Ground Fault Protection (GFP)

From Electrical Installation Guide
Revision as of 03:27, 25 November 2016 by CleanUp2016 (talk | contribs) (Cleanup_2016)


Different type of ground fault protections

(see Fig. F27)

Three types of GFP are possible dependind on the measuring device installed :

Residual Sensing RS

The “insulation fault” current is calculated using the vectorial sum of currents of current transformers secondaries. The current transformer on the neutral conductor is often outside the circuit-breaker.

Source Ground Return SGR

The insulation fault current is measured in the neutral – earth link of the LV transformer. The current transformer is outside the circuit-breaker.

Zero Sequence ZS

The insulation fault is directly measured at the secondary of the current transformer using the sum of currents in live conductors. This type of GFP is only used with low fault current values.

Positioning GFP devices in the installation

Type / installation level Main-distribution Sub-distribution Comments
Source Ground Return (SGR) Possible Used
Residual Sensing (RS) (SGR) Possible Recommended or required Often used
Zero Sequence (SGR) Possible Recommended or required Rarely used