Chapter G

Sizing and protection of conductors


Isolation of the neutral conductor: Difference between revisions

From Electrical Installation Guide
Home > Sizing and protection of conductors > The neutral conductor > Isolation of the neutral conductor
m (1 revision imported: Migrated pages - Remove empty lines begin pages)
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "")
 
(3 intermediate revisions by 2 users not shown)
Line 56: Line 56:
{{tb-notes
{{tb-notes
|A= Authorized for TT or TN-S systems if a RCD is installed at the origin of the circuit or upstream of it, and if no artificial neutral is distributed downstream of its location
|A= Authorized for TT or TN-S systems if a RCD is installed at the origin of the circuit or upstream of it, and if no artificial neutral is distributed downstream of its location
|B= The neutral overcurrent protection is not necessary:  
|B= The neutral overcurrent protection is not necessary:<br>
|txn1= &nbsp;&nbsp;&nbsp;&nbsp; - If the neutral conductor is protected against short-circuits by a device placed upstream, or,  
&nbsp;&nbsp;&nbsp;&nbsp; - If the neutral conductor is protected against short-circuits by a device placed upstream, or,<br>
|txn2= &nbsp;&nbsp;&nbsp;&nbsp; - If the circuit is protected by a RCD which sensitivity is less than 15% of the neutral admissible current.
&nbsp;&nbsp;&nbsp;&nbsp; - If the circuit is protected by a RCD which sensitivity is less than 15% of the neutral admissible current.
|C= In some coutries the rules applied for TN-S are the same as the rules for TN-C }}
|C= In some coutries the rules applied for TN-S are the same as the rules for TN-C }}
[[ru:Изоляция нейтрального провода]]
[[zh:中性线的隔离]]

Latest revision as of 09:48, 22 June 2022

DB422336.png

(see Fig. G68)

It is considered to be the good practice that every circuit be provided with the means for its isolation.

Fig. G68 – The various situations in which the neutral conductor may appear
TT TN-C TN-S IT
Single-phase

(Phase-Neutral)

DB422337.png

or
DB422340.png

DB422338.png DB422337.png DB422339.png[a]

or
DB422337.png

Single-phase

(Phase-Phase)

DB422344.png[b]

or
DB422345.png

DB422345.png DB422344.png[b]

or
DB422345.png

DB422345.png
Three-phase four wires

Sn ≥ Sph

DB422341.png DB422342.png DB422341.png[c] DB422343.png[a]

or
DB422341.png

Three-phase four wires Sn < Sph DB422343.png DB422343.png DB422343.png[a]

or
DB422341.png

  1. ^ 1 2 3 The neutral overcurrent protection is not necessary:
         - If the neutral conductor is protected against short-circuits by a device placed upstream, or,
         - If the circuit is protected by a RCD which sensitivity is less than 15% of the neutral admissible current.
  2. ^ 1 2 Authorized for TT or TN-S systems if a RCD is installed at the origin of the circuit or upstream of it, and if no artificial neutral is distributed downstream of its location
  3. ^ In some coutries the rules applied for TN-S are the same as the rules for TN-C
Share