The prefabricated outdoor MV/LV substations (see '''Fig. B55)''' comply with IEC 62271-202 standard.
The prefabricated outdoor MV/LV substations (see '''Fig. B55)''' comply with IEC 62271-202 standard.
* A type tested prefabricated outdoor substation is subjected to tests and verifications dedicated to:
* A type tested prefabricated outdoor substation is subjected to tests and verifications dedicated to:
** The degree of protection
** Degree of protection
** The temperature class
** Temperature class
** The non-flammable materials
** Non-flammable materials
** The mechanical resistance of the enclosure
** Mechanical resistance of the enclosure
** The sound level
** Sound level
** The insulation level
** Insulation level
** The internal arc withstand
** Internal arc withstand
** The earthing circuit
** Earthing circuit
** The retention of oil
** Retention of oil
** The operation of the substation.
** Operation of the substation.


=== Main benefits:===
=== Main benefits:===


The prefabricated substations provide a particularly interesting and optimized solution regarding:
The prefabricated substations provide a particularly interesting and optimized solution regarding:
 
* Delivery time
* The delivery time
* Construction works
* The construction works
* Erection works
* The erection works
* Commissioning
* The commissioning
* Total cost.
* The total cost.




[[File:Fig_B55_2015.jpg|none]]
[[File:Fig_B55_2015.jpg|none]]
'''''Fig. B55:''''' ''Type tested substation according to IEC 62271-202''
'''''Fig. B55:''''' ''Type tested substation according to IEC 62271-202''


IEC 62271-202 standard defines requirements for two types of outdoor prefabricated substations (see '''Fig. B56):'''


IEC 62271-202 standard defines requirements for two types of outdoor prefabricated substations (see '''Fig. B56''':)
* Walk-in type substation
* Walk-in type substation
* Non walk-in type substation.
* Non walk-in type substation.


[[File:Fig_B56_2015.jpg|none]]
[[File:Fig_B56_2015.jpg|none]]
'''''Fig. B56:''''' ''Walk in and non-walk in type substations''


'''''Fig. B56:''''' ''Walk in and non-walk in type substations''


The substations may be situated at ground level, half buried or completely buried (underground substation), resulting in three types of design (see '''Fig. B57''' and '''Fig. B58''').
The substations may be situated at ground level, half buried or completely buried (underground substation), resulting in three types of design (see '''Fig. B57''' and '''Fig. B58''').


[[File:Fig_B57_2015.jpg|none]]
[[File:Fig_B57_2015.jpg|none]]
'''''Fig. B57:''''' ''Outdoor substations. The three types of design''




'''''Fig. B57:''''' ''Outdoor substations. The three type of design''
{{Gallery|B36b|Two examples of outdoor substations|195px|
|PB116704.jpg|a|Ground level walk-in type
|PB116705.jpg|b|Half buried non walk-in type
}}


[[File:Fig_B58_2015.jpg|none]]
'''''Fig. B58:''''' ''Outdoor substations '''[a]''' Ground level walk in type substation; '''[b]''' Half buried non walk in type substation''


== Outdoor substation without enclosure ==
== Outdoor substation without enclosure ==
 
(see '''Fig. B59''')
(see '''Fig. B59)'''


This kind of outdoor substations based on weatherproof equipment is commonly used in countries such as UK and India for example.
This kind of outdoor substations based on weatherproof equipment is commonly used in countries such as UK and India for example.
Line 75: Line 66:
The transformer and the LV panel can be installed in dedicated outdoor type housing.
The transformer and the LV panel can be installed in dedicated outdoor type housing.


 
[[File:PB116706.jpg|none]]
[[File:Fig_B59_2015.jpg|none|350px]]
 
 
'''''Fig. B59:''''' ''Outdoor substation without enclosure''
'''''Fig. B59:''''' ''Outdoor substation without enclosure''


Line 99: Line 87:


The location of the substation must allow easy access of the personnel and handling equipment.
The location of the substation must allow easy access of the personnel and handling equipment.


[[File:Fig_B60_2015.jpg|none|400px]]
[[File:Fig_B60_2015.jpg|none|400px]]
'''''Fig. B60:''''' ''Pole mounted MV/LV substation''
'''''Fig. B60:''''' ''Pole mounted MV/LV substation''


[[ru:Подстанция наружной установки]]
[[ru:Подстанция наружной установки]]
[[zh:户外型变电站]]
[[zh:户外型变电站]]

Revision as of 15:48, 28 July 2016


Outdoor substations with prefabricated enclosures

The prefabricated outdoor MV/LV substations (see Fig. B55) comply with IEC 62271-202 standard.

  • A type tested prefabricated outdoor substation is subjected to tests and verifications dedicated to:
    • Degree of protection
    • Temperature class
    • Non-flammable materials
    • Mechanical resistance of the enclosure
    • Sound level
    • Insulation level
    • Internal arc withstand
    • Earthing circuit
    • Retention of oil
    • Operation of the substation.

Main benefits:

The prefabricated substations provide a particularly interesting and optimized solution regarding:

  • Delivery time
  • Construction works
  • Erection works
  • Commissioning
  • Total cost.


Fig B55 2015.jpg

Fig. B55: Type tested substation according to IEC 62271-202


IEC 62271-202 standard defines requirements for two types of outdoor prefabricated substations (see Fig. B56:)

  • Walk-in type substation
  • Non walk-in type substation.
Fig B56 2015.jpg

Fig. B56: Walk in and non-walk in type substations


The substations may be situated at ground level, half buried or completely buried (underground substation), resulting in three types of design (see Fig. B57 and Fig. B58).

Fig B57 2015.jpg

Fig. B57: Outdoor substations. The three types of design



Outdoor substation without enclosure

(see Fig. B59)

This kind of outdoor substations based on weatherproof equipment is commonly used in countries such as UK and India for example.

These substations are generally included in MV rings and include:

  • Two functional units dedicated to the connection of the substation to the ring
  • One functional unit for the supply and the protection of the MV/LV power transformer generally done by a circuit breaker unit
  • One single MV/LV Power transformer
  • One LV distribution panel.

The transformer and the LV panel can be installed in dedicated outdoor type housing.

PB116706.jpg

Fig. B59: Outdoor substation without enclosure

Pole mounted substation

Application

These substations are mainly used for the supply of isolated rural consumers from MV overhead lines.

Constitution

This type of substation includes (see Fig. B60):

  • A single pole mounted MV/LV power transformer that is, according to the local rules associated or not with:
    • A load break switch
    • A set of three fuses
    • A set of three surge arrestors
  • A low voltage circuit breaker
  • An earthing electrode realized at the bottom of the pole supporting the equipment.

The location of the substation must allow easy access of the personnel and handling equipment.

Fig B60 2015.jpg

Fig. B60: Pole mounted MV/LV substation