Protection of LV/LV transformers: Difference between revisions

From Electrical Installation Guide
Home > Characteristics of particular sources and loads > Protection of LV/LV transformers
m (1 revision imported: Migrated pages - removed CN links)
(group the content of all section subpages into one page)
Line 11: Line 11:
'''Note''': In the particular cases of LV/LV safety isolating transformers at extra-low voltage, an earthed metal screen between the primary and secondary windings is frequently required, according to circumstances, as recommended in European Standard EN 60742.
'''Note''': In the particular cases of LV/LV safety isolating transformers at extra-low voltage, an earthed metal screen between the primary and secondary windings is frequently required, according to circumstances, as recommended in European Standard EN 60742.


{{Section-TOC}}
==Transformer-energizing inrush current==


[[ru:Защита трансформаторов низкого/низкого напряжения]]
At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see {{FigRef|N33}}).
 
{{FigImage|DB422663_EN|svg|N33|Transformer-energizing inrush current}}
 
The magnitude of the current peak depends on:
*The value of voltage at the instant of energization
*The magnitude and polarity of the residual flux existing in the core of the transformer
*Characteristics of the load connected to the transformer
 
The first current peak can reach a value equal to 10 to 15 times the full-load r.m.s. current, but for small transformers (< 50 kVA) may reach values of 20 to 25 times the nominal full-load current. This transient current decreases rapidly, with a time constant θ of the order of several ms to severals tens of ms.
 
==Protection for the supply circuit of a LV/LV transformer==
 
The protective device on the supply circuit for a LV/LV transformer must avoid the possibility of incorrect operation due to the magnetizing inrush current surge, noted above.It is necessary to use therefore:
*Selective (i.e. slighly time-delayed) circuit-breakers of the type Compact NSX with electronic trip-unit (see {{FigRef|N34}}) or
 
{{FigImage|DB422664_EN|svg|N34|Tripping characteristic of a Compact NSX with electronic trip-unit}}
 
*Circuit-breakers having a very high magnetic-trip setting, of the types Compact NSX or Acti 9 curve D (see {{FigRef|N35}})
 
{{FigImage|DB422665_EN|svg|N35|Tripping characteristic of a Acti 9 curve D}}
 
=== Example ===
A 400 V 3-phase circuit is supplying a 125 kVA 400/230 V transformer (In = 180 A) for which the first inrush current peak can reach 12 In, i.e. 12 x 180 = 2,160 A.
 
This current peak corresponds to a rms value of 1,530 A.
 
A compact NSX250N circuit-breaker with Ir setting of 200 A and Im setting at 8 x Ir would therefore be a suitable protective device.
 
=== A particular case: Overload protection installed at the secondary side of the transformer ===
(see {{FigRef|N36}})
 
{{FigImage|DB422666_EN|svg|N36|Example}}
 
An advantage of overload protection located on the secondary side is that the short-circuit protection on the primary side can be set at a high value, or alternatively a circuit-breaker type MA (magnetic only) can be used. The primary side short-circuit protection setting must, however, be sufficiently sensitive to ensure its operation in the event of a short-circuit occuring on the secondary side of the transformer.
 
'''Note''': The primary protection is sometimes provided by fuses, type aM. This practice has two disadvantages:
*The fuses must be largely oversized (at least 4 times the nominal full-load rated current of the transformer)
*In order to provide isolating facilities on the primary side, either a load-break switch or a contactor must be associated with the fuses.
 
==Typical electrical characteristics of LV/LV 50 Hz transformers==
 
{{tb-start|id=Tab1366a|num=|title=|cols=4}}
{| class="wikitable"
|-
! colspan="24" | 3-phase (&le; 80A)
|-
| style= "width: 110px;" | kVA rating||  5 || 6.3 || 8 || 10 || 12.5 || 16 || 20 || 25 || 31.5 || 40 || 50 || 63 || 80
|-
| No-load losses (W) || 100 || 110 || 130 || 150 || 160 || 170 || 270 || 310 || 350 || 350 || 410 || 460 || 520
|-
| Full-load losses (W) || 250 || 320 || 390 || 500 || 600 || 840 || 800 || 1180 || 1240 || 1530 || 1650 || 2150 || 2540
|-
| Short-circuit voltage (%) || 4.5 || 4.5 || 4.5 || 5.5 || 5.5 || 5.5 || 5.5 || 5.5 || 5 || 5 || 4.5 || 5 || 5
|}
 
 
{{tb-start|id=Tab1366b|num=|title=|cols=4}}
{| class="wikitable"
|-
! colspan="24" | 3-phase (&ge; 100A)
|-
| style= "width: 110px;" | kVA rating|| 100 || 125 || 160 || 200 || 250 || 315 || 400 || 500 || 630 || 800
|-
| No-load losses (W) || 570 || 680 || 680 || 790 || 950 || 1160 || 1240 || 1485 || 1855 || 2160
|-
| Full-load losses (W) || 3700 || 3700 || 5900 || 5900 || 6500 || 7400 || 9300 || 9400 || 11400 || 13400
|-
| Short-circuit voltage (%) || 5.5 || 4.5 || 5.5 || 5 || 5 || 4.5 || 6 || 6 || 5.5 || 5.5
|}
 
 
{{tb-start|id=Tab1367|num=|title=|cols=4}}
{| class="wikitable"
|-
! colspan="15" | 1-phase
|-
| style= "width: 110px;" | kVA rating
| 8
| 10
| 12.5
| 16
| 20
| 25
| 31.5
| 40
| 50
| 63
| 80
| 100
| 125
| 160
|-
| No-load losses (W)
| 105
| 115
| 120
| 140
| 150
| 175
| 200
| 215
| 265
| 305
| 450
| 450
| 525
| 635
|-
| Full-load losses (W)
| 400
| 530
| 635
| 730
| 865
| 1065
| 1200
| 1400
| 1900
| 2000
| 2450
| 3950
| 3950
| 4335
|-
| Short-circuit voltage (%)
| 5
| 5
| 5
| 4.5
| 4.5
| 4.5
| 4
| 4
| 5
| 5
| 4.5
| 5.5
| 5
| 5
|}
 
==Protection of LV/LV transformers, using Schneider Electric circuit-breakers==
 
For up-to-date tables to choose the appropriate circuit breaker for protection of LV/LV transformers, refer to the latest [https://www.se.com/ww/en/download/document/LVPED318033EN/ Complementary Technical Information - Selectivity, Cascading and Coordination Guide].

Revision as of 16:43, 29 October 2021

These transformers are generally in the range of several hundreds of VA to some hundreds of kVA and are frequently used for:

  • Changing the low voltage level for:
    • Auxiliary supplies to control and indication circuits
    • Lighting circuits (230 V created when the primary system is 400 V 3-phase 3-wires)
  • Changing the method of earthing for certain loads having a relatively high capacitive current to earth (computer equipment) or resistive leakage current (electric ovens, industrial-heating processes, mass-cooking installations, etc.)

LV/LV transformers are generally supplied with protective systems incorporated, and the manufacturers must be consulted for details. Overcurrent protection must, in any case, be provided on the primary side. The exploitation of these transformers requires a knowledge of their particular function, together with a number of points described below.

Note: In the particular cases of LV/LV safety isolating transformers at extra-low voltage, an earthed metal screen between the primary and secondary windings is frequently required, according to circumstances, as recommended in European Standard EN 60742.

Transformer-energizing inrush current

At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see Fig. N33).

Fig. N33 – Transformer-energizing inrush current

The magnitude of the current peak depends on:

  • The value of voltage at the instant of energization
  • The magnitude and polarity of the residual flux existing in the core of the transformer
  • Characteristics of the load connected to the transformer

The first current peak can reach a value equal to 10 to 15 times the full-load r.m.s. current, but for small transformers (< 50 kVA) may reach values of 20 to 25 times the nominal full-load current. This transient current decreases rapidly, with a time constant θ of the order of several ms to severals tens of ms.

Protection for the supply circuit of a LV/LV transformer

The protective device on the supply circuit for a LV/LV transformer must avoid the possibility of incorrect operation due to the magnetizing inrush current surge, noted above.It is necessary to use therefore:

  • Selective (i.e. slighly time-delayed) circuit-breakers of the type Compact NSX with electronic trip-unit (see Fig. N34) or
Fig. N34 – Tripping characteristic of a Compact NSX with electronic trip-unit
  • Circuit-breakers having a very high magnetic-trip setting, of the types Compact NSX or Acti 9 curve D (see Fig. N35)
Fig. N35 – Tripping characteristic of a Acti 9 curve D

Example

A 400 V 3-phase circuit is supplying a 125 kVA 400/230 V transformer (In = 180 A) for which the first inrush current peak can reach 12 In, i.e. 12 x 180 = 2,160 A.

This current peak corresponds to a rms value of 1,530 A.

A compact NSX250N circuit-breaker with Ir setting of 200 A and Im setting at 8 x Ir would therefore be a suitable protective device.

A particular case: Overload protection installed at the secondary side of the transformer

(see Fig. N36)

Fig. N36 – Example

An advantage of overload protection located on the secondary side is that the short-circuit protection on the primary side can be set at a high value, or alternatively a circuit-breaker type MA (magnetic only) can be used. The primary side short-circuit protection setting must, however, be sufficiently sensitive to ensure its operation in the event of a short-circuit occuring on the secondary side of the transformer.

Note: The primary protection is sometimes provided by fuses, type aM. This practice has two disadvantages:

  • The fuses must be largely oversized (at least 4 times the nominal full-load rated current of the transformer)
  • In order to provide isolating facilities on the primary side, either a load-break switch or a contactor must be associated with the fuses.

Typical electrical characteristics of LV/LV 50 Hz transformers

3-phase (≤ 80A)
kVA rating 5 6.3 8 10 12.5 16 20 25 31.5 40 50 63 80
No-load losses (W) 100 110 130 150 160 170 270 310 350 350 410 460 520
Full-load losses (W) 250 320 390 500 600 840 800 1180 1240 1530 1650 2150 2540
Short-circuit voltage (%) 4.5 4.5 4.5 5.5 5.5 5.5 5.5 5.5 5 5 4.5 5 5


3-phase (≥ 100A)
kVA rating 100 125 160 200 250 315 400 500 630 800
No-load losses (W) 570 680 680 790 950 1160 1240 1485 1855 2160
Full-load losses (W) 3700 3700 5900 5900 6500 7400 9300 9400 11400 13400
Short-circuit voltage (%) 5.5 4.5 5.5 5 5 4.5 6 6 5.5 5.5


1-phase
kVA rating 8 10 12.5 16 20 25 31.5 40 50 63 80 100 125 160
No-load losses (W) 105 115 120 140 150 175 200 215 265 305 450 450 525 635
Full-load losses (W) 400 530 635 730 865 1065 1200 1400 1900 2000 2450 3950 3950 4335
Short-circuit voltage (%) 5 5 5 4.5 4.5 4.5 4 4 5 5 4.5 5.5 5 5

Protection of LV/LV transformers, using Schneider Electric circuit-breakers

For up-to-date tables to choose the appropriate circuit breaker for protection of LV/LV transformers, refer to the latest Complementary Technical Information - Selectivity, Cascading and Coordination Guide.

Share