TT system - Practical aspects: Difference between revisions

From Electrical Installation Guide
m (LMischler moved page TT system - Protective measures to TT system - Practical aspects: guide 2018)
(update_2018)
Line 3: Line 3:
__TOC__
__TOC__


== Protection against indirect contact  ==
== Specified maximum disconnecting time ==


=== General case ===
The tripping times of RCDs are generally lower than those required in most national standards; this feature facilitates their use and allows the adoption of an effective discriminative protection.
Protection against indirect contact is assured by RCDs, the sensitivity IΔn of which complies with the condition <math>I\Delta n\le\frac{50V}{R_A}</math>{{fn|1}}


The choice of sensitivity of the residual current device is a function of the resistance R<sub>A</sub> of the earth electrode for the installation, and is given in {{FigureRef|F28}}.  
IEC 60364-4-41 specifies the maximum operating time of protective devices used in TT system for the protection against indirect contact:
* For all final circuits with a rated current not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment, the maximum disconnecting time will not exceed the values indicated in {{FigRef|F13}}
* For all other circuits, the maximum disconnection time is fixed to 1 s. This limit enables discrimination between RCDs when installed on distribution circuits.


{{TableStart|Tab1156|3col}}
{{TableStart|Tab1151|2col}}
|-
|-
! IΔn
! Uo{{TabRef|Tab1151|a}} (V)
! colspan="2" | Maximum resistance of the earth electrode
! T (s)
|-
|-
| 50 < Uo ≤ 120
| 0.3
|-
| 120 < Uo ≤ 230
| 0.2
|-
| 230 < Uo ≤ 400
| 0.07
|-
| Uo > 400
| 0.04
|-
{{TableEnd|Tab1151|F13|Maximum disconnecting times in TT system for final circuits not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment
|a| Uo is the nominal phase to earth voltage }}
RCD is a general term for all devices operating on the residual-current principle.
RCCB (Residual Current Circuit Breaker) as defined in IEC 61008 series is a specific class of RCD.
General type and S type (Selective) of IEC 61008 have tripping time/current characteristics as shown in {{FigRef|F14}}. These characteristics allow a certain degree of selective tripping between the several combinations of ratings and types, as shown later in sub-clause 5.3. Industrial type RCD according to IEC 60947-2 provide more possibilities of discrimination due to their flexibility of time-delaying.
{{TableStart|Tab1152|3col}}
|-
! X I<sub>Δn</sub>
!  
!  
!(50 V)
! 1
! (25 V)
! 2
! 5
! > 5
|-
|-
| 3 A
| rowspan="2" | Domestic
| 16 Ω
| Instantaneous
| 8 Ω
| 0.3  
| 0.15
| 0.04
| 0.04
|-
|-
| 1 A
| Type S
| 50 Ω
| 0.5
| 25 Ω
| 0.2
| 0.15
| 0.15
|-
|-
| 500 mA
| rowspan="3" | Industrial
| 100 Ω
| Instantaneous
| 50 Ω
| 0.3
| 0.15
| 0.04
| 0.04
|-
|-
| 300 mA
| Time-delay : 0.06 s
| 166 Ω
| 0.5
| 83 Ω
| 0.2
| 0.15
| 0.15
|-
|-
| 30 mA
| Time-delay (other)
| 1666 Ω
| colspan="4" | According to manufacturer
| 833 Ω
|-
|-
{{TableEnd|Tab1156|F28|The upper limit of resistance for an installation earthing electrode which must not be exceeded, for given sensitivity levels of RCDs at U<sub>L</sub> voltage limits of 50 V and 25 V}}
{{TableEnd|Tab1152|F14|Maximum operating time of RCDs (in seconds)}}


=== Case of distribution circuits ===
== Case of distribution circuits ==
(see {{FigRef|F15}})


(see {{FigRef|F29}})  
IEC 60364-4-41 and a number of national standards recognize a maximum tripping time of 1 second in installation distribution circuits (as opposed to final circuits).


IEC 60364-4-41 and a number of national standards recognize a maximum tripping time of 1 second in installation distribution circuits (as opposed to final circuits). This allows a degree of selective discrimination to be achieved:  
This allows a degree of selective discrimination to be achieved:
*At level A: RCD time-delayed, e.g. “S” type  
* At level A: Time-delayed RCD, e.g. “S” type
*At level B: RCD instantaneous
* At level B: Instantaneous RCD.


{{FigImage|DB422239_EN|svg|F29|Distribution circuits}}
{{FigImage|DB422239_EN|svg|F15|Distribution circuits}}


=== Case where the exposed conductive parts of an appliance, or group of appliances, are connected to a separate earth electrode ===
=== Case where the exposed conductive parts of an appliance, or group of appliances, are connected to a separate earth electrode ===
(see {{FigRef|F16}})


(see {{FigRef|F30}})
Fault Protection is provided by a RCD at the circuit breaker level protecting each group or separately-earthed individual appliance.
 
Protection against indirect contact by a RCD at the circuit-breaker level protecting each group or separately-earthed individual appliance.


In each case, the sensitivity must be compatible with the resistance of the earth electrode concerned.
In each case, the sensitivity must be compatible with the resistance of the earth electrode concerned.


{{FigImage|DB422240_EN|svg|F30|Separate earth electrode}}
{{FigImage|DB422240_EN|svg|F16|Separate earth electrode}}
 
== High-sensitivity RCDs  ==
 
(see {{FigRef|F31}})
 
According to IEC 60364-4-41, high sensitivity RCDs ( ≤ 30 mA) must be used for protection of socket outlets with rated current ≤ 20 A in all locations. The use of such RCDs is also recommended in the following cases:
 
*Socket-outlet circuits in wet locations at all current ratings
*Socket-outlet circuits in temporary installations
*Circuits supplying laundry rooms and swimming pools
*Supply circuits to work-sites, caravans, pleasure boats, and travelling fairs. See [[Additional measure of protection against direct contact]] and [[Recommendations applicable to special installations and locations]].
 
{{FigImage|DB422241|svg|F31|Circuit supplying socket-outlets}}
 
== In high fire risk locations  ==
 
(see {{FigRef|F32}})
 
RCD protection at the circuit-breaker controlling all supplies to the area at risk is necessary in some locations, and mandatory in many countries.
 
The sensitivity of the RCD must be ≤ 500 mA, but a 300 mA sensitivity is recommended.
 
{{FigImage|DB422242_EN|svg|F32|Fire-risk location}}
 
== Protection when exposed conductive parts are not connected to earth  ==
 
(see {{FigRef|F33}})


(In the case of an existing installation where the location is dry and provision of an earthing connection is not possible, or in the event that a protective earth wire becomes broken).
=== Protection when exposed conductive parts are not connected to earth ===
(see {{FigRef|F17}})


RCDs of high sensitivity (≤ 30 mA) will afford both protection against indirect-contact hazards, and the additional protection against the dangers of direct-contact.
(In the case of an existing installation where the location is dry and provision of an earthing connection is not possible, or in the event that a protective earth wire becomes broken).


{{FigImage|DB422243|svg|F33|Unearthed exposed conductive parts (A)}}
RCDs of high sensitivity (≤ 30 mA) will afford both fault protection (against indirect contact hazards), and the additional protection against the dangers of contact with live parts (direct contact).


{{footnotes}}
{{FigImage|DB422243|svg|F17|Unearthed exposed conductive parts (A)}}
<references>
{{fn-detail|1| 25 V for work-site installations, agricultural establishments, etc.}}
</references>


[[ru:Система TT: защитные меры]]
[[fr:Protection contre les chocs et incendies électriques]]
[[zh:TT系统保护措施]]
[[de:Schutz gegen elektrischen Schlag]]
[[ru:Защита от поражения электрическим током]]
[[zh:电击防护]]

Revision as of 09:25, 12 April 2018


Specified maximum disconnecting time

The tripping times of RCDs are generally lower than those required in most national standards; this feature facilitates their use and allows the adoption of an effective discriminative protection.

IEC 60364-4-41 specifies the maximum operating time of protective devices used in TT system for the protection against indirect contact:

  • For all final circuits with a rated current not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment, the maximum disconnecting time will not exceed the values indicated in Fig. F13
  • For all other circuits, the maximum disconnection time is fixed to 1 s. This limit enables discrimination between RCDs when installed on distribution circuits.
Uo[a] (V) T (s)
50 < Uo ≤ 120 0.3
120 < Uo ≤ 230 0.2
230 < Uo ≤ 400 0.07
Uo > 400 0.04

[a]  Uo is the nominal phase to earth voltage

Fig. F13 – Maximum disconnecting times in TT system for final circuits not exceeding 63 A with one or more socket-outlets, and 32 A supplying only fixed connected current-using equipment

RCD is a general term for all devices operating on the residual-current principle.

RCCB (Residual Current Circuit Breaker) as defined in IEC 61008 series is a specific class of RCD.

General type and S type (Selective) of IEC 61008 have tripping time/current characteristics as shown in Fig. F14. These characteristics allow a certain degree of selective tripping between the several combinations of ratings and types, as shown later in sub-clause 5.3. Industrial type RCD according to IEC 60947-2 provide more possibilities of discrimination due to their flexibility of time-delaying.

X IΔn 1 2 5 > 5
Domestic Instantaneous 0.3 0.15 0.04 0.04
Type S 0.5 0.2 0.15 0.15
Industrial Instantaneous 0.3 0.15 0.04 0.04
Time-delay : 0.06 s 0.5 0.2 0.15 0.15
Time-delay (other) According to manufacturer
Fig. F14 – Maximum operating time of RCDs (in seconds)

Case of distribution circuits

(see Fig. F15)

IEC 60364-4-41 and a number of national standards recognize a maximum tripping time of 1 second in installation distribution circuits (as opposed to final circuits).

This allows a degree of selective discrimination to be achieved:

  • At level A: Time-delayed RCD, e.g. “S” type
  • At level B: Instantaneous RCD.
Fig. F15 – Distribution circuits

Case where the exposed conductive parts of an appliance, or group of appliances, are connected to a separate earth electrode

(see Fig. F16)

Fault Protection is provided by a RCD at the circuit breaker level protecting each group or separately-earthed individual appliance.

In each case, the sensitivity must be compatible with the resistance of the earth electrode concerned.

Fig. F16 – Separate earth electrode

Protection when exposed conductive parts are not connected to earth

(see Fig. F17)

(In the case of an existing installation where the location is dry and provision of an earthing connection is not possible, or in the event that a protective earth wire becomes broken).

RCDs of high sensitivity (≤ 30 mA) will afford both fault protection (against indirect contact hazards), and the additional protection against the dangers of contact with live parts (direct contact).

Fig. F17 – Unearthed exposed conductive parts (A)

ru:Защита от поражения электрическим током zh:电击防护

Share