Transformer-energizing inrush current: Difference between revisions
m (cleaned up source: table format, etc ...) |
m (1 revision) |
Revision as of 20:14, 10 December 2013
At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see Fig. N31).
Fig N31: Transformer-energizing inrush current
The magnitude of the current peak depends on:
- The value of voltage at the instant of energization
- The magnitude and polarity of the residual flux existing in the core of the transformer
- Characteristics of the load connected to the transformer
The first current peak can reach a value equal to 10 to 15 times the full-load r.m.s. current, but for small transformers (< 50 kVA) may reach values of 20 to 25 times the nominal full-load current. This transient current decreases rapidly, with a time constant θ of the order of several ms to severals tens of ms.
ru:Ток намагничивания трансформатора при включении zh:变压器励磁涌流