Breaking of the neutral conductor: Difference between revisions
m (1 revision: no page modification, previous revision = imported ch.G pages cleaned-up) |
CleanUp2016 (talk | contribs) (Cleanup_2016) |
||
Line 1: | Line 1: | ||
{{Menu_Sizing_and_protection_of_conductors}} | {{Menu_Sizing_and_protection_of_conductors}} | ||
[[File: | [[File:DB422335.svg]] | ||
(see {{FigRef|G64}}) | |||
The need to break or not the neutral conductor is related to the protection against indirect contact. | |||
== In TN-C scheme == | |||
The neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor. | |||
== In TT, TN-S and IT schemes{{fn|1}} == | |||
In the event of a fault, the circuit-breaker will open all poles, including the neutral pole, i.e. the circuit-breaker is omnipolar. | |||
The action can only be achieved with fuses in an indirect way, in which the operation of one or more fuses triggers a mechanical trip-out of all poles of an associated series-connected load-break switch. | |||
{{footnotes}} | |||
<references> | |||
{{fn-detail|1|In some coutries the rules applied for TN-S are the same than the rules for TN-C}} | |||
</references> | |||
[[ru:Отключение нейтрального провода]] | [[ru:Отключение нейтрального провода]] | ||
[[zh:中性线的分断]] | [[zh:中性线的分断]] |
Revision as of 00:19, 29 November 2016
(see Fig. G64)
The need to break or not the neutral conductor is related to the protection against indirect contact.
In TN-C scheme
The neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor.
In TT, TN-S and IT schemes[1]
In the event of a fault, the circuit-breaker will open all poles, including the neutral pole, i.e. the circuit-breaker is omnipolar.
The action can only be achieved with fuses in an indirect way, in which the operation of one or more fuses triggers a mechanical trip-out of all poles of an associated series-connected load-break switch.
Notes
- ^ In some coutries the rules applied for TN-S are the same than the rules for TN-C