given installation can be estimated from the following values, measured at 230 V 50 Hz:
In the absence of more precise data, permanent leakage current in a given installation can be estimated from the following values, measured at 230 V 50 Hz:
* Single-phase or three-phase line: 1.5 mA /100m
* Heating floor: 1mA / kW
* Fax terminal, printer: 1 mA
* Microcomputer, workstation: 2 mA
* Copy machine: 1.5 mA


Single-phase or three-phase line: 1.5 mA /100m
Since RCDs complying with IEC and many national standards may trip between 0.5 IΔn and IΔn, for residual currents higher than 0.5 IΔn it is recommended to divide the installation by sub-division of circuits to avoid unwanted tripping.  
*Heating floor: 1mA / kW
*Fax terminal, printer: 1 mA
*Microcomputer, workstation: 2 mA
*Copy machine: 1.5 mA
 
Since RCDs complying with IEC and many national standards may operate under, the limitation of permanent leakage current to 0.25 IΔn, by sub-division of circuits will, in practice, eliminate any unwanted tripping.


For very particular cases, such as the extension, or partial renovation of extended IT-earthed installations, the manufacturers must be consulted.
For very particular cases, such as the extension, or partial renovation of extended IT-earthed installations, the manufacturers must be consulted.


'''High frequency components''' (harmonics, transients, etc.), are generated by computer equipment power supplies, converters, motors with speed regulators, fluorescent lighting systems and in the vicinity of high power switching devices and reactive energy compensation banks.


=== High frequency components ===
Part of these high frequency currents may flow to earth through parasitic capacitances. Although not hazardous for the user, these currents can still cause the nuisance tripping of differential devices.  
 
High frequency components (Harmonics, transients, etc.) are generated by computer equipment power supplies, converters, motors with speed regulators, fluorescent lighting systems and in the vicinity of high power switching devices and reactive energy compensation banks.
 
Part of these high frequency currents may flow to earth through parasitic capacitances. Although not hazardous for the user, these currents can still cause the tripping of differential devices.  


SI type RCDs have a specific frequency response curve designed to prevent nuisance tripping when non-dangerous high frequency residual currents are present.


=== Energization ===
=== Energization ===
The initial energization of the capacitances mentioned above gives rise to high frequency transient currents of very short duration, similar to that shown in {{FigureRef|F53}}.


The initial energization of the capacitances mentioned above gives rise to high frequency transient currents of very short duration, similar to that shown in '''Figure&nbsp;F67'''.
The sudden occurrence of a first-fault in an IT-earthed system also causes transient earth-leakage currents at high frequency, due to the sudden rise of the two healthy phases to phase/phase voltage above earth.
 
The sudden occurrence of a first-fault on an IT-earthed system also causes transient earth-leakage currents at high frequency, due to the sudden rise of the two healthy phases to phase/phase voltage above earth.  
 
 
[[File:FigF67.jpg|none]]


'''''Fig. F67:''' Standardized 0.5 µs/100 kHz current transient wave''
SI type RCDs present a small tripping delay, allowing to let pass this transient current without nuisance tripping.


{{FigImage|DB422261_EN|svg|F53|Standardized 0.5 μs/100 KHz current transient wave}}


=== Common mode overvoltages ===
=== Common mode overvoltages ===
Electrical networks are subject to overvoltages due to lightning strikes or to abrupt changes of system operating conditions (faults, fuse operation, switching, etc.).


Electrical networks are subjected to overvoltages due to lightning strikes or to abrupt changes of system operating conditions (faults, fuse operation, switching, etc.). <br>
These sudden changes often cause large transient voltages and currents in inductive and capacitive circuits. Records have established that, on LV systems, overvoltages remain generally below 6 kV, and that they can be adequately represented by the conventional 1.2/50 μs impulse wave (see {{FigureRef|F54}}).
These sudden changes often cause large transient voltages and currents in inductive and capacitive circuits. Records have established that, on LV systems, overvoltages remain generally below 6 kV, and that they can be adequately represented by the conventional 1.2/50 μs impulse wave (see '''Fig. F68''').  


{{FigImage|DB422262_EN|svg|F54|Standardized 1.2/50 μs voltage transient wave}}


[[File:FigF68.jpg|none]]
These overvoltages give rise to transient currents represented by a current impulse wave of the conventional 8/20 μs form, having a peak value of several tens of amperes (see {{FigureRef|F55}}).


'''''Fig. F68:''' Standardized 1.2/50 µs voltage transient wave''
The transient currents flow to earth via the capacitances of the installation.


SI type RCDs offer a high surge current capability and can withstand a 8/20µs current impulse higher than 3kA.


These overvoltages give rise to transient currents represented by a current impulse wave of the conventional 8/20 μs form, having a peak value of several tens of amperes (see '''Fig. F69''').<br>The transient currents flow to earth via the capacitances of the installation.
{{FigImage|DB422263_EN|svg|F55|Standardized current-impulse wave 8/20 μs}}


== Main climatic disturbance types ==


[[File:FigF69.jpg|none]]
=== Cold ===


'''''Fig. F69:''' Standardized current-impulse wave 8/20 µs''
In the cases of temperatures under - 5°C, very high sensitivity electromechanical relays in the RCD may be “welded” by the condensation – freezing action.


Type “SI” devices can operate at temperatures down to - 25 °C.


=== Non-sinusoidal fault currents :  RCDs Type AC, A, B ===
=== Atmospheres with high concentrations of chemicals or dust ===
 
Standard IEC 60755 (General requirements for residual current operated protective devices) defines three types of RCD depending on the characteristics of the fault current:
 
* '''Type AC'''
RCD for which tripping is ensured for residual sinusoidal alternating currents.
 
* '''Type A'''
RCD for which tripping is ensured:<br>&nbsp; - for residual sinusoidal alternating currents,<br>&nbsp; - for residual pulsating direct currents,
 
* '''Type B'''
RCD for which tripping is ensured:<br>&nbsp; - as for type A,<br>&nbsp; - for pure direct residual currents which may result from three-phase rectifying circuits.<br>
 
 
=== Cold ===
 
In the cases of temperatures under - 5 °C, very high sensitivity electromechanical relays in the RCD may be “welded” by the condensation – freezing action.<br>
Type “Si” devices can operate under temperatures down to - 25 °C.


The special alloys used to make the RCDs can notably be damaged by corrosion. Dust can also block the movement of mechanical parts.


=== Atmospheres with high concentrations of chemicals or dust ===
See the measures to be taken according to the levels of severity defined by standards in {{FigureRef|F56}}.


The special alloys used to make the RCDs can be notably damaged by corrosion. Dust can also block the movement of mechanical parts.
Regulations define the choice of earth leakage protection and its implementation.


Classification of external influences is provided by Table 51A of standard '''IEC 60364-5-51''' (Selection and erection of electrical equipment – Common rules).
The main reference text is [[List of external influences|IEC 60364-5-51]]:
* this standard gives a classification for external influences in the '''Presence of corrosive or polluting substances''' (AFx, where x stands for the level of severity, from 1=negligible upto 4=extreme)
* It gives a classification (AFx) for external influences in the presence of corrosive or polluting substances,
* it also defines the measures to be taken and the choice of materials to be used according to these levels.
* It defines the choice of materials to be used according to extreme influences.
See the recommended measures to be taken and the type of earth leakage protection to implement according to levels of severity in '''Fig. F70'''.


{| class="wikitable" style="width: 1000px;"
{{tb-start|id=Tab1165a|num=F56|title=External influence classification according to IEC 60364-5-51 standard |cols=5}}
{| class="wikitable"
! colspan="2" rowspan="2" |Presence of corrosive or polluting substances (IEC 60364-5-51)
! colspan="2" |Influence of the electrical network
! rowspan="2" |Characteristics required for selection and erection of equipment
|-
|-
! rowspan="2" | '''Influence of the electrical network'''
!Clean network
!'''Disturbed network'''
!Disturbed network
| Super-immunized residual current protections<br>Type A SI:&nbsp;[[File:Symbol.gif]]
| rowspan="2" | Super-immunized residual current protections<br>SI:&nbsp;[[File:Symbol.gif]]
| rowspan="2" | Super-immunized residual current protections<br>SI:&nbsp;[[File:Symbol.gif]]<br>+<br>Appropriate additional protection (sealed cabinet or unit)
| rowspan="2" | Super-immunized residual current protections<br>SI:&nbsp;[[File:Symbol.gif]]<br>+<br>Appropriate additional protection (sealed cabinet or unit + overpressure)
|-
|-
!'''Clean network'''
|AF1
| Standard immunized residual current protections<br>Type AC
|Negligible presence
|Standard immunized residual current protections
Type AC: [[File:DB431079.svg]]
|Super-immunized residual current protections
Type A SI:  [[File:DB431080.svg]]
|Normal
|-
|-
! colspan="2" |Presence of corrosive or polluting substances<br/>(IEC 60364-5-51)
|AF2
!Negligible presence
|Significant presence of atmospheric origin
!Significant presence of atmospheric origin
| colspan="2" | Super-immunized residual current protections
!Intermittent or accidental subjection to corrosive or polluting chemical substances
Type A SI:  [[File:DB431080.svg]]
!Continuous subjection to corrosive or polluting chemical substances
|According to the nature of substances (for example, compliance to salt mist test according to IEC 60068-2-11)
|-
|-
| colspan="2" |'''Severity level'''
|AF3
| style="width: 190px" |'''AF1'''
|Intermittent or accidental subjection to corrosive or polluting chemical substances
| style="width: 190px" |'''AF2'''
| colspan="2" |Super-immunized residual current protections
| style="width: 190px" |'''AF3'''
Type A SI: [[File:DB431080.svg]]<br>+<br>Appropriate additional protection (sealed cabinet or unit)
| style="width: 190px" |'''AF4'''
|Protection against corrosion according to equipment specification
|-
|-
| colspan="2" |'''Characteristics required for selection and erection of equipment'''
|AF4
|Normal.
|Continuous subjection to corrosive or polluting chemical substances
|According to the nature of substances (for example, compliance to salt mist test according to IEC 60068-2-11)
| colspan="2" |Super-immunized residual current protections
|Protection against corrosion according to equipment specification
Type A SI:  [[File:DB431080.svg]]<br>+<br>Appropriate additional protection (sealed cabinet or unit + overpressure)
|Equipment specially designed according to the nature of substances
|Equipment specially designed according to the nature of substances
|}
|}


 
{{tb-start|id=Tab1165b|num=|title=|cols=4}}
{| class="wikitable" style="width: 700px"
{| class="wikitable"
|-
|-
! Examples of exposed sites  
! Examples of exposed sites  
Line 155: Line 133:
|}
|}


'''''Fig. F70:''' External influence classification according to IEC 60364-5-51 standard''
== Type SI RCDs immunity to nuisance tripping ==
 
== Immunity level for Schneider Electric residual current devices ==
 
The Schneider Electric range comprises various types of RCDs allowing earth leakage protection to be adapted to each application. The table below indicates the choices to be made according to the type of probable disturbances at the point of installation.
 
 
 
{| class="wikitable" style="width: 811px; height: 156px" width="811"
|-
! rowspan="3" | Device type
! Nuisance trippings
! colspan="4" | Non-trippings
|-
! rowspan="2" | High frequency leakage current
! colspan="2" | Fault current
! rowspan="2" | Low temperatures (down to - 25&nbsp;°C)
! rowspan="2" | Corrosion Dust
|-
! Rectified alternating
! Pure direct
|-
| AC
| align="center" | {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}&nbsp;
| align="center" | 
| align="center" | 
| align="center" | 
| align="center" |
|-
| A
| align="center" | {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}
| align="center" | {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}
| align="center" |
| align="center" | {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare}}
| align="center" |
|-
| SI  
| align="center" | {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}&nbsp;{{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}&nbsp;{{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}
| align="center" | {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}
| align="center" | 
| align="center" | {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}
| align="center" | {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}
|-
| B
| align="center" | {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}&nbsp;{{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}&nbsp;{{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}
| align="center" | {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}
| align="center" | {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}
| align="center" | {{#tag:math|{{FormulaTableCell}}\color{RoyalBlue}\blacksquare }}
| &nbsp;&nbsp;
|}
 
'''''Fig. F71:''' Immunity level of Schneider Electric RCDs<br>''
 
 
== Immunity to nuisance tripping ==


Type SI RCDs have been designed to avoid nuisance tripping or non-tripping in case of polluted network, lightning effect, high frequency currents, RF waves, etc.
Type SI RCDs have been designed to avoid nuisance tripping or non-tripping in case of polluted network, lightning effect, high frequency currents, RF waves, etc.


'''Figure F72 '''below indicates the levels of tests undergone by this type of RCDs.  
{{FigureRef|F57}} below indicates the levels of tests undergone by this type of RCDs.
 
 


{| class="wikitable" style="width: 807px; height: 430px" width="807"
{{tb-start|id=Tab1167|num=F57|title=Immunity to nuisance tripping tests undergone by Schneider Electric RCDs|cols=5}}
{| class="wikitable"
|-
|-
! Disturbance type  
! Disturbance type  
! Rated test wave  
! Rated test wave  
! Immunity<br>Acti 9&nbsp;:<br>ID-RCCB, DPN Vigi, Vigi iC60, Vigi C120, Vigi NG125<br>SI type
! Immunity  
Acti 9, ID-RCCB, DPN Vigi, Vigi iC60, Vigi C120, Vigi NG125
SI type
|-
|-
! colspan="3" | Continuous disturbances
| {{tb-HC2}} colspan="3" | '''Continuous disturbances'''
|-
|-
| Harmonics  
| Harmonics  
Line 229: Line 154:
| Earth leakage current = 8 x I∆n
| Earth leakage current = 8 x I∆n
|-
|-
| Transient disturbances  
| {{tb-HC2}} colspan="3" | '''Transient disturbances'''
| &nbsp;
| &nbsp;
|-
|-
| Lightning induced overvoltage  
| Lightning induced overvoltage  
| 1.2 / 50 µs pulse <br>(IEC/EN 61000-4-5)  
| 1.2 / 50 µs pulse  
(IEC/EN 61000-4-5)  
| 4.5 kV between conductors 5.5 kV / earth
| 4.5 kV between conductors 5.5 kV / earth
|-
|-
| Lightning induced current  
| Lightning induced current  
| 8 / 20 µs pulse <br>(IEC/EN 61008)  
| 8 / 20 µs pulse  
(IEC/EN 61008)  
| 5 kA peak
| 5 kA peak
|-
|-
| Switching transient, indirect lightning currents  
| Switching transient, indirect lightning currents  
| 0.5 µs / 100 kHz “&nbsp;ring wave&nbsp;” <br>(IEC/EN 61008)  
| 0.5 µs / 100 kHz “ring wave”
(IEC/EN 61008)  
| 400 A peak
| 400 A peak
|-
|-
Line 249: Line 175:
| 500 A
| 500 A
|-
|-
! colspan="3" | Electromagnetic compatibility
| {{tb-HC2}} colspan="3" | '''Electromagnetic compatibility'''
|-
|-
| Inductive load switchings fluorescent lights, motors, etc.)  
| Inductive load switching, fluorescent lights, motors, etc.)  
| Repeated bursts(IEC 61000-4-4)  
| Repeated bursts
| 5 kV / 2.5 kHz<br> 4 kV / 400 kHz
(IEC 61000-4-4)  
| 5 kV / 2.5 kHz
4 kV / 400 kHz
|-
|-
| Fluorescent lights, thyristor controlled circuits, etc.  
| Fluorescent lights, thyristor controlled circuits, etc.  
| RF conducted waves <br>(level 4 IEC 61000-4-6)<br>(level 4 IEC 61000-4-16)
| RF conducted waves  
| <br>30 V (150 kHz to 230 MHz)<br> 250 mA (15 kHz to 150 kHz)
(level 4 IEC 61000-4-6)<br>(level 4 IEC 61000-4-16)
|<br>30 V (150 kHz to 230 MHz)<br>
250 mA (15 kHz to 150 kHz)
|-
|-
| RF waves (TV&amp; radio, broadcact, telecommunications,etc.)  
| RF waves (TV & radio, broadcact, telecommunications,etc.)  
| RF radiated waves 80 MHz to 1 GHz(IEC 61000-4-3)  
| RF radiated waves 80 MHz to 1 GHz
(IEC 61000-4-3)  
| 30 V / m
| 30 V / m
|}
|}
'''''Fig. F72:''' Immunity to nuisance tripping tests undergone by Schneider Electric RCDs<br>''


== Recommendations concerning the installation of RCDs with separate toroidal current transformers ==
== Recommendations concerning the installation of RCDs with separate toroidal current transformers ==


The detector of residual current is a closed magnetic circuit (usually circular) of very high magnetic permeability, on which is wound a coil of wire, the ensemble constituting a toroidal (or ring-type) current transformer.


The detector of residual current is a closed magnetic circuit (usually circular) of very high magnetic permeability, on which is wound a coil of wire, the ensemble constituting a toroidal (or ring-type) current transformer.<br>Because of its high permeability, any small deviation from perfect symmetry of the conductors encompassed by the core, and the proximity of ferrous material (steel enclosure, chassis members, etc.) can affect the balance of magnetic forces sufficiently, at times of large load currents (motor-starting current, transformer energizing current surge, etc.) to cause unwanted tripping of the RCD.<br>Unless particular measures are taken, the ratio of operating current IΔn to maximum phase current Iph (max.) is generally less than 1/1,000.<br>This limit can be increased substantially (i.e. the response can be desensitized) by adopting the measures shown in '''Figure F73''', and summarized in '''Figure F74'''.<br>
Because of its high permeability, any small deviation from perfect symmetry of the conductors encompassed by the core, and the proximity of ferrous material (steel enclosure, chassis members, etc.) can affect the balance of magnetic forces sufficiently, at times of large load currents (motor-starting current, transformer energizing current surge, etc.) to cause unwanted tripping of the RCD.
 


Unless particular measures are taken, the ratio of operating current IΔn to maximum phase current Iph (max.) is generally less than 1/1000.


[[File:FigF73.jpg|none]]
This limit can be increased substantially (i.e. the response can be desensitized) by adopting the measures shown in {{FigureRef|F58}}, and summarized in {{FigureRef|F59}}.


'''''Fig. F73:''' Three measures to reduce the ratio IΔn/Iph (max.)&nbsp;<br>''
{{FigImage|DB422264|svg|F58|Means of reducing the ratio IΔn/Iph (max.)
|L {{=}} twice the diameter of the magnetic ring core}}


 
{{tb-start|id=Tab1168|num=F59|title=Means of reducing the ratio IΔn/Iph (max.)|cols=4}}
 
{| class="wikitable"
{| class="wikitable" style="width: 807px; height: 134px" width="807"
|-
|-
! Measures  
! Measures  
Line 304: Line 234:
|  
|  
*Of wall thickness 0.5 mm
*Of wall thickness 0.5 mm
| ø 80  
| ø 80  
| 3
| 3
Line 310: Line 239:
|  
|  
*Of length 2 x inside diameter of ring core
*Of length 2 x inside diameter of ring core
| ø 120  
| ø 120  
| 3
| 3
Line 316: Line 244:
|  
|  
*Completely surrounding the conductors and overlapping <br>the circular core equally at both ends
*Completely surrounding the conductors and overlapping <br>the circular core equally at both ends
| ø 200  
| ø 200  
| 2
| 2
|}
|}
{{tb-notes
|txn1= These measures can be combined. By carefully centralizing the cables in a ring core of 200 mm diameter, where a 50 mm core would be large enough, and using a sleeve, the ratio 1/1000 could become 1/30000.}}


These measures can be combined. By carefully centralizing the cables in a ring core of 200 mm diameter, where a 50 mm core would be large enough, and using a sleeve, the ratio 1/1,000 could become 1/30,000.
== Choice of characteristics of a residual-current circuit breaker (RCCB - IEC 61008) ==
 
'''''Fig. F74:''' Means of reducing the ratio IΔn/Iph (max.)''
 
 
 
== Choice of characteristics of a residual-current circuit-breaker (RCCB - IEC 61008) ==


=== Rated current ===
=== Rated current ===
 
The rated current of a RCCB is chosen according to the maximum sustained load current it will carry.
The rated current of a RCCB is chosen according to the maximum sustained load current it will carry.  
* If the RCCB is connected in series with, and downstream of a circuit breaker, the rated current of both items will be the same, i.e. In ≥ In1 (see (a) of {{FigureRef|F60}})
 
* If the RCCB is located upstream of a group of circuits, protected by circuit breakers, as shown in (b) of {{FigureRef|F60}}, then the RCCB rated current will be given by: In ≥ ku x ks (In1 + In2 + In3 + In4)
*If the RCCB is connected in series with, and downstream of a circuit-breaker, the rated current of both items will be the same, i.e. In ≥ In1 (see '''Fig. F75a''')  
*If the RCCB is located upstream of a group of circuits, protected by circuit-breakers, as shown in '''Figure F75b''', then the RCCB rated current will be given by: In ≥ ku x ks (In1 + In2 + In3 + In4)
 
 
[[File:FigF75.jpg|none]]
 
'''''Fig. F75:''' Residual current circuit-breakers (RCCBs)''
 


=== Electrodynamic withstand requirements ===
=== Electrodynamic withstand requirements ===
Protection against short-circuits must be provided by an upstream SCPD (Short-Circuit Protective Device). Coordination between the RCCB and the SCPDs is necessary, and manufacturers generally provide tables associating RCCBs and circuit breakers or fuses.


Protection against short-circuits must be provided by an upstream SCPD (Short-Circuit Protective Device) but it is considered that where the RCCB is located in the same distribution box (complying with the appropriate standards) as the downstream circuit-breakers (or fuses), the short-circuit protection afforded by these (outgoing-circuit) SCPDs is an adequate alternative. Coordination between the RCCB and the SCPDs is necessary, and manufacturers generally provide tables associating RCCBs and circuit-breakers or fuses.
{{FigImage|DB422265|svg|F60|Residual current circuit breakers (RCCBs)}}
 


[[ru:Чувствительность УЗО к помехам]]
[[fr:Protection contre les chocs et incendies électriques]]
[[zh:RCDs 对于扰动的灵敏性]]
[[de:Schutz gegen elektrischen Schlag]]

Latest revision as of 09:49, 22 June 2022

In certain cases, aspects of the environment can disturb the correct operation of RCDs:

  • “nuisance” tripping: Break in power supply without the situation being really hazardous. This type of tripping is often repetitive, causing major inconvenience and detrimental to the quality of the user’s electrical power supply.
  • non-tripping, in the event of a hazard. Less perceptible than nuisance tripping, these malfunctions must still be examined carefully since they undermine user safety.

Main electrical disturbance types

Permanent earth leakage currents

Every LV installation has a permanent leakage current to earth, which is either due to:

  • Unbalance of the intrinsic capacitance between live conductors and earth for three-phase circuits or
  • Capacitance between live conductors and earth for single-phase circuits

The larger the installation, the greater its capacitance with consequently increased leakage current.

The capacitive current to earth is sometimes increased significantly by filtering capacitors associated with electronic equipment (automation, IT and computer- based systems, etc.).

In the absence of more precise data, permanent leakage current in a given installation can be estimated from the following values, measured at 230 V 50 Hz:

  • Single-phase or three-phase line: 1.5 mA /100m
  • Heating floor: 1mA / kW
  • Fax terminal, printer: 1 mA
  • Microcomputer, workstation: 2 mA
  • Copy machine: 1.5 mA

Since RCDs complying with IEC and many national standards may trip between 0.5 IΔn and IΔn, for residual currents higher than 0.5 IΔn it is recommended to divide the installation by sub-division of circuits to avoid unwanted tripping.

For very particular cases, such as the extension, or partial renovation of extended IT-earthed installations, the manufacturers must be consulted.

High frequency components (harmonics, transients, etc.), are generated by computer equipment power supplies, converters, motors with speed regulators, fluorescent lighting systems and in the vicinity of high power switching devices and reactive energy compensation banks.

Part of these high frequency currents may flow to earth through parasitic capacitances. Although not hazardous for the user, these currents can still cause the nuisance tripping of differential devices.

SI type RCDs have a specific frequency response curve designed to prevent nuisance tripping when non-dangerous high frequency residual currents are present.

Energization

The initial energization of the capacitances mentioned above gives rise to high frequency transient currents of very short duration, similar to that shown in Figure F53.

The sudden occurrence of a first-fault in an IT-earthed system also causes transient earth-leakage currents at high frequency, due to the sudden rise of the two healthy phases to phase/phase voltage above earth.

SI type RCDs present a small tripping delay, allowing to let pass this transient current without nuisance tripping.

Fig. F53 – Standardized 0.5 μs/100 KHz current transient wave

Common mode overvoltages

Electrical networks are subject to overvoltages due to lightning strikes or to abrupt changes of system operating conditions (faults, fuse operation, switching, etc.).

These sudden changes often cause large transient voltages and currents in inductive and capacitive circuits. Records have established that, on LV systems, overvoltages remain generally below 6 kV, and that they can be adequately represented by the conventional 1.2/50 μs impulse wave (see Figure F54).

Fig. F54 – Standardized 1.2/50 μs voltage transient wave

These overvoltages give rise to transient currents represented by a current impulse wave of the conventional 8/20 μs form, having a peak value of several tens of amperes (see Figure F55).

The transient currents flow to earth via the capacitances of the installation.

SI type RCDs offer a high surge current capability and can withstand a 8/20µs current impulse higher than 3kA.

Fig. F55 – Standardized current-impulse wave 8/20 μs

Main climatic disturbance types

Cold

In the cases of temperatures under - 5°C, very high sensitivity electromechanical relays in the RCD may be “welded” by the condensation – freezing action.

Type “SI” devices can operate at temperatures down to - 25 °C.

Atmospheres with high concentrations of chemicals or dust

The special alloys used to make the RCDs can notably be damaged by corrosion. Dust can also block the movement of mechanical parts.

See the measures to be taken according to the levels of severity defined by standards in Figure F56.

Regulations define the choice of earth leakage protection and its implementation.

The main reference text is IEC 60364-5-51:

  • It gives a classification (AFx) for external influences in the presence of corrosive or polluting substances,
  • It defines the choice of materials to be used according to extreme influences.
Fig. F56 – External influence classification according to IEC 60364-5-51 standard
Presence of corrosive or polluting substances (IEC 60364-5-51) Influence of the electrical network Characteristics required for selection and erection of equipment
Clean network Disturbed network
AF1 Negligible presence Standard immunized residual current protections

Type AC: DB431079.svg

Super-immunized residual current protections

Type A SI: DB431080.svg

Normal
AF2 Significant presence of atmospheric origin Super-immunized residual current protections

Type A SI: DB431080.svg

According to the nature of substances (for example, compliance to salt mist test according to IEC 60068-2-11)
AF3 Intermittent or accidental subjection to corrosive or polluting chemical substances Super-immunized residual current protections

Type A SI: DB431080.svg
+
Appropriate additional protection (sealed cabinet or unit)

Protection against corrosion according to equipment specification
AF4 Continuous subjection to corrosive or polluting chemical substances Super-immunized residual current protections

Type A SI: DB431080.svg
+
Appropriate additional protection (sealed cabinet or unit + overpressure)

Equipment specially designed according to the nature of substances
Examples of exposed sites External influences
Iron and steel works. Presence of sulfur, sulfur vapor, hydrogen sulfide.
Marinas, trading ports, boats, sea edges, naval shipyards. Salt atmospheres, humid outside, low temperatures.
Swimming pools, hospitals, food & beverage. Chlorinated compounds.
Petrochemicals. Hydrogen, combustion gases, nitrogen oxides.
Breeding facilities, tips. Hydrogen sulfide.

Type SI RCDs immunity to nuisance tripping

Type SI RCDs have been designed to avoid nuisance tripping or non-tripping in case of polluted network, lightning effect, high frequency currents, RF waves, etc.

Figure F57 below indicates the levels of tests undergone by this type of RCDs.

Fig. F57 – Immunity to nuisance tripping tests undergone by Schneider Electric RCDs
Disturbance type Rated test wave Immunity

Acti 9, ID-RCCB, DPN Vigi, Vigi iC60, Vigi C120, Vigi NG125 SI type

Continuous disturbances
Harmonics 1 kHz Earth leakage current = 8 x I∆n
Transient disturbances
Lightning induced overvoltage 1.2 / 50 µs pulse

(IEC/EN 61000-4-5)

4.5 kV between conductors 5.5 kV / earth
Lightning induced current 8 / 20 µs pulse

(IEC/EN 61008)

5 kA peak
Switching transient, indirect lightning currents 0.5 µs / 100 kHz “ring wave”

(IEC/EN 61008)

400 A peak
Downstream surge arrester operation, capacitance loading 10 ms pulse 500 A
Electromagnetic compatibility
Inductive load switching, fluorescent lights, motors, etc.) Repeated bursts

(IEC 61000-4-4)

5 kV / 2.5 kHz

4 kV / 400 kHz

Fluorescent lights, thyristor controlled circuits, etc. RF conducted waves

(level 4 IEC 61000-4-6)
(level 4 IEC 61000-4-16)


30 V (150 kHz to 230 MHz)

250 mA (15 kHz to 150 kHz)

RF waves (TV & radio, broadcact, telecommunications,etc.) RF radiated waves 80 MHz to 1 GHz

(IEC 61000-4-3)

30 V / m

Recommendations concerning the installation of RCDs with separate toroidal current transformers

The detector of residual current is a closed magnetic circuit (usually circular) of very high magnetic permeability, on which is wound a coil of wire, the ensemble constituting a toroidal (or ring-type) current transformer.

Because of its high permeability, any small deviation from perfect symmetry of the conductors encompassed by the core, and the proximity of ferrous material (steel enclosure, chassis members, etc.) can affect the balance of magnetic forces sufficiently, at times of large load currents (motor-starting current, transformer energizing current surge, etc.) to cause unwanted tripping of the RCD.

Unless particular measures are taken, the ratio of operating current IΔn to maximum phase current Iph (max.) is generally less than 1/1000.

This limit can be increased substantially (i.e. the response can be desensitized) by adopting the measures shown in Figure F58, and summarized in Figure F59.

L = twice the diameter of the magnetic ring core
Fig. F58 – Means of reducing the ratio IΔn/Iph (max.)
Fig. F59 – Means of reducing the ratio IΔn/Iph (max.)
Measures Diameter (mm) Sensitivity diminution factor
Careful centralizing of cables through the ring core 3
Oversizing of the ring core ø 50 → ø 100 2
ø 80 → ø 200 2
ø 120 → ø 300 6
Use of a steel or soft-iron shielding sleeve ø 50 4
  • Of wall thickness 0.5 mm
ø 80 3
  • Of length 2 x inside diameter of ring core
ø 120 3
  • Completely surrounding the conductors and overlapping
    the circular core equally at both ends
ø 200 2
  • These measures can be combined. By carefully centralizing the cables in a ring core of 200 mm diameter, where a 50 mm core would be large enough, and using a sleeve, the ratio 1/1000 could become 1/30000.

Choice of characteristics of a residual-current circuit breaker (RCCB - IEC 61008)

Rated current

The rated current of a RCCB is chosen according to the maximum sustained load current it will carry.

  • If the RCCB is connected in series with, and downstream of a circuit breaker, the rated current of both items will be the same, i.e. In ≥ In1 (see (a) of Figure F60)
  • If the RCCB is located upstream of a group of circuits, protected by circuit breakers, as shown in (b) of Figure F60, then the RCCB rated current will be given by: In ≥ ku x ks (In1 + In2 + In3 + In4)

Electrodynamic withstand requirements

Protection against short-circuits must be provided by an upstream SCPD (Short-Circuit Protective Device). Coordination between the RCCB and the SCPDs is necessary, and manufacturers generally provide tables associating RCCBs and circuit breakers or fuses.

Fig. F60 – Residual current circuit breakers (RCCBs)
Share