EMC behaviour of different electrical distribution architecturing: Difference between revisions

From Electrical Installation Guide
Home > ElectroMagnetic Compatibility (EMC) > EMC behaviour of different electrical distribution architecturing
m (1 revision: no page modification, previous revision = imported ch.R pages cleaned-up)
(Cleanup_2016)
Line 4: Line 4:


European standards (see EN 50174-2, EN 50310 and HD 60364-4-444) recommend the TN-S eathing system which causes the fewest EMC problems for installations comprising information-technology equipment (including telecom equipment).
European standards (see EN 50174-2, EN 50310 and HD 60364-4-444) recommend the TN-S eathing system which causes the fewest EMC problems for installations comprising information-technology equipment (including telecom equipment).
{| class="wikitable"
 
{{TableStart|Tab1440|5col}}
|-
|-
!  
!  
Line 13: Line 14:
|-
|-
| Safety of persons  
| Safety of persons  
| Correct <br> Use of residual current devices (circuit breaker)is mandatory
| Correct  
| colspan="3" | Correct <br>Continuity of the PE conductor must be ensured throughout the installation
Use of residual current devices (circuit breaker)is mandatory
| colspan="3" | Correct
Continuity of the PE conductor must be ensured throughout the installation
|-
|-
| Safety of property
| Safety of property
Line 26: Line 29:
| High ground-fault current (about 1 kA)  
| High ground-fault current (about 1 kA)  
| Low ground-fault current for first fault (< about ten mA), but high for second fault
| Low ground-fault current for first fault (< about ten mA), but high for second fault
| High ground-fault current <br> (about 1 kA)
| High ground-fault current (about 1 kA)
|-
|-
| Availability of energy  
| Availability of energy  
Line 35: Line 38:
|-
|-
| EMC performance
| EMC performance
| Correct <br>
| Correct
- Risk of overvoltages<br>
* Risk of overvoltages
- Equipotential problems<br>
* Equipotential problems
- Need to manage devices with high leakage currents
* Need to manage devices with high leakage currents
| Excellent <br>
| Excellent  
- Good equipotential situation<br>
* Good equipotential situation
- Need to manage devices with high leakage currents<br>
* Need to manage devices with high leakage currents
- High ground- currents (transient disturbances)<br>
* High ground- currents (transient disturbances)  
| Poor (to be avoided)<br>
| Poor (to be avoided)
- Risk of overvoltages<br>
* Risk of overvoltages
- Common-mode filters and surge arrestors must handle the phase- to-phase voltages<br>
* Common-mode filters and surge arrestors must handle the phase- to-phase voltages
- RCDs subject to nuisance tripping if common-mode capacitors are present<br>
* RCDs subject to nuisance tripping if common-mode capacitors are present
- Equivalent to TN system for second fault<br>
* Equivalent to TN system for second fault
| Poor (not recommended)<br>
| Poor (not recommended)
- Neutral and PE are combined<br>
* Neutral and PE are combined
- 50/60 Hz and harmonics currents circulate in the earthing and grounding structures<br>
* 50/60 Hz and harmonics currents circulate in the earthing and grounding structures
- High ground-fault currents (transient disturbances)
* High ground-fault currents (transient disturbances)
|}
|-
 
{{TableEnd|Tab1440|R1|Main characteristics of the different earthing sytems}}
'''''Fig. R1:''''' ''Main characteristics of the different earthing sytems''


When an installation includes high-power equipment (motors, air-conditioning, lifts, power electronics, etc.), it is advised to install one or more transformers specifically for these systems. Electrical distribution must be organised in a star system and all outgoing circuits must exit the main low-voltage switchboard (MLVS).<br>Electronic systems (control/monitoring, regulation, measurement instruments, etc.) must be supplied by a dedicated transformer in a TN-S system.<br>{{FigureRef|R2}} below illustrates these recommendations.
When an installation includes high-power equipment (motors, air-conditioning, lifts, power electronics, etc.), it is advised to install one or more transformers specifically for these systems. Electrical distribution must be organised in a star system and all outgoing circuits must exit the main low-voltage switchboard (MLVS).


[[File:Fig R02.jpg|none]]
Electronic systems (control/monitoring, regulation, measurement instruments, etc.) must be supplied by a dedicated transformer in a TN-S system.
'''''Fig. R2:''' Recommendations of separated distributions''


{{FigureRef|R2}} below illustrates these recommendations.


{{FigImage|DB422765_EN|svg|R2|Recommendations of separated distributions}}


[[ru:ЭМС для различных схем распределения электроэнергии]]
[[ru:ЭМС для различных схем распределения электроэнергии]]
[[zh:不同配电系统结构的电磁兼容性能]]
[[zh:不同配电系统结构的电磁兼容性能]]

Revision as of 23:21, 13 December 2016


The system earthing arrangement must be properly selected to ensure the safety of life and property. The behaviour of the different systems with respect to EMC considerations must be taken into account. Figure R1 below presents a summary of their main characteristics.

European standards (see EN 50174-2, EN 50310 and HD 60364-4-444) recommend the TN-S eathing system which causes the fewest EMC problems for installations comprising information-technology equipment (including telecom equipment).

TT TN-S IT TN-C
Safety of persons Correct

Use of residual current devices (circuit breaker)is mandatory

Correct

Continuity of the PE conductor must be ensured throughout the installation

Safety of property Correct Poor Correct Poor
Medium ground-fault current (< about ten amps) High ground-fault current (about 1 kA) Low ground-fault current for first fault (< about ten mA), but high for second fault High ground-fault current (about 1 kA)
Availability of energy Correct Correct Excellent Correct
EMC performance Correct
  • Risk of overvoltages
  • Equipotential problems
  • Need to manage devices with high leakage currents
Excellent
  • Good equipotential situation
  • Need to manage devices with high leakage currents
  • High ground- currents (transient disturbances)
Poor (to be avoided)
  • Risk of overvoltages
  • Common-mode filters and surge arrestors must handle the phase- to-phase voltages
  • RCDs subject to nuisance tripping if common-mode capacitors are present
  • Equivalent to TN system for second fault
Poor (not recommended)
  • Neutral and PE are combined
  • 50/60 Hz and harmonics currents circulate in the earthing and grounding structures
  • High ground-fault currents (transient disturbances)
Fig. R1 – Main characteristics of the different earthing sytems

When an installation includes high-power equipment (motors, air-conditioning, lifts, power electronics, etc.), it is advised to install one or more transformers specifically for these systems. Electrical distribution must be organised in a star system and all outgoing circuits must exit the main low-voltage switchboard (MLVS).

Electronic systems (control/monitoring, regulation, measurement instruments, etc.) must be supplied by a dedicated transformer in a TN-S system.

Figure R2 below illustrates these recommendations.

Fig. R2 – Recommendations of separated distributions

ru:ЭМС для различных схем распределения электроэнергии zh:不同配电系统结构的电磁兼容性能

Share