Worked example of cable calculation: Difference between revisions
No edit summary |
|||
Line 24: | Line 24: | ||
|- | |- | ||
| valign="top" align="left" bgcolor="#66cc33" colspan="2" | '''General network characteristics ''' | | valign="top" align="left" bgcolor="#66cc33" colspan="2" | '''General network characteristics ''' | ||
| | |||
| | | | ||
| valign="top" align="left" | Number of poles and protected poles | | valign="top" align="left" | Number of poles and protected poles | ||
Line 29: | Line 30: | ||
|- | |- | ||
| Earthing system | | Earthing system | ||
| | |||
| TN-S | | TN-S | ||
| | | | ||
Line 35: | Line 37: | ||
|- | |- | ||
| Neutral distributed | | Neutral distributed | ||
| | |||
| No | | No | ||
| | | | ||
Line 41: | Line 44: | ||
|- | |- | ||
| Voltage (V) | | Voltage (V) | ||
| | |||
| 400 | | 400 | ||
| | | | ||
Line 47: | Line 51: | ||
|- | |- | ||
| Frequency (Hz) | | Frequency (Hz) | ||
| | |||
| 50 | | 50 | ||
| | | | ||
Line 52: | Line 57: | ||
|- | |- | ||
| Upstream fault level (MVA) | | Upstream fault level (MVA) | ||
| | |||
| 500 | | 500 | ||
| | | | ||
Line 58: | Line 64: | ||
|- | |- | ||
| Resistance of MV network (mΩ) | | Resistance of MV network (mΩ) | ||
| | |||
| 0.0351 | | 0.0351 | ||
| | | | ||
Line 64: | Line 71: | ||
|- | |- | ||
| Reactance of MV network (mΩ) | | Reactance of MV network (mΩ) | ||
| | |||
| 0.351 | | 0.351 | ||
| | | | ||
Line 70: | Line 78: | ||
|- | |- | ||
| valign="top" align="left" bgcolor="#66cc33" colspan="2" | '''Transformer T1''' | | valign="top" align="left" bgcolor="#66cc33" colspan="2" | '''Transformer T1''' | ||
| | |||
| | | | ||
| Ambient temperature (°C) | | Ambient temperature (°C) | ||
Line 75: | Line 84: | ||
|- | |- | ||
| Rating (kVA) | | Rating (kVA) | ||
| | |||
| 630 | | 630 | ||
| | | | ||
Line 81: | Line 91: | ||
|- | |- | ||
| Short-circuit impedance voltage (%) | | Short-circuit impedance voltage (%) | ||
| | |||
| 4 | | 4 | ||
| | | | ||
Line 87: | Line 98: | ||
|- | |- | ||
| Transformer resistance RT (mΩ) | | Transformer resistance RT (mΩ) | ||
| | |||
| 3.472 | | 3.472 | ||
| | | | ||
Line 93: | Line 105: | ||
|- | |- | ||
| Transformer reactance XT (mΩ) | | Transformer reactance XT (mΩ) | ||
| | |||
| 10.64 | | 10.64 | ||
| | | | ||
Line 99: | Line 112: | ||
|- | |- | ||
| 3-phase short-circuit current Ik3 (kA) | | 3-phase short-circuit current Ik3 (kA) | ||
| | |||
| 21.54 | | 21.54 | ||
| | | | ||
Line 105: | Line 119: | ||
|- | |- | ||
| valign="top" align="left" bgcolor="#66cc33" colspan="2" | '''Cable C1''' | | valign="top" align="left" bgcolor="#66cc33" colspan="2" | '''Cable C1''' | ||
| | |||
| | | | ||
| PE conductor selected csa (mm2) | | PE conductor selected csa (mm2) | ||
Line 110: | Line 125: | ||
|- | |- | ||
| Length (m) | | Length (m) | ||
| | |||
| 5 | | 5 | ||
| | | | ||
Line 116: | Line 132: | ||
|- | |- | ||
| Maximum load current (A) | | Maximum load current (A) | ||
| | |||
| 860<br> | | 860<br> | ||
| | | | ||
Line 122: | Line 139: | ||
|- | |- | ||
| Type of insulation | | Type of insulation | ||
| | |||
| PVC | | PVC | ||
| | | | ||
Line 128: | Line 146: | ||
|- | |- | ||
| Ambient temperature (°C) | | Ambient temperature (°C) | ||
| | |||
| 30 | | 30 | ||
| | | | ||
Line 134: | Line 153: | ||
|- | |- | ||
| Conductor material | | Conductor material | ||
| | |||
| Copper | | Copper | ||
| | | | ||
Line 139: | Line 159: | ||
|- | |- | ||
| Single-core or multi-core cable | | Single-core or multi-core cable | ||
| | |||
| Single | | Single | ||
| | | | ||
Line 145: | Line 166: | ||
|- | |- | ||
| Installation method | | Installation method | ||
| | |||
| F | | F | ||
| | | | ||
Line 151: | Line 173: | ||
|- | |- | ||
| Number of layers | | Number of layers | ||
| | |||
| 1 | | 1 | ||
| | | | ||
Line 156: | Line 179: | ||
|- | |- | ||
| Phase conductor selected csa (mm2) | | Phase conductor selected csa (mm2) | ||
| | |||
| 2 x 240 | | 2 x 240 | ||
| | | | ||
Line 162: | Line 186: | ||
|- | |- | ||
| Neutral conductor selected csa (mm2) | | Neutral conductor selected csa (mm2) | ||
| | |||
| 2 x 240 | | 2 x 240 | ||
| | | | ||
Line 168: | Line 193: | ||
|- | |- | ||
| PE conductor selected csa (mm2) | | PE conductor selected csa (mm2) | ||
| | |||
| 1 x 120 | | 1 x 120 | ||
| | | | ||
Line 174: | Line 200: | ||
|- | |- | ||
| Voltage drop ΔU (%) | | Voltage drop ΔU (%) | ||
| | |||
| 0.122 | | 0.122 | ||
| | | | ||
Line 180: | Line 207: | ||
|- | |- | ||
| 3-phase short-circuit current Ik3 (kA) | | 3-phase short-circuit current Ik3 (kA) | ||
| | |||
| 21.5 | | 21.5 | ||
| | | | ||
Line 186: | Line 214: | ||
|- | |- | ||
| Courant de défaut phase-terre Id (kA) | | Courant de défaut phase-terre Id (kA) | ||
| | |||
| 15.9 | | 15.9 | ||
| | | | ||
Line 192: | Line 221: | ||
|- | |- | ||
| valign="top" align="left" bgcolor="#66cc33" colspan="2" | '''Circuit-breaker Q1''' | | valign="top" align="left" bgcolor="#66cc33" colspan="2" | '''Circuit-breaker Q1''' | ||
| | |||
| | | | ||
| Overload trip Ir (A) | | Overload trip Ir (A) | ||
Line 197: | Line 227: | ||
|- | |- | ||
| Load current (A) | | Load current (A) | ||
| | |||
| 860 | | 860 | ||
| | | | ||
Line 203: | Line 234: | ||
|- | |- | ||
| Type | | Type | ||
| | |||
| Compact | | Compact | ||
| | | | ||
Line 208: | Line 240: | ||
|- | |- | ||
| Reference | | Reference | ||
| | |||
| NS1000N | | NS1000N | ||
| | | | ||
Line 214: | Line 247: | ||
|- | |- | ||
| Rated current (A) | | Rated current (A) | ||
| | |||
| 1000 | | 1000 | ||
| | | | ||
Line 220: | Line 254: | ||
|- | |- | ||
| Number of poles and protected poles | | Number of poles and protected poles | ||
| | |||
| 4P4d | | 4P4d | ||
| | | | ||
Line 226: | Line 261: | ||
|- | |- | ||
| Tripping unit | | Tripping unit | ||
| | |||
| Micrologic 5.0 | | Micrologic 5.0 | ||
| | | | ||
Line 232: | Line 268: | ||
|- | |- | ||
| Overload trip Ir (A) | | Overload trip Ir (A) | ||
| | |||
| 900 | | 900 | ||
| | | | ||
Line 238: | Line 275: | ||
|- | |- | ||
| Short-delay trip Im / Isd (A) | | Short-delay trip Im / Isd (A) | ||
| | |||
| 9000 | | 9000 | ||
| | | | ||
Line 244: | Line 282: | ||
|- | |- | ||
| Tripping time tm (ms) | | Tripping time tm (ms) | ||
| | |||
| 50 | | 50 | ||
| | | | ||
Line 250: | Line 289: | ||
|- | |- | ||
| valign="top" align="left" bgcolor="#66cc33" colspan="2" | '''Switchboard B2''' | | valign="top" align="left" bgcolor="#66cc33" colspan="2" | '''Switchboard B2''' | ||
| | |||
| | | | ||
| Phase conductor selected csa (mm2) | | Phase conductor selected csa (mm2) | ||
Line 255: | Line 295: | ||
|- | |- | ||
| Reference | | Reference | ||
| | |||
| Linergy 1250 | | Linergy 1250 | ||
| | | | ||
Line 261: | Line 302: | ||
|- | |- | ||
| Rated current (A) | | Rated current (A) | ||
| | |||
| 1050 | | 1050 | ||
| | | | ||
Line 267: | Line 309: | ||
|- | |- | ||
| valign="top" align="left" bgcolor="#66cc33" colspan="2" | '''Circuit breaker Q3''' | | valign="top" align="left" bgcolor="#66cc33" colspan="2" | '''Circuit breaker Q3''' | ||
| | |||
| | | | ||
| Cable voltage drop ΔU (%) | | Cable voltage drop ΔU (%) | ||
Line 272: | Line 315: | ||
|- | |- | ||
| Load current (A) | | Load current (A) | ||
| | |||
| 509 | | 509 | ||
| | | | ||
Line 278: | Line 322: | ||
|- | |- | ||
| Type | | Type | ||
| | |||
| Compact | | Compact | ||
| | | | ||
Line 284: | Line 329: | ||
|- | |- | ||
| Reference | | Reference | ||
| | |||
| NSX630F | | NSX630F | ||
| | | | ||
Line 290: | Line 336: | ||
|- | |- | ||
| Rated current (A) | | Rated current (A) | ||
| | |||
| 630 | | 630 | ||
| | | |
Revision as of 05:47, 28 January 2010
Worked example of cable calculation
(see Fig. G65)
The installation is supplied through a 630 kVA transformer. The process requires a high degree of supply continuity and part of the installation can be supplied by a 250 kVA standby generator. The global earthing system is TN-S, except for the most critical loads supplied by an isolation transformer with a downstream IT configuration.
The single-line diagram is shown in Figure G65 below. The results of a computer study for the circuit from transformer T1 down to the cable C7 is reproduced on Figure G66. This study was carried out with Ecodial 3.4 software (a Schneider Electric product).
This is followed by the same calculations carried out by the simplified method described in this guide.
Fig. G65:Example of single-line diagram
Calculation using software Ecodial 3.3
General network characteristics | Number of poles and protected poles | 4P4d | |||
Earthing system | TN-S | Tripping unit | Micrologic 2.3 | ||
Neutral distributed | No | Overload trip Ir (A) | 510 | ||
Voltage (V) | 400 | Short-delay trip Im / Isd (A) | 5100 | ||
Frequency (Hz) | 50 | Cable C3 | |||
Upstream fault level (MVA) | 500 | Length | 20 | ||
Resistance of MV network (mΩ) | 0.0351 | Maximum load current (A) | 509 | ||
Reactance of MV network (mΩ) | 0.351 | Type of insulation | PVC | ||
Transformer T1 | Ambient temperature (°C) | 30 | |||
Rating (kVA) | 630 | Conductor material | Copper | ||
Short-circuit impedance voltage (%) | 4 | Single-core or multi-core cable | Single | ||
Transformer resistance RT (mΩ) | 3.472 | Installation method | F | ||
Transformer reactance XT (mΩ) | 10.64 | Phase conductor selected csa (mm2) | 2 x 95 | ||
3-phase short-circuit current Ik3 (kA) | 21.54 | Neutral conductor selected csa (mm2) | 2 x 95 | ||
Cable C1 | PE conductor selected csa (mm2) | 1 x 95 | |||
Length (m) | 5 | Cable voltage drop ΔU (%) | 0.53 | ||
Maximum load current (A) | 860 |
Total voltage drop ΔU (%) | 0.65 | ||
Type of insulation | PVC | 3-phase short-circuit current Ik3 (kA) | 19.1 | ||
Ambient temperature (°C) | 30 | 1-phase-to-earth fault current Id (kA) | 11.5 | ||
Conductor material | Copper | Switchboard B6 | |||
Single-core or multi-core cable | Single | Reference | Linergy 800 | ||
Installation method | F | Rated current (A) | 750 | ||
Number of layers | 1 | Circuit-breaker Q7 | |||
Phase conductor selected csa (mm2) | 2 x 240 | Load current (A) | 255 | ||
Neutral conductor selected csa (mm2) | 2 x 240 | Type | Compact | ||
PE conductor selected csa (mm2) | 1 x 120 | Reference | NSX400F | ||
Voltage drop ΔU (%) | 0.122 | Rated current (A) | 400 | ||
3-phase short-circuit current Ik3 (kA) | 21.5 | Number of poles and protected poles | 3P3d | ||
Courant de défaut phase-terre Id (kA) | 15.9 | Tripping unit | Micrologic 2.3 | ||
Circuit-breaker Q1 | Overload trip Ir (A) | 258 | |||
Load current (A) | 860 | Short-delay trip Im / Isd (A) | 2576 | ||
Type | Compact | Cable C7 | |||
Reference | NS1000N | Length | 5 | ||
Rated current (A) | 1000 | Maximum load current (A) | 255 | ||
Number of poles and protected poles | 4P4d | Type of insulation | PVC | ||
Tripping unit | Micrologic 5.0 | Ambient temperature (°C) | 30 | ||
Overload trip Ir (A) | 900 | Conductor material | Copper | ||
Short-delay trip Im / Isd (A) | 9000 | Single-core or multi-core cable | Single | ||
Tripping time tm (ms) | 50 | Installation method | F | ||
Switchboard B2 | Phase conductor selected csa (mm2) | 1 x 95 | |||
Reference | Linergy 1250 | Neutral conductor selected csa (mm2) | - | ||
Rated current (A) | 1050 | PE conductor selected csa (mm2) | 1 x 50 | ||
Circuit breaker Q3 | Cable voltage drop ΔU (%) | 0.14 | |||
Load current (A) | 509 | Total voltage drop ΔU (%) | 0.79 | ||
Type | Compact | 3-phase short-circuit current Ik3 (kA) | 18.0 | ||
Reference | NSX630F | 1-phase-to-earth fault current Id (kA) | 10.0 | ||
Rated current (A) | 630 |
Fig. G66:Partial results of calculation carried out with Ecodial 3.4 software (Schneider Electric)
The same calculation using the simplified method recommended in this guide
- Dimensioning circuit C1
The MV/LV 630 kVA transformer has a rated no-load voltage of 420 V. Circuit C1 must be suitable for a current of:
Two single-core PVC-insulated copper cables in parallel will be used for each phase.These cables will be laid on cable trays according to method F.
Each conductor will therefore carry 433A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 240mm².
The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 5 metres, are:
(cable resistance: 22.5 mΩ.mm2/m)
X = 0,08 x 5 = 0,4 mΩ (cable reactance: 0.08 mΩ/m)
- Dimensioning circuit C3
Circuit C3 supplies two 150kW loads with cos φ = 0.85, so the total load current is:
Two single-core PVC-insulated copper cables in parallel will be used for each phase. These cables will be laid on cable trays according to method F.
Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm².
The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 20 metres, are:
- Dimensioning circuit C7
Circuit C7 supplies one 150kW load with cos φ = 0.85, so the total load current is:
One single-core PVC-insulated copper cable will be used for each phase. The cables will be laid on cable trays according to method F.
Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm².
The resistance and the inductive reactance for a length of 20 metres is:
(cable resistance: 22.5 mΩ.mm2/m)
(cable reactance: 0.08 mΩ/m)
- Calculation of short-circuit currents for the selection of circuit-breakers Q1, Q3, Q7 (seeFig. G67)
Fig. G67:Example of short-circuit current evaluation
- The protective conductor
When using the adiabatic method, the minimum c.s.a. for the protective earth conductor (PE) can be calculated by the formula given in Figure G58:
For circuit C1, I = 20.2kA and k = 143.
t is the maximum operating time of the MV protection, e.g. 0.5s
This gives:
A single 120 mm2 conductor is therefore largely sufficient, provided that it also satisfies the requirements for indirect contact protection (i.e. that its impedance is sufficiently low).
Generally, for circuits with phase conductor c.s.a. Sph ≥ 50 mm2, the PE conductor minimum c.s.a. will be Sph / 2. Then, for circuit C3, the PE conductor will be 95mm2, and for circuit C7, the PE conductor will be 50mm2.
- Protection against indirect-contact hazards
For circuit C3 of Figure G65, Figures F41 andF40, or the formula given page F25 may be used for a 3-phase 4-wire circuit.
The maximum permitted length of the circuit is given by:
(The value in the denominator 630 x 11 is the maximum current level at which the instantaneous short-circuit magnetic trip of the 630 A circuit-breaker operates).
The length of 20 metres is therefore fully protected by “instantaneous” over-current devices.
- Voltage drop
The voltage drop is calculated using the data given inFigure G28, for balanced three-phase circuits, motor power normal service (cos φ = 0.8).
The results are summarized on figure G68:
Fig. G68:Voltage drop introduced by the different cables
The total voltage drop at the end of cable C7 is then: 0.77%.