Transformer-energizing inrush current: Difference between revisions
m (1 revision) |
*>CleanUpAuto (clean-up 2016 - imported revision step 20) |
||
Line 3: | Line 3: | ||
__TOC__ | __TOC__ | ||
At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see | At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see {{FigRef|N31}}). | ||
[[File:FigN31.jpg|none]] | [[File:FigN31.jpg|none]] | ||
'''''Fig N31:''' Transformer-energizing inrush current'' | '''''Fig N31:''' Transformer-energizing inrush current'' | ||
The magnitude of the current peak depends on: | The magnitude of the current peak depends on: |
Revision as of 08:53, 8 December 2016
At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see Fig. N31).
Fig N31: Transformer-energizing inrush current
The magnitude of the current peak depends on:
- The value of voltage at the instant of energization
- The magnitude and polarity of the residual flux existing in the core of the transformer
- Characteristics of the load connected to the transformer
The first current peak can reach a value equal to 10 to 15 times the full-load r.m.s. current, but for small transformers (< 50 kVA) may reach values of 20 to 25 times the nominal full-load current. This transient current decreases rapidly, with a time constant θ of the order of several ms to severals tens of ms.
ru:Ток намагничивания трансформатора при включении zh:变压器励磁涌流