Talk:Circuit-breaker ( full page )/Archive 1: Difference between revisions
(Created page with 'Hello I think, that there is made a mistake by 'Rated impulse-withstand voltage (Uimp)' For industrial devices we can really speak about Uimp=8kV, if we speak about overvoltag…') |
(Wikitext talk to Structured Discussions conversion) |
||
(2 intermediate revisions by 2 users not shown) | |||
Line 1: | Line 1: | ||
{{Archive for converted wikitext talk page|from=Talk:Circuit-breaker ( full page )|date=2019-12-18}} | |||
Hello | Hello | ||
Latest revision as of 13:23, 18 December 2019
This page is an archive. Do not edit the contents of this page. Please direct any additional comments to the current talk page.
Hello
I think, that there is made a mistake by 'Rated impulse-withstand voltage (Uimp)'
For industrial devices we can really speak about Uimp=8kV, if we speak about overvoltage category IV and nominal voltage 690V. But domestic devices standard do not know voltages over 3x400 V and highest overvoltage category there is III. So - correct 'usual' Uimp by those installation is 4 kV. Some (selektive) Main CB-s are rather exceptions of that rule.
BR
trebla