The power in watts indicated on the tube of a discharge lamp does not include the power dissipated in the ballast.

Figure A8: gives the current taken by a complete unit, including all associated ancillary equipment.

These lamps depend on the luminous electrical discharge through a gas or vapour of a metallic compound, which is contained in a hermetically-sealed transparent envelope at a pre-determined pressure. These lamps have a long start-up time, during which the current Ia is greater than the nominal current In. Power and current demands are given for different types of lamp (typical average values which may differ slightly from one manufacturer to another).

Type of
lamp (W)
Power
demand
(W) at
230 V 400 V
Current In(A) Starting Luminous
efficiency
(lumens
per watt)
Average
timelife of
lamp (h)
Utilization
PF not
corrected
230 V 400 V
PF
corrected
 230 V 400 V
Ia/In Period
(mins)
High-pressure sodium vapour lamps
50 60 0.76 0.3 1.4 to 1.6 4 to 6 80 to 120 9000
  • Lighting of large halls
  • Outdoor spaces
  • Public lighting


70 80 1 0.45
100 115 1.2 0.65
150 168 1.8 0.85
250 274 3 1.4
400 431 4.4 2.2
1000 1055 10.45 4.9
Low-pressure sodium vapour lamps
26 34.5 0.45 0.17 1.1 to 1.3 7 to 15 100 to 200 8000 to 12000 
 
  • Lighting of autoroutes
  • Security lighting,station
  • Platform, storage areas



36 46.5   0.22
66 80.5   0.39
91 105.5   0.49
131 154   0.69
Mercury vapour + metal halide (also called metal-iodide)
70 80.5 1 0.40 1.7 3 to 5 70 to 90 6000
  • Lighting of very large areas by

    projectors (for example:
    sports stadiums, etc.)


150 172 1.80 0.88 6000
250 276 2.10 1.35 6000
400 425 3.40 2.15 6000
1000 1046 8.25 5.30 6000
2000 2092     2052 16.50    8.60 10.50      6 2000
Mercury vapour + fluorescent substance (fluorescent bulb)
50 57 0.6 0.30 1.7 to 2 3 to 6 40 to 60 8000 to 12000
  • Workshops with very high

    ceilings (halls, hangars)

  • Outdoor lighting
  • Low light output[1]



80 90 0.8 0.45
125 141 1.15 0.70
250 268 2.15 1.35
400 421 3.25 2.15
700 731 5.4 3.85
1000 1046 8.25 5.30
2000 2140    2080 15 11        6.1

[1] Replaced by sodium vapour lamps.
Note: these lamps are sensitive to voltage dips. They extinguish if the voltage falls to less than 50% of their nominal voltage, and will not re-ignite before cooling for approximately 4 minutes.
Note: Sodium vapour low-pressure lamps have a light-output efficiency which is superior to that of all other sources. However, use of these lamps is restricted by the fact that the yellow-orange colour emitted makes colour recognition practically impossible.

Fig. A8a: Current demands of discharge lamps