TT system - Practical aspects: Difference between revisions
m (LMischler moved page TT system - Protective measures to TT system - Practical aspects: guide 2018) |
(update_2018) |
||
Line 3: | Line 3: | ||
__TOC__ | __TOC__ | ||
== | == Specified maximum disconnecting time == | ||
The tripping times of RCDs are generally lower than those required in most national standards; this feature facilitates their use and allows the adoption of an effective discriminative protection. | |||
IEC 60364-4-41 specifies the maximum operating time of protective devices used in TT system for the protection against indirect contact: | |||
* For all final circuits with a rated current not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment, the maximum disconnecting time will not exceed the values indicated in {{FigRef|F13}} | |||
* For all other circuits, the maximum disconnection time is fixed to 1 s. This limit enables discrimination between RCDs when installed on distribution circuits. | |||
{{TableStart| | {{TableStart|Tab1151|2col}} | ||
|- | |- | ||
! | ! Uo{{TabRef|Tab1151|a}} (V) | ||
! | ! T (s) | ||
|- | |- | ||
| 50 < Uo ≤ 120 | |||
| 0.3 | |||
|- | |||
| 120 < Uo ≤ 230 | |||
| 0.2 | |||
|- | |||
| 230 < Uo ≤ 400 | |||
| 0.07 | |||
|- | |||
| Uo > 400 | |||
| 0.04 | |||
|- | |||
{{TableEnd|Tab1151|F13|Maximum disconnecting times in TT system for final circuits not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment | |||
|a| Uo is the nominal phase to earth voltage }} | |||
RCD is a general term for all devices operating on the residual-current principle. | |||
RCCB (Residual Current Circuit Breaker) as defined in IEC 61008 series is a specific class of RCD. | |||
General type and S type (Selective) of IEC 61008 have tripping time/current characteristics as shown in {{FigRef|F14}}. These characteristics allow a certain degree of selective tripping between the several combinations of ratings and types, as shown later in sub-clause 5.3. Industrial type RCD according to IEC 60947-2 provide more possibilities of discrimination due to their flexibility of time-delaying. | |||
{{TableStart|Tab1152|3col}} | |||
|- | |||
! X I<sub>Δn</sub> | |||
! | ! | ||
! | ! 1 | ||
! | ! 2 | ||
! 5 | |||
! > 5 | |||
|- | |- | ||
| 3 | | rowspan="2" | Domestic | ||
| | | Instantaneous | ||
| | | 0.3 | ||
| 0.15 | |||
| 0.04 | |||
| 0.04 | |||
|- | |- | ||
| | | Type S | ||
| | | 0.5 | ||
| | | 0.2 | ||
| 0.15 | |||
| 0.15 | |||
|- | |- | ||
| | | rowspan="3" | Industrial | ||
| | | Instantaneous | ||
| | | 0.3 | ||
| 0.15 | |||
| 0.04 | |||
| 0.04 | |||
|- | |- | ||
| | | Time-delay : 0.06 s | ||
| | | 0.5 | ||
| | | 0.2 | ||
| 0.15 | |||
| 0.15 | |||
|- | |- | ||
| | | Time-delay (other) | ||
| | | colspan="4" | According to manufacturer | ||
| | |||
|- | |- | ||
{{TableEnd| | {{TableEnd|Tab1152|F14|Maximum operating time of RCDs (in seconds)}} | ||
== Case of distribution circuits == | |||
(see {{FigRef|F15}}) | |||
( | IEC 60364-4-41 and a number of national standards recognize a maximum tripping time of 1 second in installation distribution circuits (as opposed to final circuits). | ||
This allows a degree of selective discrimination to be achieved: | |||
*At level A: | * At level A: Time-delayed RCD, e.g. “S” type | ||
*At level B: RCD | * At level B: Instantaneous RCD. | ||
{{FigImage|DB422239_EN|svg| | {{FigImage|DB422239_EN|svg|F15|Distribution circuits}} | ||
=== Case where the exposed conductive parts of an appliance, or group of appliances, are connected to a separate earth electrode === | === Case where the exposed conductive parts of an appliance, or group of appliances, are connected to a separate earth electrode === | ||
(see {{FigRef|F16}}) | |||
Fault Protection is provided by a RCD at the circuit breaker level protecting each group or separately-earthed individual appliance. | |||
Protection | |||
In each case, the sensitivity must be compatible with the resistance of the earth electrode concerned. | In each case, the sensitivity must be compatible with the resistance of the earth electrode concerned. | ||
{{FigImage|DB422240_EN|svg| | {{FigImage|DB422240_EN|svg|F16|Separate earth electrode}} | ||
=== Protection when exposed conductive parts are not connected to earth === | |||
(see {{FigRef|F17}}) | |||
(In the case of an existing installation where the location is dry and provision of an earthing connection is not possible, or in the event that a protective earth wire becomes broken). | |||
RCDs of high sensitivity (≤ 30 mA) will afford both fault protection (against indirect contact hazards), and the additional protection against the dangers of contact with live parts (direct contact). | |||
{{ | {{FigImage|DB422243|svg|F17|Unearthed exposed conductive parts (A)}} | ||
[[ru: | [[fr:Protection contre les chocs et incendies électriques]] | ||
[[zh: | [[de:Schutz gegen elektrischen Schlag]] | ||
[[ru:Защита от поражения электрическим током]] | |||
[[zh:电击防护]] |
Revision as of 09:25, 12 April 2018
Specified maximum disconnecting time
The tripping times of RCDs are generally lower than those required in most national standards; this feature facilitates their use and allows the adoption of an effective discriminative protection.
IEC 60364-4-41 specifies the maximum operating time of protective devices used in TT system for the protection against indirect contact:
- For all final circuits with a rated current not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment, the maximum disconnecting time will not exceed the values indicated in Fig. F13
- For all other circuits, the maximum disconnection time is fixed to 1 s. This limit enables discrimination between RCDs when installed on distribution circuits.
Uo[a] (V) | T (s) |
---|---|
50 < Uo ≤ 120 | 0.3 |
120 < Uo ≤ 230 | 0.2 |
230 < Uo ≤ 400 | 0.07 |
Uo > 400 | 0.04 |
[a] Uo is the nominal phase to earth voltage
RCD is a general term for all devices operating on the residual-current principle.
RCCB (Residual Current Circuit Breaker) as defined in IEC 61008 series is a specific class of RCD.
General type and S type (Selective) of IEC 61008 have tripping time/current characteristics as shown in Fig. F14. These characteristics allow a certain degree of selective tripping between the several combinations of ratings and types, as shown later in sub-clause 5.3. Industrial type RCD according to IEC 60947-2 provide more possibilities of discrimination due to their flexibility of time-delaying.
X IΔn | 1 | 2 | 5 | > 5 | |
---|---|---|---|---|---|
Domestic | Instantaneous | 0.3 | 0.15 | 0.04 | 0.04 |
Type S | 0.5 | 0.2 | 0.15 | 0.15 | |
Industrial | Instantaneous | 0.3 | 0.15 | 0.04 | 0.04 |
Time-delay : 0.06 s | 0.5 | 0.2 | 0.15 | 0.15 | |
Time-delay (other) | According to manufacturer |
Case of distribution circuits
(see Fig. F15)
IEC 60364-4-41 and a number of national standards recognize a maximum tripping time of 1 second in installation distribution circuits (as opposed to final circuits).
This allows a degree of selective discrimination to be achieved:
- At level A: Time-delayed RCD, e.g. “S” type
- At level B: Instantaneous RCD.
Case where the exposed conductive parts of an appliance, or group of appliances, are connected to a separate earth electrode
(see Fig. F16)
Fault Protection is provided by a RCD at the circuit breaker level protecting each group or separately-earthed individual appliance.
In each case, the sensitivity must be compatible with the resistance of the earth electrode concerned.
Protection when exposed conductive parts are not connected to earth
(see Fig. F17)
(In the case of an existing installation where the location is dry and provision of an earthing connection is not possible, or in the event that a protective earth wire becomes broken).
RCDs of high sensitivity (≤ 30 mA) will afford both fault protection (against indirect contact hazards), and the additional protection against the dangers of contact with live parts (direct contact).