Equipment and appliances requiring reactive energy

From Electrical Installation Guide
Revision as of 16:32, 6 December 2016 by LMischler (talk | contribs) (1 revision: no page modification, previous revision = imported ch.L pages cleaned-up)

Home > Power Factor Correction > Power factor and Reactive power > Equipment and appliances requiring reactive energy


All AC equipment and appliances that include electromagnetic devices, or depend on magnetically coupled windings, require some degree of reactive current to create magnetic flux.

The most common items in this class are transformers, reactors, motors and discharge lamps with magnetic ballasts (see Fig. L5).

The proportion of reactive power (kvar) with respect to active power (kW) when a piece of equipment is fully loaded varies according to the item concerned being:

  • 65-75% for asynchronous motors (corresponding to a Power Factor 0.8 – 0.85)
  • 5-10% for transformers (corresponding to a Power Factor close to 0.995)


FigL02.jpg


Fig. L5: Power consuming items that also require reactive energy