Different kinds of motor control solution are compared in the following tables.
Is / In | Ts / Tn | Speed control | Torque control | |
---|---|---|---|---|
Direct on line | 5-10 | 5-10 | No | No |
Star – Delta | 2-3 | 1-2 | No | No |
Auto-transformer | 2-3 | 1-2 | No | No |
Soft starter | 3-5 | 1.5-2.5 | No | Yes |
Variable speed drive | 1.5 | 1.5-2 | Yes | Yes |
pros | cons | |
---|---|---|
Direct on line |
Reduced cost, high starting torque |
High in-rush current |
Star – Delta | Reduced in-rush current | Reduced starting torque |
Auto-transformer | Reduced in-rush current | High weight |
Soft starter |
Reduced in-rush current, controlled start and stop |
Reduced starting torque |
Variable speed drive |
Controlled speed, Energy saving at reduced speed |
Higher cost |