EMC behaviour of different electrical distribution architecturing: Difference between revisions

From Electrical Installation Guide
Home > ElectroMagnetic Compatibility (EMC) > EMC behaviour of different electrical distribution architecturing
(removed empty lines at the beginning of wiki pages)
m (1 revision imported: Migrated pages - Remove empty lines begin pages)

Revision as of 17:36, 20 December 2019

The system earthing arrangement must be properly selected to ensure the safety of life and property. The behaviour of the different systems with respect to EMC considerations must be taken into account. Figure R1 below presents a summary of their main characteristics.

European standards (see EN 50174-2, EN 50310 and HD 60364-4-444) recommend the TN-S eathing system which causes the fewest EMC problems for installations comprising information-technology equipment (including telecom equipment).

Fig. R1 – Main characteristics of the different earthing sytems
TT TN-S IT TN-C
Safety of persons Correct

Use of residual current devices (circuit breaker)is mandatory

Correct

Continuity of the PE conductor must be ensured throughout the installation

Safety of property Correct Poor Correct Poor
Medium ground-fault current (< about ten amps) High ground-fault current (about 1 kA) Low ground-fault current for first fault (< about ten mA), but high for second fault High ground-fault current (about 1 kA)
Availability of energy Correct Correct Excellent Correct
EMC performance Correct
  • Risk of overvoltages
  • Equipotential problems
  • Need to manage devices with high leakage currents
Excellent
  • Good equipotential situation
  • Need to manage devices with high leakage currents
  • High ground- currents (transient disturbances)
Poor (to be avoided)
  • Risk of overvoltages
  • Common-mode filters and surge arrestors must handle the phase- to-phase voltages
  • RCDs subject to nuisance tripping if common-mode capacitors are present
  • Equivalent to TN system for second fault
Poor (not recommended)
  • Neutral and PE are combined
  • 50/60 Hz and harmonics currents circulate in the earthing and grounding structures
  • High ground-fault currents (transient disturbances)

When an installation includes high-power equipment (motors, air-conditioning, lifts, power electronics, etc.), it is advised to install one or more transformers specifically for these systems. Electrical distribution must be organised in a star system and all outgoing circuits must exit the main low-voltage switchboard (MLVS).

Electronic systems (control/monitoring, regulation, measurement instruments, etc.) must be supplied by a dedicated transformer in a TN-S system.

Figure R2 below illustrates these recommendations.

Fig. R2 – Recommendations of separated distributions

ru:ЭМС для различных схем распределения электроэнергии zh:不同配电系统结构的电磁兼容性能

Share