Combined switchgear elements: Difference between revisions
CleanUp2016 (talk | contribs) (Cleanup_2016) |
CleanUp2016 (talk | contribs) (Cleanup_2016_while rechecking) |
||
Line 16: | Line 16: | ||
*The type in which a non-automatic switch is associated with a set of fuses in a common enclosure. | *The type in which a non-automatic switch is associated with a set of fuses in a common enclosure. | ||
:In some countries, and in IEC 60947-3, the terms “switch-fuse” and “fuse-switch” have specific meanings, viz: | |||
In some countries, and in IEC 60947-3, the terms “switch-fuse” and “fuse-switch” have specific meanings, viz: | :* A switch-fuse comprises a switch (generally 2 breaks per pole) on the upstream side of three fixed fuse-bases, into which the fuse carriers are inserted (see {{FigRef|H18}}) | ||
* A switch-fuse comprises a switch (generally 2 breaks per pole) on the upstream side of three fixed fuse-bases, into which the fuse carriers are inserted (see {{FigRef|H18}}) | |||
{{FigImage|DB422400|svg|H18|Symbol for a non-automatic fuse-switch}} | {{FigImage|DB422400|svg|H18|Symbol for a non-automatic fuse-switch}} | ||
* A fuse-switch consists of three switch blades each constituting a double-break per phase. | :* A fuse-switch consists of three switch blades each constituting a double-break per phase. | ||
: These blades are not continuous throughout their length, but each has a gap in the centre which is bridged by the fuse cartridge. Some designs have only a single break per phase, as shown in {{FigureRef|H19}}. | :: These blades are not continuous throughout their length, but each has a gap in the centre which is bridged by the fuse cartridge. Some designs have only a single break per phase, as shown in {{FigureRef|H19}}. | ||
{{Gallery|H19|Symbol for a non-automatic switch-fuse|170px| | {{Gallery|H19|Symbol for a non-automatic switch-fuse|170px| |
Revision as of 06:06, 3 December 2016
Single units of switchgear do not, in general, fulfil all the requirements of the three basic functions, viz: Protection, control and isolation.
Where the installation of a circuit-breaker is not appropriate (notably where the switching rate is high, over extended periods) combinations of units specifically designed for such a performance are employed. The most commonly-used combinations are described below.
Switch and fuse combinations
Two cases are distinguished:
- The type in which the operation of one (or more) fuse(s) causes the switch to open.
- This is achieved by the use of fuses fitted with striker pins, and a system of switch tripping springs and toggle mechanisms (see Fig. H17)
- The type in which a non-automatic switch is associated with a set of fuses in a common enclosure.
- In some countries, and in IEC 60947-3, the terms “switch-fuse” and “fuse-switch” have specific meanings, viz:
- A switch-fuse comprises a switch (generally 2 breaks per pole) on the upstream side of three fixed fuse-bases, into which the fuse carriers are inserted (see Fig. H18)
- A fuse-switch consists of three switch blades each constituting a double-break per phase.
- These blades are not continuous throughout their length, but each has a gap in the centre which is bridged by the fuse cartridge. Some designs have only a single break per phase, as shown in Figure H19.
The current range for these devices is limited to 100 A maximum at 400 V 3-phase, while their principal use is in domestic and similar installations. To avoid confusion between the first group (i.e. automatic tripping) and the second group, the term “switch-fuse” should be qualified by the adjectives “automatic” or “non-automatic”.
Fuse - disconnector + discontactor
Fuse - switch-disconnector + discontactor
As previously mentioned, a discontactor does not provide protection against short-circuit faults. It is necessary, therefore, to add fuses (generally of type aM) to perform this function. The combination is used mainly for motor control circuits, where the disconnector or switch-disconnector allows safe operations such as:
- The changing of fuse links (with the circuit isolated)
- Work on the circuit downstream of the discontactor (risk of remote closure of the discontactor)
The fuse-disconnector must be interlocked with the discontactor such that no opening or closing manœuvre of the fuse disconnector is possible unless the discontactor is open (Figure H20), since the fuse disconnector has no load-switching capability.
A fuse-switch-disconnector (evidently) requires no interlocking (Figure H21).
The switch must be of class AC22 or AC23 if the circuit supplies a motor.
Circuit-breaker + contactor
Circuit-breaker + discontactor
These combinations are used in remotely controlled distribution systems in which the rate of switching is high, or for control and protection of a circuit supplying motors.