LV distribution - centralized or distributed layout

From Electrical Installation Guide
Revision as of 20:13, 10 December 2013 by LMischler (talk | contribs) (1 revision)

Home > MV and LV architecture selection guide for buildings > Choice of architecture details > LV distribution - centralized or distributed layout



Layout

Position of the main MV and LV equipment on the site or in the building.
This layout choice is applied to the results of stage 1.

Selection guide:

  • Place power sources as close as possible to the barycenter of power consumers,
  • Reduce atmospheric constraints: building dedicated premises if the layout in the workshop is too restrictive (temperature, vibrations, dust, etc.),
  • Placing heavy equipment (transformers, generators, etc) close to walls or main exists for ease of maintenance,

A layout example is given in the following diagram (Fig. D12):



FigD12.jpg
Fig. D12: The position of the global current consumer barycenter guides the positioning of power sources




Centralized or distributed layout

In centralized layout, current consumers are connected to the power sources by a star-connection. Cables are suitable for centralized layout, with point to point links between the MLVS and current consumers or sub-distribution boards (radial distribution, star- distribution) (Fig. D13):


FigD13.jpg

Fig. D13: Example of centralized layout with point to point links


In decentralized layout, current consumers are connected to sources via a busway. Busbar trunking systems are well suited to decentralized layout, to supply many loads that are spread out, making it easy to change, move or add connections (Fig D14):


FigD14.jpg

Fig. D14: Example of decentralized layout, with busbar trunking links


Factors in favour of centralized layout (see summary table in Fig. D15):

  • Installation flexibility: no,
  • Load distribution: localized loads (high unit power loads).

Factors in favor of decentralized layout:

  • Installation flexibility: "Implementation" flexibility (moving of workstations, etc…),
  • Load distribution: uniform distribution of low unit power loads


  Load distribution
 Flexibility  Localized loads     Intermediate distribution  Uniform distributed
 No flexibility Centralized Decentralized
 Design flexibility
 Implementation flexibility Centralized   Decentralized
 Operation flexibility

Fig. D15: Recommendations for centralized or decentralized layout


Power supply by cables gives greater independence of circuits (lighting, power sockets, HVAC, motors, auxiliaries, security, etc), reducing the consequences of a fault from the point of view of power availability.
The use of busbar trunking systems allows load power circuits to be combined and saves on conductors by taking advantage of a clustering coefficient. The choice between cable and busbar trunking, according to the clustering coefficient, allows us to find an economic optimum between investment costs, implementation costs and operating costs.
These two distribution modes are often combined.