TT system - Practical aspects: Difference between revisions
(update_2018) |
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "") |
||
(10 intermediate revisions by 2 users not shown) | |||
Line 1: | Line 1: | ||
{{Menu_Protection_against_electric_shocks}} | {{Menu_Protection_against_electric_shocks}}__TOC__ | ||
__TOC__ | |||
== Specified maximum disconnecting time == | == Specified maximum disconnecting time == | ||
The tripping times of RCDs are generally lower than those required in most national standards; this feature facilitates their use and allows the adoption of an effective | The tripping times of RCDs are generally lower than those required in most national standards; this feature facilitates their use and allows the adoption of an effective selective protection. | ||
IEC 60364-4-41 specifies the maximum operating time of protective devices used in TT system for the protection against indirect contact: | IEC 60364-4-41 specifies the maximum operating time of protective devices used in TT system for the protection against indirect contact: | ||
* For all final circuits with a rated current not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment, the maximum disconnecting time will not exceed the values indicated in {{FigRef|F13}} | * For all final circuits with a rated current not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment, the maximum disconnecting time will not exceed the values indicated in {{FigRef|F13}} | ||
* For all other circuits, the maximum disconnection time is fixed to 1 s. This limit enables | * For all other circuits, the maximum disconnection time is fixed to 1 s. This limit enables selectivity between RCDs when installed on distribution circuits. | ||
{{ | {{tb-start|id=Tab1151|num=F13|title=Maximum disconnecting times in TT system for final circuits not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment|cols=2}} | ||
{| class="wikitable" | |||
|- | |- | ||
! Uo{{ | ! Uo{{tn|A}} (V AC) | ||
! T (s) | ! T (s) | ||
|- | |- | ||
Line 27: | Line 25: | ||
| Uo > 400 | | Uo > 400 | ||
| 0.04 | | 0.04 | ||
| | |} | ||
{{ | {{tb-notes | ||
| | |A= Uo is the nominal phase to earth voltage }} | ||
RCD is a general term for all devices operating on the residual-current principle. | RCD is a general term for all devices operating on the residual-current principle. | ||
Line 35: | Line 33: | ||
RCCB (Residual Current Circuit Breaker) as defined in IEC 61008 series is a specific class of RCD. | RCCB (Residual Current Circuit Breaker) as defined in IEC 61008 series is a specific class of RCD. | ||
General type and S type (Selective) of IEC 61008 have tripping time/current characteristics as shown in {{FigRef|F14}}. These characteristics allow a certain degree of selective tripping between the several combinations of ratings and types, as shown later in [[ | General type and S type (Selective) of IEC 61008 have tripping time/current characteristics as shown in {{FigRef|F14}}. These characteristics allow a certain degree of selective tripping between the several combinations of ratings and types, as shown later in [[Coordination of residual current protective devices]]. Industrial type RCD according to IEC 60947-2 provide more possibilities of selectivity due to their flexibility of time-delaying. | ||
{{ | {{tb-start|id=Tab1152|num=F14|title=Maximum operating time of RCDs (in seconds)|cols=3}} | ||
{| class="wikitable" | |||
|- | |- | ||
! | ! x I<sub>Δn</sub> | ||
! | ! | ||
! 1 | ! 1 | ||
Line 74: | Line 73: | ||
| Time-delay (other) | | Time-delay (other) | ||
| colspan="4" | According to manufacturer | | colspan="4" | According to manufacturer | ||
| | |} | ||
== Case of distribution circuits == | == Case of distribution circuits == | ||
Line 82: | Line 80: | ||
IEC 60364-4-41 and a number of national standards recognize a maximum tripping time of 1 second in installation distribution circuits (as opposed to final circuits). | IEC 60364-4-41 and a number of national standards recognize a maximum tripping time of 1 second in installation distribution circuits (as opposed to final circuits). | ||
This allows a degree of | This allows a degree of selectivity to be achieved: | ||
* At level A: Time-delayed RCD, e.g. “S” type | * At level A: Time-delayed RCD, e.g. “S” type | ||
* At level B: Instantaneous RCD. | * At level B: Instantaneous RCD. | ||
Line 88: | Line 86: | ||
{{FigImage|DB422239_EN|svg|F15|Distribution circuits}} | {{FigImage|DB422239_EN|svg|F15|Distribution circuits}} | ||
== Case where the exposed conductive parts of an appliance, or group of appliances, are connected to a separate earth electrode == | |||
(see {{FigRef|F16}}) | (see {{FigRef|F16}}) | ||
Line 97: | Line 95: | ||
{{FigImage|DB422240_EN|svg|F16|Separate earth electrode}} | {{FigImage|DB422240_EN|svg|F16|Separate earth electrode}} | ||
== Protection when exposed conductive parts are not connected to earth == | |||
(see {{FigRef|F17}}) | (see {{FigRef|F17}}) | ||
Line 108: | Line 106: | ||
[[fr:Protection contre les chocs et incendies électriques]] | [[fr:Protection contre les chocs et incendies électriques]] | ||
[[de:Schutz gegen elektrischen Schlag]] | [[de:Schutz gegen elektrischen Schlag]] | ||
Latest revision as of 09:48, 22 June 2022
Specified maximum disconnecting time
The tripping times of RCDs are generally lower than those required in most national standards; this feature facilitates their use and allows the adoption of an effective selective protection.
IEC 60364-4-41 specifies the maximum operating time of protective devices used in TT system for the protection against indirect contact:
- For all final circuits with a rated current not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment, the maximum disconnecting time will not exceed the values indicated in Fig. F13
- For all other circuits, the maximum disconnection time is fixed to 1 s. This limit enables selectivity between RCDs when installed on distribution circuits.
Uo[a] (V AC) | T (s) |
---|---|
50 < Uo ≤ 120 | 0.3 |
120 < Uo ≤ 230 | 0.2 |
230 < Uo ≤ 400 | 0.07 |
Uo > 400 | 0.04 |
- ^ Uo is the nominal phase to earth voltage
RCD is a general term for all devices operating on the residual-current principle.
RCCB (Residual Current Circuit Breaker) as defined in IEC 61008 series is a specific class of RCD.
General type and S type (Selective) of IEC 61008 have tripping time/current characteristics as shown in Fig. F14. These characteristics allow a certain degree of selective tripping between the several combinations of ratings and types, as shown later in Coordination of residual current protective devices. Industrial type RCD according to IEC 60947-2 provide more possibilities of selectivity due to their flexibility of time-delaying.
x IΔn | 1 | 2 | 5 | > 5 | |
---|---|---|---|---|---|
Domestic | Instantaneous | 0.3 | 0.15 | 0.04 | 0.04 |
Type S | 0.5 | 0.2 | 0.15 | 0.15 | |
Industrial | Instantaneous | 0.3 | 0.15 | 0.04 | 0.04 |
Time-delay : 0.06 s | 0.5 | 0.2 | 0.15 | 0.15 | |
Time-delay (other) | According to manufacturer |
Case of distribution circuits
(see Fig. F15)
IEC 60364-4-41 and a number of national standards recognize a maximum tripping time of 1 second in installation distribution circuits (as opposed to final circuits).
This allows a degree of selectivity to be achieved:
- At level A: Time-delayed RCD, e.g. “S” type
- At level B: Instantaneous RCD.
Case where the exposed conductive parts of an appliance, or group of appliances, are connected to a separate earth electrode
(see Fig. F16)
Fault Protection is provided by a RCD at the circuit breaker level protecting each group or separately-earthed individual appliance.
In each case, the sensitivity must be compatible with the resistance of the earth electrode concerned.
Protection when exposed conductive parts are not connected to earth
(see Fig. F17)
(In the case of an existing installation where the location is dry and provision of an earthing connection is not possible, or in the event that a protective earth wire becomes broken).
RCDs of high sensitivity (≤ 30 mA) will afford both fault protection (against indirect contact hazards), and the additional protection against the dangers of contact with live parts (direct contact).