The main possible connection configurations are as follows ('''Fig. D9'''): | The main possible connection configurations are as follows ('''Fig. D9'''): | ||
Line 11: | Line 11: | ||
---- | ---- | ||
[[File:FigD09.jpg|none|500x292px]] | |||
'''''Fig. D9:''' MV circuit configuration'' | |||
---- | ---- | ||
Line 21: | Line 22: | ||
<br> | <br> | ||
{| style="width: 65%; height: 122px | {| class="wikitable" style="width: 65%; height: 122px" | ||
|- | |- | ||
| | | | ||
! colspan="3" | MV circuit configuration | |||
|- | |- | ||
! Characteristic to consider | |||
! Single feeder | |||
! Open ring 1 MV substation | |||
! Open ring 2 MV substations | |||
|- | |- | ||
| Site topology | |||
| Any <br>< 25000m² | |||
| Building with one <br>level or several buildings<br>≤ 25000m² | |||
| Several buildings<br>≥ 25000m² | |||
|- | |- | ||
| Maintainability | | Maintainability |
Revision as of 13:10, 15 November 2013
The main possible connection configurations are as follows (Fig. D9):
- single feeder, one or several transformers
- open ring, one MV incomer
- open ring, 2 MV incomers
The basic configuration is a radial single-feeder architecture, with one single transformer.
In the case of using several transformers, no ring is realised unless all of the transformers are located in a same substation.
Closed-ring configuration is not taken into account.
Fig. D9: MV circuit configuration
For the different possible configurations, the most probable and usual set of characteristics is given in the table on Fig D10.
MV circuit configuration | |||
---|---|---|---|
Characteristic to consider | Single feeder | Open ring 1 MV substation | Open ring 2 MV substations |
Site topology | Any < 25000m² |
Building with one level or several buildings ≤ 25000m² |
Several buildings ≥ 25000m² |
Maintainability | Minimal or standard | Enhanced | Enhanced |
Power demand | Any | > 1250kVA | > 2500kVA |
Disturbance sensitivity | Long interruption acceptable | Short interruption acceptable | Short interruption acceptable |
Fig. D10: Typical values of the installation characteristics
Another exceptional configuration: power supply by 2 MV substations and connection of the transformers to each of these 2 substations (MV “double ended” connection).