Different kinds of motor control solution are compared in the following tables.



    Is / In Ts / Tn Speed control Torque control
Direct on line 5-10 5-10 No No
Star – Delta 2-3 1-2 No No
Auto-tranformer 2-3 1-2 No No
Soft starter 3-5 1.5-2.5 No Yes
Variable speed drive 1.5 1.5-2 Yes Yes


   pros cons
Direct on line Reduced cost Hight starting torque when necessary
Hight in-rush current, High torque so high contrainsts on motor, mechanics, ... not necessarily needed for the application starting
Star – Delta Reduced in-rush current Reduced starting torque, switching voltage & currents
Auto-tranformer Reduced in-rush current Hight weight
Soft starter

Reduced in-rush current controlled start and stop

Interesting solution in medium voltage as good value for money

Reduced starting torque
Variable speed drive

Controlled speed Energy saving at reduced speed

Sometimes the main "modern" solution according to the driven process characteristics

Higher cost

Fig. N63a: Comparison of different motor control solution