Induction motors: Difference between revisions
m (r2.7.2) (robot Adding: zh:感应电机) |
m (added proper blue background for math formula inside blue box) |
||
Line 4: | Line 4: | ||
{| width="60%" cellspacing="1" cellpadding="1" border="1" | {| width="60%" cellspacing="1" cellpadding="1" border="1" | ||
|- | |- | ||
| bgcolor="#0099cc" | The nominal power in kW (Pn) of a motor indicates its rated equivalent mechanical power output.<br>The apparent power in kVA (Pa) supplied to the motor is a function of the output, the motor efficiency and the power factor | | bgcolor="#0099cc" | The nominal power in kW (Pn) of a motor indicates its rated equivalent mechanical power output.<br>The apparent power in kVA (Pa) supplied to the motor is a function of the output, the motor efficiency and the power factor: | ||
<math>\definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue} Pa=\frac{Pn}{n\cos\phi}</math> | |||
|} | |} | ||
<br> | <br> |
Revision as of 19:23, 12 September 2013
The nominal power in kW (Pn) of a motor indicates its rated equivalent mechanical power output. The apparent power in kVA (Pa) supplied to the motor is a function of the output, the motor efficiency and the power factor: [math]\displaystyle{ \definecolor{bgblue}{RGB}{0,153,204}\pagecolor{bgblue} Pa=\frac{Pn}{n\cos\phi} }[/math] |
Current demand
The full-load current Ia supplied to the motor is given by the following formulae:
- 3-phase motor: Ia = Pn x 1,000 / (√3 x U x η x cosφ)
- 1-phase motor: Ia = Pn x 1,000 / (U x η x cosφ)
where
Ia: current demand (in amps)
Pn: nominal power (in kW)
U: voltage between phases for 3-phase motors and voltage between the terminals for single-phase motors (in volts). A single-phase motor may be connected phase-to-neutral or phase-to-phase.
η: per-unit efficiency, i.e. output kW / input kW
cosφ: power factor, i.e. kW input / kVA input
Subtransient current and protection setting
- Subtransient current peak value can be very high ; typical value is about 12 to 15 times the rms rated value Inm. Sometimes this value can reach 25 times Inm.
- Schneider Electric circuit-breakers, contactors and thermal relays are designed to withstand motor starts with very high subtransient current (subtransient peak value can be up to 19 times the rms rated value Inm).
- If unexpected tripping of the overcurrent protection occurs during starting, this means the starting current exceeds the normal limits. As a result, some maximum switchgear withstands can be reached, life time can be reduced and even some devices can be destroyed. In order to avoid such a situation, oversizing of the switchgear must be considered.
- Schneider Electric switchgears are designed to ensure the protection of motor starters against short-circuits. According to the risk, tables show the combination of circuit-breaker, contactor and thermal relay to obtain type 1 or type 2 coordination (see chapter N).
Motor starting current
Although high efficiency motors can be found on the market, in practice their starting currents are roughly the same as some of standard motors.
The use of start-delta starter, static soft start unit or variable speed drive allows to reduce the value of the starting current (Example : 4 Ia instead of 7.5 Ia).
Compensation of reactive-power (kvar) supplied to induction motors
It is generally advantageous for technical and financial reasons to reduce the current supplied to induction motors. This can be achieved by using capacitors without affecting the power output of the motors.
The application of this principle to the operation of induction motors is generally referred to as “power-factor improvement” or “power-factor correction”.
As discussed in chapter L, the apparent power (kVA) supplied to an induction motor can be significantly reduced by the use of shunt-connected capacitors. Reduction of input kVA means a corresponding reduction of input current (since the voltage remains constant).
Compensation of reactive-power is particularly advised for motors that operate for long periods at reduced power.
As noted above [math]\displaystyle{ \mbox{cos}\phi= \frac{\mbox{kW input}}{\mbox{kVA input}} }[/math] so that a kVA input reduction in kVA input will increase (i.e. improve) the value of cosφ
The current supplied to the motor, after power-factor correction, is given by:[math]\displaystyle{ \mbox{I} = \mbox{Ia}\frac{\mbox{cos}\phi}{\mbox{cos}\phi^'} }[/math]
where cos φ is the power factor before compensation and cos φ' is the power factor after compensation, Ia being the original current.
Figure A4 below shows, in function of motor rated power, standard motor current values for several voltage supplies.
kW | hp | 230V | 380 - 415V | 400V | 440- 480 V | 500V | 690V |
A | A | A | A | A | A | ||
0.18 0.25 0.37 |
- - - |
1.0 1.5 1.9 |
- - - |
0.6 0.85 1.1 |
- - - |
0.48 0.68 0.88 |
0.35 0.49 0.64 |
- 0.55 - |
1/2 - 3/4 |
- 2.6 - |
1.3 - 1.8 |
- 1.5 - |
1.1 - 1.6 |
- 1.2 - |
- 0.87 - |
- 0.75 1.1 |
1 - - |
- 3.3 4.7 |
2.3 - - |
- 1.9 2.7 |
2.1 - - |
- 1.5 2.2 |
- 1.1 1.6 |
- - 1.5 |
1-1/2 2 - |
- - 6.3 |
3.3 4.3 - |
- - 3.6 |
3.0 3.4 - |
- - 2.9 |
- - 2.1 |
2.2 - 3.0 |
- 3 - |
8.5 - 11.3 |
- 6.1 - |
4.9 - 6.5 |
- 4.8 - |
3.9 - 5.2 |
2.8 - 3.8 |
3.7 4 5.5 |
- - - |
- 15 20 |
- 9.7 - |
- 8.5 11.5 |
- 7.6 - |
- 6.8 9.2 |
- 4.9 6.7 |
- - 7.5 |
7-1/2 10 - |
- - 27 |
14.0 18.0 - |
- - 15.5 |
11.0 14.0 - |
- - 12.4 |
- - 8.9 |
11 - - |
- 15 20 |
38.0 - - |
- 27.0 34.0 |
22.0 - - |
- 21.0 27.0 |
17.6 - - |
12.8 - - |
15 18.5 - |
- - 25 |
51 61 - |
- - 44 |
39 35 - |
- - 34 |
23 28 - |
17 21 - |
22 - - |
- 30 40 |
72 - - |
- 51 66 |
41 - - |
- 40 52 |
33 - - |
24 - - |
30 37 - |
- - 50 |
96 115 - |
- - 83 |
55 66 - |
- - 65 |
44 53 - |
32 39 - |
- 45 55 |
60 - - |
- 140 169 |
103 - - |
- 80 97 |
77 - - |
- 64 78 |
- 47 57 |
- - 75 |
75 100 - |
- - 230 |
128 165 - |
- - 132 |
96 124 - |
- - 106 |
- - 77 |
90 - 110 |
- 125 - |
278 - 340 |
- 208 - |
160 - 195 |
- 156 |
128 - 156 |
93 - 113 |
- 132 - |
150 - 200 |
- 400 - |
240 - 320 |
- 230 - |
180 - 240 |
- 184 - |
- 134 - |
150 160 185 |
- - - |
- 487 - |
- - - |
- 280 - |
- - - |
- 224 - |
- 162 - |
- 200 220 |
250 - - |
- 609 - |
403 - - |
- 350 - |
302 - - |
- 280 - |
- 203 - |
- 250 280 |
300 - - |
- 748 - |
482 - - |
- 430 - |
361 - - |
- 344 - |
- 250 - |
- - 300 |
350 400 - |
- - - |
560 636 - |
- - - |
414 474 - |
- - - |
- - - |
315 - 335 |
- 540 - |
940 - - |
- - - |
540 - - |
- 515 - |
432 - - |
313 - - |
355 - 375 |
- 500 - |
1061 - - |
- 786 - |
610 - - |
- 590 - |
488 - - |
354 - - |
400 425 450 |
- - - |
1200 - - |
- - - |
690 - - |
- - - |
552 - - |
400 - - |
475 500 530 |
- - - |
- 1478 - |
- - - |
- 850 - |
- - - |
- 680 - |
- 493 - |
560 600 630 |
- - - |
1652 - 1844 |
- - - |
950 - 1060 |
- - - |
760 - 848 |
551 - 615 |
670 710 750 |
- - - |
- 2070 - |
- - - |
- 1190 - |
- - - |
- 952 - |
- 690 - |
800 850 900 |
- - - |
2340 - 2640 |
- - - |
1346 - 1518 |
- - - |
1076 - 1214 |
780 - 880 |
950 1000 |
- - |
- 2910 |
- - |
- 1673 |
- - |
- 1339 |
- 970 |
Fig.A4: Rated operational power and currents