Chapter G

Sizing and protection of conductors


Protection of the neutral conductor: Difference between revisions

From Electrical Installation Guide
Home > Sizing and protection of conductors > The neutral conductor > Protection of the neutral conductor
m (1 revision: no page modification, previous revision = imported ch.G pages cleaned-up)
(Cleanup_2016)
Line 1: Line 1:
{{Menu_Sizing_and_protection_of_conductors}}
{{Menu_Sizing_and_protection_of_conductors}}
<br>
 
__TOC__
__TOC__
(see {{FigRef|G64}})  
(see {{FigRef|G64}})  


===== Protection against overload =====
== Protection against overload ==
 
If the neutral conductor is correctly sized (including harmonics), no specific protection of the neutral conductor is required because it is protected by the phase protection. <br>However, in practice, if the c.s.a. of the neutral conductor is lower than the phase c.s.a, a neutral overload protection must be installed.
 
[[File:DB422333.svg]]
 
== Protection against short-circuit  ==
 
If the c.s.a. of the neutral conductor is lower than the c.s.a. of the phase conductor, the neutral conductor must be protected against short-circuit.
 
If the c.s.a. of the neutral conductor is equal or greater than the c.s.a. of the phase conductor, no specific protection of the neutral conductor is required because it is protected by the phase protection.


If the neutral conductor is correctly sized (including harmonics), no specific protection of the neutral conductor is required because it is protected by the phase protection. <br>However, in practice, if the c.s.a. of the neutral conductor is lower than the phase c.s.a, a neutral overload protection must be installed.<br><br>[[File:PictoChap7a.jpg|none]]
[[File:DB422334.svg]]
===== Protection against short-circuit  =====


If the c.s.a. of the neutral conductor is lower than the c.s.a. of the phase conductor, the neutral conductor must be protected against short-circuit.<br>If the c.s.a. of the neutral conductor is equal or greater than the c.s.a. of the phase conductor, no specific protection of the neutral conductor is required because it is protected by the phase protection.<br><br>[[File:PictoChap7b.jpg|none]]
[[ru:Защита нейтрального провода]]
[[ru:Защита нейтрального провода]]
[[zh:中性线的保护]]
[[zh:中性线的保护]]

Revision as of 00:02, 29 November 2016


(see Fig. G64)

Protection against overload

If the neutral conductor is correctly sized (including harmonics), no specific protection of the neutral conductor is required because it is protected by the phase protection.
However, in practice, if the c.s.a. of the neutral conductor is lower than the phase c.s.a, a neutral overload protection must be installed.

DB422333.svg

Protection against short-circuit

If the c.s.a. of the neutral conductor is lower than the c.s.a. of the phase conductor, the neutral conductor must be protected against short-circuit.

If the c.s.a. of the neutral conductor is equal or greater than the c.s.a. of the phase conductor, no specific protection of the neutral conductor is required because it is protected by the phase protection.

DB422334.svg