Practical values of power factor: Difference between revisions
From Electrical Installation Guide
CleanUp2016 (talk | contribs) (Cleanup_2016) |
(fig L6 reviewed - closer to EN book 2016 (separate furnace from ovens) (cleanup_2016)) |
||
Line 33: | Line 33: | ||
| 0.4 to 0.6 || 2.29 to 1.33 | | 0.4 to 0.6 || 2.29 to 1.33 | ||
|- | |- | ||
| rowspan=" | | rowspan="3" |Ovens | ||
| colspan="3" |Ovens using resistance elements | | colspan="3" |Ovens using resistance elements | ||
| 1.0 || 0 | | 1.0 || 0 | ||
Line 42: | Line 42: | ||
| colspan="3" |Dielectric type heating ovens | | colspan="3" |Dielectric type heating ovens | ||
| 0.85 || 0.62 | | 0.85 || 0.62 | ||
|- | |- | ||
| rowspan="4" |Welding | | rowspan="4" |Welding | ||
Line 59: | Line 55: | ||
| colspan="3" |Arc-welding transformer-rectifier set | | colspan="3" |Arc-welding transformer-rectifier set | ||
| 0.7 to 0.8 || 1.02 to 0.75 | | 0.7 to 0.8 || 1.02 to 0.75 | ||
|- | |||
| colspan="4" |Arc furnace | |||
|0.8 | |||
|0.75 | |||
|- | |- | ||
{{TableEnd|Tab1331|L6|Values of cos φ and tan φ for commonly-used equipment}} | {{TableEnd|Tab1331|L6|Values of cos φ and tan φ for commonly-used equipment}} |
Revision as of 10:38, 30 December 2016
Average power factor values for the most commonly-used equipment and appliances
(see Fig. L6)
Equipment and appliances | cos φ | tan φ | |||
---|---|---|---|---|---|
Motor | Common induction motor | loaded at | 0 % | 0.17 | 5.80 |
25% | 0.55 | 1.52 | |||
50 % | 0.73 | 0.94 | |||
75 % | 0.80 | 0.75 | |||
100 % | 0.85 | 0.62 | |||
Lamps | Incandescent lamps | 1.0 | 0 | ||
Fluorescent lamps (uncompensated) | 0.5 | 1.73 | |||
Fluorescent lamps (compensated) | 0.93 | 0.39 | |||
Discharge lamps | 0.4 to 0.6 | 2.29 to 1.33 | |||
Ovens | Ovens using resistance elements | 1.0 | 0 | ||
Induction heating ovens (compensated) | 0.85 | 0.62 | |||
Dielectric type heating ovens | 0.85 | 0.62 | |||
Welding | Resistance-type soldering machines | 0.8 to 0.9 | 0.75 to 0.48 | ||
Fixed 1-phase arc-welding set | 0.5 | 1.73 | |||
Arc-welding motor-generating set | 0.7 to 0.9 | 1.02 to 0.48 | |||
Arc-welding transformer-rectifier set | 0.7 to 0.8 | 1.02 to 0.75 | |||
Arc furnace | 0.8 | 0.75 |
Fig. L6 – Values of cos φ and tan φ for commonly-used equipment