Transformer-energizing inrush current: Difference between revisions
m (r2.7.2) (robot Adding: ru:Ток намагничивания трансформатора при включении) |
m (r2.7.2) (robot Adding: zh:变压器励磁涌流) |
||
Line 21: | Line 21: | ||
[[ru:Ток намагничивания трансформатора при включении]] | [[ru:Ток намагничивания трансформатора при включении]] | ||
[[zh:变压器励磁涌流]] |
Revision as of 11:30, 28 January 2013
At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see Fig. N31).
Fig N31: Transformer-energizing inrush current
The magnitude of the current peak depends on:
- The value of voltage at the instant of energization
- The magnitude and polarity of the residual flux existing in the core of the transformer
- Characteristics of the load connected to the transformer
The first current peak can reach a value equal to 10 to 15 times the full-load r.m.s. current, but for small transformers (< 50 kVA) may reach values of 20 to 25 times the nominal full-load current. This transient current decreases rapidly, with a time constant θ of the order of several ms to severals tens of ms.
ru:Ток намагничивания трансформатора при включении zh:变压器励磁涌流