Line 4: Line 4:


The level of disturbance depends on the voltage variations (dv/dt) and the value of the coupling capacitance between the disturber and the victim.<br>Capacitive coupling increases with:
The level of disturbance depends on the voltage variations (dv/dt) and the value of the coupling capacitance between the disturber and the victim.<br>Capacitive coupling increases with:
*The frequency
*The frequency
*The proximity of the disturber to the victim and the length of the parallel cables
*The proximity of the disturber to the victim and the length of the parallel cables
Line 11: Line 10:
*The insulation of the victim cable (εr of the cable insulation), particularly for tightly coupled pairs
*The insulation of the victim cable (εr of the cable insulation), particularly for tightly coupled pairs


'''Figure R35 '''shows the results of capacitive coupling (cross-talk) between two cables.
{{FigureRef|R35}} shows the results of capacitive coupling (cross-talk) between two cables.


----
[[File:Fig_R25.jpg|none]]
[[File:Fig_R25.jpg|none]]
'''''Fig. R35: '''Typical result of capacitive coupling (capacitive cross-talk)''
'''''Fig. R35: '''Typical result of capacitive coupling (capacitive cross-talk)''
----


== Examples  ==
== Examples  ==


(see '''Fig. R36''')  
(see {{FigRef|R36}})  


*Nearby cables subjected to rapid voltage variations (dv/dt)  
*Nearby cables subjected to rapid voltage variations (dv/dt)  
Line 27: Line 24:
*Coupling capacitance between the primary and secondary windings of transformers  
*Coupling capacitance between the primary and secondary windings of transformers  
*Cross-talk between cables
*Cross-talk between cables
----


[[File:Fig R26.jpg|none]]
[[File:Fig R26.jpg|none]]
'''''Fig. R36:''' Example of capacitive coupling''  
'''''Fig. R36:''' Example of capacitive coupling''
 
----


== Counter-measures  ==
== Counter-measures  ==


(see '''Fig. R37''')
(see {{FigRef|R37}})


*Limit the length of parallel runs of disturbers and victims to the strict minimum
*Limit the length of parallel runs of disturbers and victims to the strict minimum
Line 48: Line 41:
*Reduce the dv/dt of the disturber by increasing the signal rise time where possible
*Reduce the dv/dt of the disturber by increasing the signal rise time where possible


----
[[File:Fig_R27.jpg|none]]
[[File:Fig_R27.jpg|none]]
'''''Fig. R37:''' Cable shielding with perforations reduces capacitive coupling''
'''''Fig. R37:''' Cable shielding with perforations reduces capacitive coupling''
----


[[ru:Емкостная связь]]
[[ru:Емкостная связь]]
[[zh:电容耦合]]
[[zh:电容耦合]]

Revision as of 17:50, 13 December 2016

Definition

The level of disturbance depends on the voltage variations (dv/dt) and the value of the coupling capacitance between the disturber and the victim.
Capacitive coupling increases with:

  • The frequency
  • The proximity of the disturber to the victim and the length of the parallel cables
  • The height of the cables with respect to a ground referencing plane
  • The input impedance of the victim circuit (circuits with a high input impedance are more vulnerable)
  • The insulation of the victim cable (εr of the cable insulation), particularly for tightly coupled pairs

Figure R35 shows the results of capacitive coupling (cross-talk) between two cables.

Fig R25.jpg

Fig. R35: Typical result of capacitive coupling (capacitive cross-talk)

Examples

(see Fig. R36)

  • Nearby cables subjected to rapid voltage variations (dv/dt)
  • Start-up of fluorescent lamps
  • High-voltage switch-mode power supplies (photocopy machines, etc.)
  • Coupling capacitance between the primary and secondary windings of transformers
  • Cross-talk between cables
Fig R26.jpg

Fig. R36: Example of capacitive coupling

Counter-measures

(see Fig. R37)

  • Limit the length of parallel runs of disturbers and victims to the strict minimum
  • Increase the distance between the disturber and the victim
  • For two-wire connections, run the two wires as close together as possible
  • Position a PEC bonded at both ends and between the disturber and the victim
  • Use two or four-wire cables rather than individual conductors
  • Use symmetrical transmission systems on correctly implemented, symmetrical wiring systems
  • Shield the disturbing cables, the victim cables or both (the shielding must be bonded)
  • Reduce the dv/dt of the disturber by increasing the signal rise time where possible
Fig R27.jpg

Fig. R37: Cable shielding with perforations reduces capacitive coupling