Motor control systems: Difference between revisions
From Electrical Installation Guide
Migrate2019 (talk | contribs) (converted syntax for tables) |
m (1 revision imported: Migrated pages - Tables) |
(No difference)
|
Revision as of 16:37, 20 December 2019
Different kinds of motor control solution are compared in the following tables.
Fig. N75 – Comparison of different motor control solutions
Type | Is/In | Ts/Tn | Speed control | Torque control | Pros | Cons |
---|---|---|---|---|---|---|
Direct on line | 5-10 | 5-10 | No | No | Reduced cost, high starting torque | High in-rush current |
Star – Delta | 2-3 | 1-2 | No | No | Reduced in-rush current | Reduced starting torque |
Auto-transformer | 2-3 | 1-2 | No | No | Reduced in-rush current | High weight |
Soft starter | 3-5 | 1.5-2.5 | No | Yes | Reduced in-rush current, controlled start and stop | Reduced starting torque |
Variable speed drive | 1.5 | 1.5-2 | Yes | Yes | Controlled speed, Energy saving at reduced speed | Higher cost |