Motor starter configurations: Difference between revisions

From Electrical Installation Guide
m (r2.7.2) (robot Adding: zh:电动机启动配置)
m (cleaned up source: table format, etc ...)
Line 6: Line 6:


----
----
<br>[[Image:FigN66.jpg|none|700px|]]
[[File:FigN66.jpg|none|700px|]]


'''''Fig. N66:''' The various functions and their combinations forming a motor starter''  
'''''Fig. N66:''' The various functions and their combinations forming a motor starter''  
Line 16: Line 16:
The different applicable standards are listed on '''Figure N67.'''  
The different applicable standards are listed on '''Figure N67.'''  


{| cellspacing="1" cellpadding="1" width="65%" border="1"
{| class="wikitable" width="65%"
|-
|-
| bgcolor="#0099cc" | '''Standard'''
! Standard  
| bgcolor="#0099cc" | '''Title'''
! Title
|-
|-
| IEC 60947-1  
| IEC 60947-1  
Line 45: Line 45:
Different utilization categories have been defined for contactors in IEC 60947-4-1. The selection relative to asynchronous motor control is given in '''Figure N68'''.  
Different utilization categories have been defined for contactors in IEC 60947-4-1. The selection relative to asynchronous motor control is given in '''Figure N68'''.  


{| cellspacing="1" cellpadding="1" width="65%" border="1"
{| class="wikitable" width="65%"
|-
|-
| bgcolor="#0099cc" | '''Category'''
! Category  
| bgcolor="#0099cc" | '''Typical applications'''
! Typical applications
|-
|-
| AC-1  
| AC-1  

Revision as of 13:10, 15 November 2013


Different configurations of switchgear and control-gear are commonly proposed. Some examples are shown on Figure N66.


FigN66.jpg

Fig. N66: The various functions and their combinations forming a motor starter



The different applicable standards are listed on Figure N67.

Standard Title
IEC 60947-1 Low-voltage switchgear and controlgear – General rules
IEC 60947-4-1 Contactors and motor-starters –Electromechanical contactors and motor-starters
IEC 60947-4-2 Contactors and motor-starters – AC semiconductor motor controllers and starters
IEC 60947-6-2 Multiple function equipment – Control and protective switching devices (or equipment) (CPS)
IEC 61800 Adjustable speed electrical power drive systems

Fig. N67: Applicable standards



Different utilization categories have been defined for contactors in IEC 60947-4-1. The selection relative to asynchronous motor control is given in Figure N68.

Category Typical applications
AC-1 Non-inductive or slightly inductive loads, resistance furnaces
AC-2 Slip-ring motors: starting, switching off
AC-3 Squirrel-cage motors: starting, switching off motors during running
AC-4 Squirrel-cage motors: starting, plugging(1), inching(2)

(1) By plugging is understood stopping or reversing the motor rapidly by reversing motor primary connections while the motor is running.
(2) By inching (jogging) is understood energizing a motor once or repeatedly for short periods to obtain small movements of the driven mechanism

Fig. N68: Different categories of AC contactors used for asynchronous motor control