EMC implementation - Raised floors: Difference between revisions

From Electrical Installation Guide
Home > ElectroMagnetic Compatibility (EMC) > EMC implementation > EMC implementation - Raised floors
(Created page with '{{Menu_EMC_guidelines}} __TOC__ The inclusion of the floors in the mesh contributes to equipotentiality of the area and consequently to the distribution and dilution of disturbi…')
 
Line 9: Line 9:


----
----
[[ru:Конструктивное исполнение ЭМС - фальшполы]]

Revision as of 14:26, 14 September 2012

The inclusion of the floors in the mesh contributes to equipotentiality of the area and consequently to the distribution and dilution of disturbing LF currents.
The screening effect of a false floor is directly related to its equipotentiality. If the contact between the floor plates is poor (rubber antistatic joints, for example) or if the contact between the support brackets is faulty (pollution, corrosion, mildew, etc. or if there are no support brackets), it is necessary to add an equipotential mesh. In this case, it is sufficient to ensure effective electrical connections between the metal support columns. Small spring clips are available on the market to connect the metal columns to the equipotential mesh. Ideally, each column should be connected, but it is often sufficient to connect every other column in each direction. A mesh 1.5 to 2 metres is size is suitable in most cases. The recommended cross-sectional area of the copper is 10 mm2 or more. In general, a flat braid is used. To reduce the effects of corrosion, it is advised to use tin-plated copper (see Fig. R8).
Perforated floor plates act like normal floor plates when they have a cellular steel structure.
Preventive maintenance is required for the floor plates approximately every five years (depending on the type of floor plate and the environment, including humidity, dust and corrosion). Rubber or polymer antistatic joints must be maintained, similar to the bearing surfaces of the floor plates (cleaning with a suitable product).



Fig R08.jpg




















Fig. R8: False floor implementation


ru:Конструктивное исполнение ЭМС - фальшполы

Share