Chapter G

Sizing and protection of conductors


Short-circuit current: Difference between revisions

From Electrical Installation Guide
Home > Sizing and protection of conductors > Short-circuit current
(removed empty lines at the beginning of wiki pages)
m (1 revision imported: Migrated pages - Remove empty lines begin pages)

Revision as of 17:34, 20 December 2019

Knowing the levels of 3-phase symmetrical short-circuit currents (Isc) at different points in an installation is an essential feature of its design

A knowledge of 3-phase symmetrical short-circuit current values (Isc) at strategic points of an installation is necessary in order to determine switchgear (breaking capacity), cables (thermal withstand rating), protective devices (selective trip settings) and so on...

In the following notes a 3-phase short-circuit of zero impedance (the so-called bolted short-circuit) fed through a typical MV/LV distribution transformer will be examined. Except in very unusual circumstances, this type of fault is the most severe, and is certainly the simplest to calculate.

Short-circuit currents occurring in a network supplied from a generator and also in DC systems are dealt with in Chapter Characteristics of particular sources and loads.

The simplified calculations and practical rules which follow give conservative results of sufficient accuracy, in the large majority of cases, for installation design purposes.

ru:Ток короткого замыкания zh:短路电流

Share