Overcurrent protection principles: Difference between revisions
CleanUp2016 (talk | contribs) (Cleanup_2016_as per box points) |
(cleanup 2016) |
||
Line 17: | Line 17: | ||
|S| Cross sectional area of insulated conductor (mm<sup>2</sup>) | |S| Cross sectional area of insulated conductor (mm<sup>2</sup>) | ||
|I| Short-circuit current (A r.m.s.) | |I| Short-circuit current (A r.m.s.) | ||
|k| Insulated conductor constant (values of k | |k| Insulated conductor constant (values of k are given in {{FigureRef|G52}})}} | ||
For a given insulated conductor, the maximum permissible current varies according to the environment. For instance, for a high ambient temperature (θa1 > θa2), Iz1 is less than Iz2 (see {{FigRef|G5}}). θ means “temperature”. | For a given insulated conductor, the maximum permissible current varies according to the environment. For instance, for a high ambient temperature (θa1 > θa2), Iz1 is less than Iz2 (see {{FigRef|G5}}). θ means “temperature”. | ||
'''Note''': | '''Note''': | ||
{{def | |||
|ISC|3-phase short-circuit current | |||
|ISCB|rated 3-ph. short-circuit breaking current of the circuit-breaker | |||
|Ir (or Irth){{fn|1}}|regulated “nominal” current level; e.g. a 50 A nominal circuit-breaker can be regulated to have a protective range, i.e. a conventional overcurrent tripping level (see {{FigRef|G6}}) similar to that of a 30 A circuit-breaker.}} | |||
{{FigImage|DB422282_EN|svg|G3|Circuit protection by circuit breaker}} | {{FigImage|DB422282_EN|svg|G3|Circuit protection by circuit breaker}} |
Revision as of 05:50, 16 May 2017
A protective device is provided at the origin of the circuit concerned (see Fig. G3 and Fig. G4 ).
- Acting to cut-off the current in a time shorter than that given by the I2t characteristic of the circuit cabling
- But allowing the maximum load current IB to flow indefinitely
The characteristics of insulated conductors when carrying short-circuit currents can, for periods up to 5 seconds following short-circuit initiation, be determined approximately by the formula:
- I2t = k2 S2
which shows that the allowable heat generated is proportional to the squared cross-sectional-area of the condutor.
where
t = Duration of short-circuit current (seconds)
S = Cross sectional area of insulated conductor (mm2)
I = Short-circuit current (A r.m.s.)
k = Insulated conductor constant (values of k are given in Figure G52)
For a given insulated conductor, the maximum permissible current varies according to the environment. For instance, for a high ambient temperature (θa1 > θa2), Iz1 is less than Iz2 (see Fig. G5). θ means “temperature”.
Note:
ISC = 3-phase short-circuit current
ISCB = rated 3-ph. short-circuit breaking current of the circuit-breaker
Ir (or Irth)[1] = regulated “nominal” current level; e.g. a 50 A nominal circuit-breaker can be regulated to have a protective range, i.e. a conventional overcurrent tripping level (see Fig. G6) similar to that of a 30 A circuit-breaker.
Notes
- ^ Both designations are commonly used in different standards.