Definition of reactive power: Difference between revisions

From Electrical Installation Guide
m (1 revision: no page modification, previous revision = imported ch.L pages cleaned-up)
(Cleanup_2016)
Line 11: Line 11:
I<sub>r</sub> is called the '''reactive''' component of the current.
I<sub>r</sub> is called the '''reactive''' component of the current.


 
{{FigImage|DB422580|svg|L1|Current vector diagram}}
[[File:Fig_L01.jpg|none]]
 
 
'''''Fig. L1 :''''' ''Current vector diagram''
 


The previous diagram drawn up for currents also applies to powers, by multiplying each current by the common voltage V. See {{FigRef|L2}}.
The previous diagram drawn up for currents also applies to powers, by multiplying each current by the common voltage V. See {{FigRef|L2}}.


We thus define:
We thus define:
* '''Apparent power''': S = V x I (kVA) <br>
* '''Apparent power''': S = V x I (kVA)  
* '''Active power''': P = V x Ia (kW)<br>
* '''Active power''': P = V x Ia (kW)
* '''Reactive power''': Q = V x Ir (kvar)<br>
* '''Reactive power''': Q = V x Ir (kvar)
 
[[File:Fig_L02.jpg|none]]
 
'''''Fig. L2 :''''' ''Power vector diagram''


{{FigImage|DB422581|svg|L2|Power vector diagram}}


In this diagram, we can see that:
In this diagram, we can see that:
* '''Power Factor''': P/S = cos φ
* '''Power Factor''': P/S = cos φ


This formula is applicable for sinusoidal voltage and current. This is why the '''Power Factor''' is then designated as '''"Displacement Power Factor"'''.
This formula is applicable for sinusoidal voltage and current. This is why the '''Power Factor''' is then designated as '''"Displacement Power Factor"'''.
Line 40: Line 31:
A simple formula is obtained, linking apparent, active and reactive power:  
A simple formula is obtained, linking apparent, active and reactive power:  
* S<sup>2</sup> = P<sup>2</sup> + Q<sup>2</sup>
* S<sup>2</sup> = P<sup>2</sup> + Q<sup>2</sup>


A power factor close to unity means that the apparent power S is minimal. This means that the electrical equipment rating is minimal for the transmission of a given active power P to the load. The reactive power is then small compared with the active
A power factor close to unity means that the apparent power S is minimal. This means that the electrical equipment rating is minimal for the transmission of a given active power P to the load. The reactive power is then small compared with the active
Line 46: Line 36:


A low value of power factor indicates the opposite condition.
A low value of power factor indicates the opposite condition.


'''Useful formulae''' (for balanced and near-balanced loads on 4-wire systems):
'''Useful formulae''' (for balanced and near-balanced loads on 4-wire systems):
Line 62: Line 51:
**Three phase (3 wires or 3 wires + neutral): S = √3.U.I
**Three phase (3 wires or 3 wires + neutral): S = √3.U.I


where:<br>
where:
V= Voltage between phase and neutral <br>
U = Voltage between phases <br>
I = Line current <br>
φ = Phase angle between vectors V and I.
 


{{def
|V| Voltage between phase and neutral
|U| Voltage between phases
|I| Line current
|φ| Phase angle between vectors V and I.}}


== An example of power calculations (see {{FigRef|L3}}) ==
== An example of power calculations (see {{FigRef|L3}}) ==


 
{{TableStart|Tab1330|5col}}
{| class="wikitable"
|-
|-
! colspan="2" | Type of circuit  
! colspan="2" | Type of circuit  
Line 112: Line 100:
|-
|-
| ρ= 0.91 (motor efficiency)
| ρ= 0.91 (motor efficiency)
|}
|-
 
{{TableEnd|Tab1330|L3|Example in the calculation of active and reactive power}}
'''''Fig. L3 :''''' ''Example in the calculation of active and reactive power''
 


The calculations for the three-phase example above are as follows:
The calculations for the three-phase example above are as follows:


Pn = delivered shaft power = 51 kW<br>
{{def|
P = active power consumed
|Pn| delivered shaft power {{=}} 51 kW
|P| active power consumed }}


<math>P=\frac {Pn}{\rho}=\frac{51}{0.91}=56\, kW</math>  
<math>P=\frac {Pn}{\rho}=\frac{51}{0.91}=56\, kW</math>  
Line 136: Line 123:
<math>Q=\sqrt{S^2 - P^2}=\sqrt{65^2 - 56^2}=33\, kvar</math>
<math>Q=\sqrt{S^2 - P^2}=\sqrt{65^2 - 56^2}=33\, kvar</math>


 
{{FigImage|DB422582|svg|L2b|Calculation power diagram}}
[[File:FigL05.jpg|none]]
 
'''''Fig. L2b :''''' ''Calculation power diagram''

Revision as of 23:42, 6 December 2016


For most electrical loads like motors, the current I is lagging behind the voltage V by an angle φ.

If currents and voltages are perfectly sinusoidal signals, a vector diagram can be used for representation.

In this vector diagram, the current vector can be split into two components: one in phase with the voltage vector (component Ia), one in quadrature (lagging by 90 degrees) with the voltage vector (component Ir). See Fig. L1.

Ia is called the active component of the current.

Ir is called the reactive component of the current.

Fig. L1 – Current vector diagram

The previous diagram drawn up for currents also applies to powers, by multiplying each current by the common voltage V. See Fig. L2.

We thus define:

  • Apparent power: S = V x I (kVA)
  • Active power: P = V x Ia (kW)
  • Reactive power: Q = V x Ir (kvar)
Fig. L2 – Power vector diagram

In this diagram, we can see that:

  • Power Factor: P/S = cos φ

This formula is applicable for sinusoidal voltage and current. This is why the Power Factor is then designated as "Displacement Power Factor".

  • Q/S = sinφ
  • Q/P = tanφ

A simple formula is obtained, linking apparent, active and reactive power:

  • S2 = P2 + Q2

A power factor close to unity means that the apparent power S is minimal. This means that the electrical equipment rating is minimal for the transmission of a given active power P to the load. The reactive power is then small compared with the active power.

A low value of power factor indicates the opposite condition.

Useful formulae (for balanced and near-balanced loads on 4-wire systems):

  • Active power P (in kW)
    • Single phase (1 phase and neutral): P = V.I.cos φ
    • Single phase (phase to phase): P = U.I.cos φ
    • Three phase (3 wires or 3 wires + neutral): P = √3.U.I.cos φ
  • Reactive power Q (in kvar)
    • Single phase (1 phase and neutral): Q = V.I.sin φ
    • Single phase (phase to phase): Q = U.I.sin φ
    • Three phase (3 wires or 3 wires + neutral): Q = √3.U.I.sin φ
  • Apparent power S (in kVA)
    • Single phase (1 phase and neutral): S = V.I
    • Single phase (phase to phase): S = U.I
    • Three phase (3 wires or 3 wires + neutral): S = √3.U.I

where:

V = Voltage between phase and neutral
U = Voltage between phases
I = Line current
φ = Phase angle between vectors V and I.

An example of power calculations (see Fig. L3)

Type of circuit Apparent power S (kVA) Active power P (kW) Reactive power Q (kvar)
Single-phase (phase and neutral) S = VI P = VI cos φ Q = VI sin φ
Single-phase (phase to phase) S = UI P = UI cos φ Q = UI sin φ
Example 5 kW of load 10 kVA 5 kW 8.7 kvar
cos φ = 0.5
Three phase 3-wires or 3-wires + neutral S = [math]\displaystyle{ \definecolor{bggrey}{RGB}{234,234,234}\pagecolor{bggrey}\sqrt 3 }[/math] UI P = [math]\displaystyle{ \definecolor{bggrey}{RGB}{234,234,234}\pagecolor{bggrey}\sqrt 3 }[/math] UI cos φ Q = [math]\displaystyle{ \definecolor{bggrey}{RGB}{234,234,234}\pagecolor{bggrey}\sqrt 3 }[/math] UI sin φ
Example Motor Pn = 51 kW 65 kVA 56 kW 33 kvar
cos φ= 0.86
ρ= 0.91 (motor efficiency)
Fig. L3 – Example in the calculation of active and reactive power

The calculations for the three-phase example above are as follows:


delivered shaft power = 51 kW = P
active power consumed =

[math]\displaystyle{ P=\frac {Pn}{\rho}=\frac{51}{0.91}=56\, kW }[/math]

S = apparent power

[math]\displaystyle{ S=\frac{P}{cos \varphi}=\frac {56}{0.86}= 65\, kVA }[/math]

So that, on referring to diagram Figure L3 or using a pocket calculator, the value of tan φ corresponding to a cos φ of 0.86 is found to be 0.59

Q = P tan φ = 56 x 0.59 = 33 kvar (see Figure L15).

Alternatively:

[math]\displaystyle{ Q=\sqrt{S^2 - P^2}=\sqrt{65^2 - 56^2}=33\, kvar }[/math]

Fig. L2b – Calculation power diagram