Talk:Definition of standardised earthing schemes/Archive 1: Difference between revisions

From Electrical Installation Guide
(→‎IEC60343-5-54 PEN: new section)
No edit summary
Line 18: Line 18:
So TNC can not be used for portable equipment, and when used for fixed installation PEN shall have S>=10mm2 If active conductors' size is lower, it's usually cheaper to go to TNS.
So TNC can not be used for portable equipment, and when used for fixed installation PEN shall have S>=10mm2 If active conductors' size is lower, it's usually cheaper to go to TNS.
--[[User:Mathieu GUILLOT|Mathieu GUILLOT]] 08:42, 30 April 2010 (UTC)
--[[User:Mathieu GUILLOT|Mathieu GUILLOT]] 08:42, 30 April 2010 (UTC)
In that case sentence related to TN-S system should be:
The TN-S system (5 wires) is obligatory for circuits with cross-sectional areas less than 10 mm2 '''OR''' for portable equipment.

Revision as of 09:20, 30 April 2010

Is the following sentence related to TN-C system  correct with or without "OR"?

This system is not permitted for conductors of less than 10 mm2 OR for portable equipment.

IEC60343-5-54 PEN

To be precise, the IEC60364 states:

411.4.3 In fixed installations, a single conductor may serve both as a protective conductor and as a neutral conductor (PEN conductor) provided that the requirements of 543.4 of IEC 60364-5-54 are satisfied. No switching or isolating device shall be inserted in the PEN conductor.

543.4.1 A PEN conductor may only be used in fixed electrical installations and, for mechanical reasons, shall have a cross-sectional area not less than 10 mm2 in copper or 16 mm² in aluminium.

So TNC can not be used for portable equipment, and when used for fixed installation PEN shall have S>=10mm2 If active conductors' size is lower, it's usually cheaper to go to TNS. --Mathieu GUILLOT 08:42, 30 April 2010 (UTC)

In that case sentence related to TN-S system should be: The TN-S system (5 wires) is obligatory for circuits with cross-sectional areas less than 10 mm2 OR for portable equipment.