Breaking of the neutral conductor: Difference between revisions
(update_2018) |
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "") |
||
(7 intermediate revisions by 2 users not shown) | |||
Line 1: | Line 1: | ||
{{Menu_Sizing_and_protection_of_conductors}} | {{Menu_Sizing_and_protection_of_conductors}} | ||
[[File:DB422335.png]] | [[File:DB422335.png]] | ||
(see {{FigRef| | (see {{FigRef|G68}}) | ||
The need to break or not the neutral conductor is related to the protection against indirect contact (fault protection). | The need to break or not the neutral conductor is related to the protection against indirect contact (fault protection). | ||
Line 17: | Line 16: | ||
{{footnotes}} | {{footnotes}} | ||
<references> | <references> | ||
{{fn-detail|1|In some coutries the rules applied for TN-S are the same | {{fn-detail|1|In some coutries the rules applied for TN-S are the same as the rules for TN-C}} | ||
</references> | </references> | ||
Latest revision as of 09:49, 22 June 2022
(see Fig. G68)
The need to break or not the neutral conductor is related to the protection against indirect contact (fault protection).
In TN-C scheme
The neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor.
In TT, TN-S and IT schemes[1]
In the event of a fault, the circuit-breaker will open all poles, including the neutral pole, i.e. the circuit-breaker is omnipolar.
The action can only be achieved with fuses in an indirect way, in which the operation of one or more fuses triggers a mechanical trip-out of all poles of an associated series-connected load-break switch.
Notes
- ^ In some coutries the rules applied for TN-S are the same as the rules for TN-C