Motor starter configurations: Difference between revisions
No edit summary |
(Improved format) |
||
Line 6: | Line 6: | ||
---- | ---- | ||
<br>[[Image:FigN66.jpg| | <br>[[Image:FigN66.jpg|none|700px|]] | ||
'''''Fig. N66:''' The various functions and their combinations forming a motor starter'' | '''''Fig. N66:''' The various functions and their combinations forming a motor starter'' | ||
---- | ---- | ||
The different applicable standards are listed on '''Figure N67.''' | |||
{| | {| cellspacing="1" cellpadding="1" width="65%" border="1" | ||
|- | |- | ||
| bgcolor="#0099cc" | '''Standard''' | | bgcolor="#0099cc" | '''Standard''' | ||
Line 43: | Line 41: | ||
---- | ---- | ||
Different utilization categories have been defined for contactors in IEC 60947-4-1. The selection relative to asynchronous motor control is given in '''Figure N68'''. | |||
{| | {| cellspacing="1" cellpadding="1" width="65%" border="1" | ||
|- | |- | ||
| bgcolor="#0099cc" | '''Category''' | | bgcolor="#0099cc" | '''Category''' | ||
Line 67: | Line 63: | ||
|} | |} | ||
1) By plugging is understood stopping or reversing the motor rapidly by reversing motor primary connections while the motor is running.<br>2) By inching (jogging) is understood energizing a motor once or repeatedly for short periods to obtain small movements of the driven mechanism | (1) By plugging is understood stopping or reversing the motor rapidly by reversing motor primary connections while the motor is running.<br> | ||
(2) By inching (jogging) is understood energizing a motor once or repeatedly for short periods to obtain small movements of the driven mechanism | |||
'''''Fig. N68:''' Different categories of AC contactors used for asynchronous motor control'' |
Revision as of 14:29, 9 February 2012
Different configurations of switchgear and control-gear are commonly proposed. Some examples are shown on Figure N66.
Fig. N66: The various functions and their combinations forming a motor starter
The different applicable standards are listed on Figure N67.
Standard | Title |
IEC 60947-1 | Low-voltage switchgear and controlgear – General rules |
IEC 60947-4-1 | Contactors and motor-starters –Electromechanical contactors and motor-starters |
IEC 60947-4-2 | Contactors and motor-starters – AC semiconductor motor controllers and starters |
IEC 60947-6-2 | Multiple function equipment – Control and protective switching devices (or equipment) (CPS) |
IEC 61800 | Adjustable speed electrical power drive systems |
Fig. N67: Applicable standards
Different utilization categories have been defined for contactors in IEC 60947-4-1. The selection relative to asynchronous motor control is given in Figure N68.
Category | Typical applications |
AC-1 | Non-inductive or slightly inductive loads, resistance furnaces |
AC-2 | Slip-ring motors: starting, switching off |
AC-3 | Squirrel-cage motors: starting, switching off motors during running |
AC-4 | Squirrel-cage motors: starting, plugging(1), inching(2) |
(1) By plugging is understood stopping or reversing the motor rapidly by reversing motor primary connections while the motor is running.
(2) By inching (jogging) is understood energizing a motor once or repeatedly for short periods to obtain small movements of the driven mechanism
Fig. N68: Different categories of AC contactors used for asynchronous motor control