Energy saving opportunities-: Difference between revisions

From Electrical Installation Guide
No edit summary
No edit summary
Line 86: Line 86:
{| style="width: 793px; height: 212px" cellspacing="1" cellpadding="1" width="793" border="1"
{| style="width: 793px; height: 212px" cellspacing="1" cellpadding="1" width="793" border="1"
|-
|-
| bgcolor="#0099cc" | '''Technology'''
| bgcolor="#0099cc" | '''Technology'''  
| valign="top" bgcolor="#0099cc" | '''Disadvantage'''
| valign="top" bgcolor="#0099cc" | '''Disadvantage'''
|-
|-
| Control of stopping and starting
| Control of stopping and starting  
| This method is only effective when intermittent flow is acceptable.
| This method is only effective when intermittent flow is acceptable.
|-
|-
| valign="top" | Control valve: a valve is used to control flow by increasing frictional resistance at the pump’s outlet.
| valign="top" | Control valve: a valve is used to control flow by increasing frictional resistance at the pump’s outlet.  
| Energy is wasted, as the flow produced by the pump is subsequently reduced by the action of the valve. In addition, pumps have an optimal operating level and increasing resistance by this method may force the pump to operate at a less efficient level (with additional energy loss) where it may be less reliable.
| Energy is wasted, as the flow produced by the pump is subsequently reduced by the action of the valve. In addition, pumps have an optimal operating level and increasing resistance by this method may force the pump to operate at a less efficient level (with additional energy loss) where it may be less reliable.
|-
|-
| Bypass device: with this method, the pump turns continuously at full speed and excess fluid at the pump’s outlet is channelled upstream, causing flow to be reduced without the risk of outlet pressure increasing.
| Bypass device: with this method, the pump turns continuously at full speed and excess fluid at the pump’s outlet is channelled upstream, causing flow to be reduced without the risk of outlet pressure increasing.  
| valign="top" | The system is very inefficient, as the energy used to pump excess fluid is completely wasted.
| valign="top" | The system is very inefficient, as the energy used to pump excess fluid is completely wasted.
|-
|-
| Multiple pumps or fans: these configurations support ad hoc increases by activating extra pumps or fans, making control difficult.
| Multiple pumps or fans: these configurations support ad hoc increases by activating extra pumps or fans, making control difficult.  
| valign="top" | There is usually a loss in efficiency, as the actual need is often somewhere between the different speeds available.
| valign="top" | There is usually a loss in efficiency, as the actual need is often somewhere between the different speeds available.
|-
|-
| Damper: a similar technology to the control valve in systems with a pump, this reduces flow by partly obstructing the fan’s outlet.
| Damper: a similar technology to the control valve in systems with a pump, this reduces flow by partly obstructing the fan’s outlet.  
| valign="top" | Energy is wasted, as the flow generated by the fan is subsequently reduced by the action of the damper.
| valign="top" | Energy is wasted, as the flow generated by the fan is subsequently reduced by the action of the damper.
|-
|-
Line 107: Line 107:
| valign="top" | The system is very inefficient, as the energy used to propel the air or gas is completely wasted.
| valign="top" | The system is very inefficient, as the energy used to propel the air or gas is completely wasted.
|-
|-
| Fan with adjustable blades: the flow can be changed by adjusting the blades.
| Fan with adjustable blades: the flow can be changed by adjusting the blades.  
| Energy is wasted, as the flow generated by the fan is subsequently reduced by the action of the blades.
| Energy is wasted, as the flow generated by the fan is subsequently reduced by the action of the blades.
|-
|-
| Inlet guide blades: fins are used to obstruct or facilitate gas flow inside a fan, thereby determining its efficiency.
| Inlet guide blades: fins are used to obstruct or facilitate gas flow inside a fan, thereby determining its efficiency.  
| The fan does not generate excess flow, but does not operate at maximum efficiency either.
| The fan does not generate excess flow, but does not operate at maximum efficiency either.
|}
|}


'''''Fig. K11:''' Examples of technologies which may benefit from using a variable speed drive''
'''''Fig. K11:''' Examples of technologies which may benefit from using a variable speed drive''  


----
----


Using a variable speed drive (see Fig. K12), as opposed to the technologies <br>discussed earlier, constitutes an active energy efficiency method and provides the type of variable efficiency required for optimal pump or fan operation.


&nbsp;
----
 
'''''Fig. K12:''' Altivar drives with different power ratings''
 
----
Certain scenarios favour simple solutions:
 
*When changing the dimensions of the pulleys enables fans or pumps to turn at their optimal speed. This solution does not afford the flexibility associated with variable speed drives, but it involves little work and could well be covered by the maintenance budget without the need for any additional investment.
*When the fan or pump can operate at full speed continuously without the control features referred to above being installed, or with these control features installed but unused (e.g. with dampers and valves fully opened). Under this arrangement, the device will operate at or near optimum efficiency.
 
In reality, the potential savings will depend on the model of the fan or pump used, its intrinsic efficiency, the size of the motor, annual operating hours and the cost of electricity locally. These savings can be calculated using special software or can be estimated with some accuracy by installing temporary meters and analysing the data obtained.
 
==== Control ====
 
{| style="width: 792px; height: 18px" cellspacing="1" cellpadding="1" width="792" border="1"
|-
| bgcolor="#0099cc" | Speed regulation: Correctly adjusting energy consumption in line with needs
|}
 
The previous section showed how pumps and fans can benefit from the use of variable speed drives. Still further advantages can be enjoyed by using these in conjunction with control devices tailored to meet individual requirements.
 
*Control based on fixed pressure and variable flow: this type of control is often used for water distribution systems (drinking water, irrigation). It is also used to circulate fluids in cooling applications.
*Control for heating systems: in heating and cooling circuits, flow should vary with temperature.
*Control based on fixed flow and variable pressure: mainly associated with pumping applications (pressure differences caused by different levels) such as cleaning, watering, cooling and freezing installations. These require a certain amount of water, even where suction and discharge conditions vary.
 
The immediate advantages are:
 
*Improved control and greater accuracy in terms of pressure and flow values
*Significant reduction of transient effects within the electrical network and of mechanical restrictions affecting systems
*Reduced noise and vibrations, as drives support fine speed adjustments, thereby preventing equipment from operating at the resonance frequency for ducts and pipes
*Smooth starting and stopping
 
These in turn bring about further advantages:
 
*Greater reliability and extended service lives for systems
*Simpler tubing and pipe systems (by dispensing with dampers, control valves and bypass pipes)
*Reduced maintenance
 
The ultimate goal is to reduce energy consumption and its associated costs.<br><br>&nbsp;

Revision as of 12:01, 2 February 2010

In industrial applications, motors account for 60% of the energy consumed

A number of different measures can be adopted to save energy (see Fig. K7).

  • Reduce energy use

These measures try to achieve the same results by consuming less (e.g. installing highly energy-efficient lights which provide the same quality of light but consume less energy) or reduce energy consumption by taking care to use no more energy than is strictly necessary (e.g. another method would be to have fewer lights in a room which is too brightly lit).

  • Save energy

These measures reduce costs per unit rather than reducing the total amount of energy used. For example, day-time activities could be performed at night to in order to take advantage of cheaper rates. Similarly, work could be scheduled to avoid peak hours and demand response programmes.

  • Energy reliability

As well as contributing to operational efficiency by avoiding lost production, these measures avoid the energy losses associated with frequent restarts and the extra work generated when batches of products go to waste.


Fig. K7: An overall strategy for energy management


Everyone immediately thinks of equipment for transforming energy (motors, lighting/heating devices) when considering areas where savings can be made. Less obvious, perhaps, are the potential savings offered by the various control devices and programmes associated with this type of equipment.

 Motors

Motorised systems are one of the potential areas where energy savings can be made.
Those wishing to improve passive energy efficiency often consider replacing motors as a starting point. There are two reasons for this:

  • To benefit from the advantages offered by new high-performance motors (see. Fig. K8)

Fig. K8: Definition of energy efficiency classes for LV motors established by the European Commission and the European Committee of Manufacturers of Electrical Machines and Power Electronics (CEMEP)


  • To rectify oversizing

Motors operating for long periods are obvious candidates for replacement by high-performance motors, particularly if these existing motors are old and require rewinding.
Depending on the power they generate, high-performance motors can improve operational efficiency by up to 10% compared to standard motors. Where motors have undergone rewinding, efficiency is reduced by 3% to 4% compared to the original motor.
By contrast, replacement with high-performance motors will not prove to be cost effective if the existing standard-efficiency motor – particularly if it has not undergone rewinding – experiences low or moderate levels of use (e.g. less than 30,000 hours per year). It is also important to ensure that the new motor’s critical performance characteristics (such as speed) are equivalent to those of the existing motor.

  • As well as being inefficient, oversized motors are more expensive to buy than correctly sized motors. Motors are at their most effective when operating at between 60% and 100% of their nominal load. Efficiency reduces rapidly at loads below 50%. In the past, designers tended to develop oversized motors in order to provide an adequate safety margin and eliminate the risk of failure, even in conditions which were highly unlikely to occur. Studies show that at least a third of motors are clearly oversized and operate at below 50% of their nominal load. The average load for a motor is around 60%.

Larger motors also tend to have lower power factors, which can lead to charges being levied for reactive power. When deciding whether to replace a motor, it is essential to take these factors, as well as the motor’s remaining life cycle, into consideration. It is also important to remember that the expense of replacing an admittedly oversized motor may not be justified if its load is very small or it is only used infrequently.
All things considered, every parameter needs to be taken into account before making a decision on replacing a motor.
Other approaches are also possible, as far as motors are concerned:

  • Improving active energy efficiency by simply stopping motors when they no longer need to be running. This method may require improvements to be made in terms of automation, training or monitoring, and operator incentives may have to be offered. If an operator is not accountable for energy consumption, he/she may well forget to stop a motor at times when it is not required.
  • Monitoring and correcting all the components within the drive chains, starting with those on the larger motors capable of affecting overall efficiency. This may involve, for example, aligning shafts or couplings as required. An angular offset of 0.6 mm in a coupling can result in a power loss of as much as 8%.
  • Paying special attention to pumps and fans, because:

  - 63% of the energy used by motors is for fluid propulsion in components such as pumps and fans.
  - Flow control often uses valves, dampers and throttles, all of which cause energy to be lost by blocking ducts whilst motors are
    operating at full speed.
  - Effective project planning can often recoup investments in less than ten months.

 Speed variation

Savings can be made by sizing motors correctly and using speed control and/or a variable speed drive

A number of technologies can be used to vary flow or pressure within a system (see Fig. K9). The technology chosen will depend on how the pump and fan have been designed. For example, the pump used may be a displacement or centrifugal pump, and the fan used may be a centrifugal or axial-flow fan.


Fig. K9: Theoretical energy savings based on reducing fan speed by half


Every time a fan or a pump is installed with a view to achieving specific flow or pressure levels, sizing is based on maximum demand. As a result, oversizing is the norm, and the device concerned will not operate efficiently at other speeds. In general, systematic oversizing, combined with the ineffective control methods described above, allows scope for significant energy savings to be made by using control methods aimed at reducing the pump or fan’s supply current during periods of reduced demand.
Systems with fans and pumps are governed by certain correlations:

  • Flow is proportional to shaft speed, e.g. reducing speed by half reduces flow by the same amount (see Fig. K10). 

Fig. K10: Relationship between energy and flow for different methods of fan control (damper, inlet vanes and variable speed)


  • Pressure or head is proportional to the square of the shaft speed; halving the shaft speed reduces pressure by a quarter.
  • Energy is proportional to the cube of the shaft speed.

Halving the shaft speed reduces energy consumption by an eighth and, by implication, halving the flow reduces energy consumption by an eighth.
In light of this, energy consumption can be reduced in cases where the fan or the pump does not have to generate 100% of the flow or pressure. The savings involved are significant, even where the flow is only reduced by a small amount
(see Fig. K11). Unfortunately, the efficiency losses incurred by the various components mean that these theoretical values cannot be achieved in practice.


Technology Disadvantage
Control of stopping and starting This method is only effective when intermittent flow is acceptable.
Control valve: a valve is used to control flow by increasing frictional resistance at the pump’s outlet. Energy is wasted, as the flow produced by the pump is subsequently reduced by the action of the valve. In addition, pumps have an optimal operating level and increasing resistance by this method may force the pump to operate at a less efficient level (with additional energy loss) where it may be less reliable.
Bypass device: with this method, the pump turns continuously at full speed and excess fluid at the pump’s outlet is channelled upstream, causing flow to be reduced without the risk of outlet pressure increasing. The system is very inefficient, as the energy used to pump excess fluid is completely wasted.
Multiple pumps or fans: these configurations support ad hoc increases by activating extra pumps or fans, making control difficult. There is usually a loss in efficiency, as the actual need is often somewhere between the different speeds available.
Damper: a similar technology to the control valve in systems with a pump, this reduces flow by partly obstructing the fan’s outlet. Energy is wasted, as the flow generated by the fan is subsequently reduced by the action of the damper.
Overflow valve: a similar technology to the bypass valve in systems with a pump. The fan rotates at full speed continuously and the excess gas flow is evacuated.
The system is very inefficient, as the energy used to propel the air or gas is completely wasted.
Fan with adjustable blades: the flow can be changed by adjusting the blades. Energy is wasted, as the flow generated by the fan is subsequently reduced by the action of the blades.
Inlet guide blades: fins are used to obstruct or facilitate gas flow inside a fan, thereby determining its efficiency. The fan does not generate excess flow, but does not operate at maximum efficiency either.

Fig. K11: Examples of technologies which may benefit from using a variable speed drive


Using a variable speed drive (see Fig. K12), as opposed to the technologies
discussed earlier, constitutes an active energy efficiency method and provides the type of variable efficiency required for optimal pump or fan operation.


Fig. K12: Altivar drives with different power ratings


Certain scenarios favour simple solutions:

  • When changing the dimensions of the pulleys enables fans or pumps to turn at their optimal speed. This solution does not afford the flexibility associated with variable speed drives, but it involves little work and could well be covered by the maintenance budget without the need for any additional investment.
  • When the fan or pump can operate at full speed continuously without the control features referred to above being installed, or with these control features installed but unused (e.g. with dampers and valves fully opened). Under this arrangement, the device will operate at or near optimum efficiency.

In reality, the potential savings will depend on the model of the fan or pump used, its intrinsic efficiency, the size of the motor, annual operating hours and the cost of electricity locally. These savings can be calculated using special software or can be estimated with some accuracy by installing temporary meters and analysing the data obtained.

Control

Speed regulation: Correctly adjusting energy consumption in line with needs

The previous section showed how pumps and fans can benefit from the use of variable speed drives. Still further advantages can be enjoyed by using these in conjunction with control devices tailored to meet individual requirements.

  • Control based on fixed pressure and variable flow: this type of control is often used for water distribution systems (drinking water, irrigation). It is also used to circulate fluids in cooling applications.
  • Control for heating systems: in heating and cooling circuits, flow should vary with temperature.
  • Control based on fixed flow and variable pressure: mainly associated with pumping applications (pressure differences caused by different levels) such as cleaning, watering, cooling and freezing installations. These require a certain amount of water, even where suction and discharge conditions vary.

The immediate advantages are:

  • Improved control and greater accuracy in terms of pressure and flow values
  • Significant reduction of transient effects within the electrical network and of mechanical restrictions affecting systems
  • Reduced noise and vibrations, as drives support fine speed adjustments, thereby preventing equipment from operating at the resonance frequency for ducts and pipes
  • Smooth starting and stopping

These in turn bring about further advantages:

  • Greater reliability and extended service lives for systems
  • Simpler tubing and pipe systems (by dispensing with dampers, control valves and bypass pipes)
  • Reduced maintenance

The ultimate goal is to reduce energy consumption and its associated costs.

 