{{Menu_Protection_against_electric_shocks}} | {{Menu_Protection_against_electric_shocks}} | ||
__TOC__ | |||
Residual current devices (RCD) are commonly incorporated in or associated with the following components: | Residual current devices (RCD) are commonly incorporated in or associated with the following components: | ||
Line 12: | Line 12: | ||
RCDs are mandatorily used at the origin of TT-earthed installations, where their ability to discriminate with other RCDs allows selective tripping, thereby ensuring the level of service continuity required. | RCDs are mandatorily used at the origin of TT-earthed installations, where their ability to discriminate with other RCDs allows selective tripping, thereby ensuring the level of service continuity required. | ||
== Industrial type circuit-breakers with integrated or adaptable RCD module == | |||
(see '''Fig. F64''') | (see '''Fig. F64''') | ||
{| style="width: | {| style="width: 680px; height: 12px" cellspacing="1" cellpadding="1" border="1" | ||
|- | |- | ||
| bgcolor="#0099cc" | Industrial circuit-breakers with an integrated RCD are covered in IEC 60947-2 and its appendix B | | bgcolor="#0099cc" | Industrial circuit-breakers with an integrated RCD are covered in IEC 60947-2 and its appendix B | ||
|} | |} | ||
<br>[[Image:FigF64a_2013.jpg]][[Image:FigF64b_2013.jpg]][[Image:FigF64c_2013.jpg|162x183px]] | |||
Industrial type circuit- Acti 9 DIN-rail industrial <br>breaker Vigi Compact Circuit-breaker with adaptable Vigi RCD module <br><br>'''''Fig. F64:''' Industrial-type CB with RCD module'' | |||
Adaptable residual current circuit-breakers, including DIN-rail mounted units (e.g. Compact or Acti 9), are available, to which may be associated an auxiliary RCD module (e.g. Vigi). <br>The ensemble provides a comprehensive range of protective functions (isolation, protection against short-circuit, overload, and earth-fault. | Adaptable residual current circuit-breakers, including DIN-rail mounted units (e.g. Compact or Acti 9), are available, to which may be associated an auxiliary RCD module (e.g. Vigi). <br>The ensemble provides a comprehensive range of protective functions (isolation, protection against short-circuit, overload, and earth-fault. | ||
== Household and similar miniature circuit-breakers with RCD == | |||
(see '''Fig. F65''') | (see '''Fig. F65''') | ||
{| style="width: | {| style="width: 680px; height: 17px" cellspacing="1" cellpadding="1" border="1" | ||
|- | |- | ||
| bgcolor="#0099cc" | Household or domestic circuit-breakers with an integrated RCD are covered in IEC 60898, IEC 61008 and IEC 61009 | | bgcolor="#0099cc" | Household or domestic circuit-breakers with an integrated RCD are covered in IEC 60898, IEC 61008 and IEC 61009 | ||
|} | |} | ||
[[Image:FigF65a_2013.jpg|116x291px]] [[Image:FigF65b_2013.jpg|171x287px]] | |||
The incoming-supply “Monobloc” Déclic Vigi residual<br>circuit-breaker can current circuit-breakers intended <br>also have time-delayed for protection of terminal socket-outlet<br>characteristics and circuits in domestic and tertiary <br>integrate a RCD sector applications.<br>(type S). | |||
'''''Fig. F65:''' Domestic residual current circuit-breakers (RCCBs) for earth leakage protection'' | '''''Fig. F65:''' Domestic residual current circuit-breakers (RCCBs) for earth leakage protection'' | ||
== Residual current circuit-breakers and RCDs with separate toroidal current transformer == | |||
(see '''Fig. F66''') | (see '''Fig. F66''') | ||
{| style="width: | {| style="width: 680px; height: 19px" cellspacing="1" cellpadding="1" border="1" | ||
|- | |- | ||
| bgcolor="#0099cc" | Residual current load break switches are covered by particular national standards.RCDs with separate toroidal current transformers are standardized in IEC 60947-2 appendix M | | bgcolor="#0099cc" | Residual current load break switches are covered by particular national standards.RCDs with separate toroidal current transformers are standardized in IEC 60947-2 appendix M | ||
Line 57: | Line 57: | ||
RCDs with separate toroidal CTs can be used in association with circuit-breakers or contactors. | RCDs with separate toroidal CTs can be used in association with circuit-breakers or contactors. | ||
[[Image:FigF66a_2013.jpg]][[Image:FigF66b_2013.jpg]] | |||
'''''Fig. F66:''' RCDs with separate toroidal current transformers (Vigirex)'' | |||
[[ru:Типы УЗО]] | [[ru:Типы УЗО]] | ||
[[zh:RCDs简述]] | [[zh:RCDs简述]] |
Revision as of 11:38, 13 August 2013
Residual current devices (RCD) are commonly incorporated in or associated with the following components:
- Industrial-type moulded-case circuit-breakers (MCCB) and air circuit-breakers (ACB) conforming to IEC 60947-2 and its appendix B and M
- Industrial type miniature circuit-breakers (MCB) conforming to IEC 60947-2 and its appendix B and M
- Household and similar miniature circuit-breakers (MCB) complying with IEC 60898, IEC 61008, IEC 61009
- Residual load switch conforming to particular national standards
- Relays with separate toroidal (ring-type) current transformers, conforming to IEC 60947-2 Appendix M
RCDs are mandatorily used at the origin of TT-earthed installations, where their ability to discriminate with other RCDs allows selective tripping, thereby ensuring the level of service continuity required.
Industrial type circuit-breakers with integrated or adaptable RCD module
(see Fig. F64)
Industrial circuit-breakers with an integrated RCD are covered in IEC 60947-2 and its appendix B |
Industrial type circuit- Acti 9 DIN-rail industrial
breaker Vigi Compact Circuit-breaker with adaptable Vigi RCD module
Fig. F64: Industrial-type CB with RCD module
Adaptable residual current circuit-breakers, including DIN-rail mounted units (e.g. Compact or Acti 9), are available, to which may be associated an auxiliary RCD module (e.g. Vigi).
The ensemble provides a comprehensive range of protective functions (isolation, protection against short-circuit, overload, and earth-fault.
Household and similar miniature circuit-breakers with RCD
(see Fig. F65)
Household or domestic circuit-breakers with an integrated RCD are covered in IEC 60898, IEC 61008 and IEC 61009 |
The incoming-supply “Monobloc” Déclic Vigi residual
circuit-breaker can current circuit-breakers intended
also have time-delayed for protection of terminal socket-outlet
characteristics and circuits in domestic and tertiary
integrate a RCD sector applications.
(type S).
Fig. F65: Domestic residual current circuit-breakers (RCCBs) for earth leakage protection
Residual current circuit-breakers and RCDs with separate toroidal current transformer
(see Fig. F66)
Residual current load break switches are covered by particular national standards.RCDs with separate toroidal current transformers are standardized in IEC 60947-2 appendix M |
RCDs with separate toroidal CTs can be used in association with circuit-breakers or contactors.
Fig. F66: RCDs with separate toroidal current transformers (Vigirex)