Chapter G

Sizing and protection of conductors


The neutral conductor: Difference between revisions

From Electrical Installation Guide
Home > Sizing and protection of conductors > The neutral conductor
m (r2.7.2) (robot Adding: zh:中性线)
m (cleaned up source: table format, etc ...)
Line 13: Line 13:




{| cellpadding="1" style="border: 1px solid #8888aa; background: #f7f8ff; padding: 5px; "
{{Manual_TOC |
|
'''Contents:'''
* [[Sizing the neutral conductor|Sizing the neutral conductor]]
* [[Sizing the neutral conductor|Sizing the neutral conductor]]
* [[Protection of the neutral conductor|Protection of the neutral conductor]]
* [[Protection of the neutral conductor|Protection of the neutral conductor]]
* [[Breaking of the neutral conductor|Breaking of the neutral conductor]]
* [[Breaking of the neutral conductor|Breaking of the neutral conductor]]
* [[Isolation of the neutral conductor|Isolation of the neutral conductor]]
* [[Isolation of the neutral conductor|Isolation of the neutral conductor]]
|}
}}


[[ru:Нейтральный провод]]
[[ru:Нейтральный провод]]
[[zh:中性线]]
[[zh:中性线]]

Revision as of 13:10, 15 November 2013


The c.s.a. and the protection of the neutral conductor, apart from its current-carrying requirement, depend on several factors, namely:

  • The type of earthing system, TT, TN, etc.
  • The harmonic currents
  • The method of protection against indirect contact hazards according to the methods described below

   The color of the neutral conductor is statutorily blue. PEN conductor, when insulated, shall be marked by one of the following 
   methods:

  • Green-and-yellow throughout its length with, in addition, light blue markings at the terminations, or
  • Light blue throughout its length with, in addition, green-and-yellow markings at the terminations