Other lamp technologies - choice of contactors

From Electrical Installation Guide
Revision as of 02:45, 26 July 2016 by LMischler (talk | contribs) (table modified as per guide 2015)

Home > Characteristics of particular sources and loads > Lighting circuits > Other lamp technologies - choice of contactors


Modular contactors and impulse relays do not use the same technologies. Their rating is determined according to different standards.
For example, for a given rating, an impulse relay is more efficient than a modular contactor for the control of light fittings with a strong inrush current, or with a low power factor (non-compensated inductive circuit).

Figure 51 shows the maximum number of light fittings for each relay, according to the type, power and configuration of a given lamp. As an indication, the total acceptable power is also mentioned.

  • These values are given for a 230 V circuit with 2 active conductors (single-phase phase/neutral or two-phase phase/phase). For 110 V circuits, divide the values in the table by 2.
  • To obtain the equivalent values for the whole of a 230 V three-phase circuit, multiply the number of lamps and the total acceptable power:
    • by [math]\displaystyle{ \sqrt 3 }[/math] (1.73) for circuits without neutral;
    • by [math]\displaystyle{ \sqrt 3 }[/math] for circuits with 230 V between phase and neutral or 400 V between phases.

Note: The power ratings of the lamps most commonly used are shown in bold.

For powers not mentioned, use a proportional rule with the nearest values.

Products iCT contactors iCT+ contactors
Type of lamp Maximum number of light fittings for a single-phase circuit and maximum power output per circuit
16 A 25 A 40 A 63 A 20 A
Basic incandescent lamps, LV halogen lamps, replacement mercury vapour lamps (without ballast)
40 W 38 1500 W

2000 W

57 2300 W 115 4600 W 172 6900 W 4660 W x cos φ
60 W 30 45 85 125
75 W 25 38 70 100
100 W 19 28 50 73
ELV 12 or 24 V halogen lamps
With ferromagnetic transformer 20 W 15 300 W

à

600 W

23 450 W

à 900 W

42 850 W

à 1950 W

63 1250 W

à

2850 W

4660 W x Cos φ
50 W 10 15 27 42
75 W 8 12 23 35
100 W 6 8 18 27
With electronic transformer 20 W 62 1250 W

à 1600 W

90 1850 W

à 2250 W

182 3650 W

à 4200 W

275 5500 W

à 6000 W

50 W 25 39 76 114
75 W 20 28 53 78
100 W 16 22 42 60
Fluorescent tubes with starter and ferromagnetic ballast
1 tube without compensation(a) 15 W 22 330 W

à 850 W

30 450 W

à 1200 W

70 1050 W

à 2400 W

100 1500 W

à 3850 W

4660 W x cos φ
18 W 22 30 70 100
20 W 22 30 70 100
36 W 20 28 60 90
40 W 20 28 60 90
58 W 13 17 35 56
65 W 13 17 35 56
80 W 10 15 30 48
115 W 7 10 20 32
1 tube with parallel compensation(b) 15 W 5 µF 15 200 W

à 800 W

20 300 W

à

1200 W

40 600 W

à 2400 W

60 900 W

à 3500 W

18 W 5 µF 15 20 40 60
20 W 5 µF 15 20 40 60
36 W 5 µF 15 20 40 60
40 W 5 µF 15 20 40 60
58 W 7 µF 10 15 30 43
65 W 7 µF 10 15 30 43
80 W 7 µF 10 15 30 43
115 W 16 µF 5 7 14 20
2 or 4 tubes with series compensation 2 x 18 W 30 1100 W

à 1500 W

46 1650 W

à 2400 W

80 2900 W

à 3800 W

123 4450 W

à 5900 W

4 x 18 W 16 24 44 68
2 x 36 W 16 24 44 68
2 x 58 W 10 16 27 42
2 x 65 W 10 16 27 42
2 x 80 W 9 13 22 34
2 x 115 W 6 10 16 25
Fluorescent tubes with electronic ballast
1 or 2 tubes 18 W 74 1300 W

à 1400 W

111 2000 W

à 2200 W

222 4000 W

à 4400 W

333 6000 W

à 6600 W

4660 W x cos φ
36 W 38 58 117 176
58 W 25 37 74 111
2 x 18 W 36 55 111 166
2 x 36 W 20 30 60 90
2 x 58 W 12 19 38 57
Compact fluorescent lamps
With external electronic ballast 5 W 210 1050 W

à 1300 W

330 1650 W

à 2000 W

670 3350 W

à 4000 W

Non testé 4660 W x cos φ
7 W 150 222 478
9 W 122 194 383
11 W 104 163 327
18 W 66 105 216
26 W 50 76 153
With integral electronic ballast (replacement for incandescent lamps) 5 W 160 800 W

à 900 W

230 1150 W

à 1300 W

470 2350 W

à 2600 W

710 3550 W

à 3950 W

7 W 114 164 335 514
9 W 94 133 266 411
11 W 78 109 222 340
18 W 48 69 138 213
26 W 34 50 100 151
LED lamps
With driver 10 W 48 500 W

à 1400 W

69 700 W

à 1950 W

98 1000 W

à 3000 W

200 2000 W

à 6200 W

4660 W x cos φ
30 W 38 54 77 157
50 W 27 39 56 114
75 W 17 25 36 73
150 W 9 12 18 37
200 W 7 9 15 31
Low-pressure sodium vapour lamps with ferromagnetic ballast with external ignitor
Without compensation(a) 35 W 5 270 W

à 360 W

9 320 W

à 720 W

14 500 W

à 1100 W

24 850 W

à 1800 W

4660 W x cos φ
55 W 5 9 14 24
90 W 3 6 9 19
135 W 2 4 6 10
180 W 2 4 6 10
With parallel compensation(b) 35 W 20 µF 3 100 W

à 180 W

5 175 W

à 360 W

10 350 W

à 720 W

15 550 W

à 1100 W

55 W 20 µF 3 5 10 15
90 W 26 µF 2 4 8 11
135 W 40 µF 1 2 5 7
180 W 45 µF 1 2 4 6
High-pressure sodium vapour lamps

Metal-iodide lamps

With ferromagnetic ballast with external ignitor, without compensation(a) 35 W 16 600 W 24 850 W

à 1200 W

42 1450 W

à 2000 W

64 2250 W

à 3200 W

4660 W x cos φ
70 W 8 12 20 32
150 W 4 7 13 18
250 W 2 4 8 11
400 W 1 3 5 8
1000 W 0 1 2 3
With ferromagnetic ballast with external ignitor and parallel compensation(b) 35 W 6 µF 12 450 W

à 1000 W

18 650 W

à 2000 W

31 1100 W

à 4000 W

50 1750 W

à 6000 W

70 W 12 µF 6 9 16 25
150 W 20 µF 4 6 10 15
250 W 32 µF 3 4 7 10
400 W 45 µF 2 3 5 7
1000 W 60 µF 1 2 3 5
2000 W 85 µF 0 1 2 3
With electronic ballast 35 W 24 850 W

à 1350 W

38 1350 W

à 2200 W

68 2400 W

à 4000 W

102 3600 W

à 600 W

70 W 18 29 51 76
150 W 9 14 26 40

(a) Circuits with non-compensated ferromagnetic ballasts consume twice as much current for a given lamp power output. This explains the small number of lamps in this configuration.

(b) The total capacitance of the power factor correction capacitors in parallel in a circuit limits the number of lamps that can be controlled by a contactor. The total downstream capacitance of a modular contactor of rating 16, 25, 40 or 63 A should not exceed 75, 100, 200 or 300 μF respectively. Allow for these limits to calculate the maximum acceptable number of lamps if the capacitance values are different from those in the table.

Fig. N52a:  Maximum number of light fittings for each relay, according to the type, power and configuration of a given lamp


Products iTL impulse relays iTL+ impulse relays Reflex iC60 (C curve)
Type of lamp Maximum number of light fittings for a single-phase circuit and maximum power output per circuit
16 A 32 A 16 A 10 A 16 A 25 A 40 A 63 A
Basic incandescent lamps, LV halogen lamps, replacement mercury vapour lamps (without ballast)
40W 40 1500W

à 1600W

106 4000W

à 4200W

3680W x

cosφ

28 1120W

à 2175W

46 1840W

à 2600W

70 2800W

à 3600W

140 5600W

à 6800W

207 8280W

à 9800W

60W 25 66 23 36 55 103 152
75W 20 53 29 31 46 80 121
100W 16 42 15 23 33 60 88
ELV 12 or 24 V halogen lamps
With ferromagnetic transformer 20W 70 1350W

à 1450W

180 3600W

à 3750W

3680W x

cosφ

11 220W

à 500W

19 380W

à 800W

27 540W

à 1050W

50 1000W

à 2200W

75 1500W

à 3300W

50W 28 74 8 12 19 33 51
75W 19 50 7 10 14 27 43
100W 14 37 5 8 10 22 33
With electronic transformer 20W 60 1200W

à 1400W

160 3200W

à 3350W

47 940W

à 1200W

74 1480W

à 2000W

108 2160W

à 2600W

220 4400W

à 5100W

333 6660W

à 7300W

50W 25 65 19 31 47 92 137
75W 18 44 15 24 34 64 94
100W 14 33 12 20 26 51 73
Fluorescent tubes with starter and ferromagnetic ballast
1 tube without compensation(a) 15W 83 1250W

à 1300W

213 3200W

à 3350W

3680W x

cosφ

16 244W

à 647W

26 390W

à 1035W

37 555W

à 1520W

85 1275W

à 2880W

121 1815W

à 4640W

18W 70 186 16 26 37 85 121
20W 62 160 16 26 37 85 121
36W 35 93 15 24 34 72 108
40W 31 81 15 24 34 72 108
58W 21 55 9 15 21 43 68
65W 20 50 9 15 21 43 68
80W 16 41 8 12 19 36 58
115W 11 29 6 9 12 24 38
1 tube with parallel compensation(b) 15W 5µF 60 900W 160 2400W 11 165W

à 640W

19 285W

à 960W

24 360W

à 1520W

48 720W

à 2880W

72 1080W

à 4080W

18W 5µF 50 133 11 19 24 48 72
20W 5µF 45 120 11 19 24 48 72
36W 5µF 25 66 11 19 24 48 72
40W 5µF 22 60 11 19 24 48 72
58W 7µF 16 42 8 12 19 36 51
65W 7µF 13 37 8 12 19 36 51
80W 7µF 11 30 8 12 19 36 51
115W 16µF 7 20 4 7 9 17 24
2 or 4 tubes with series compensation 2 x 18W 56 2000W 148 5300W 23 828W

à 1150W

36 1296W

à 1840W

56 2016W

à 2760W

96 3456W

à 4600W

148 5328W

à 7130W

4 x 18W 28 74 12 20 29 52 82
2 x 36W 28 74 12 20 29 52 82
2 x 58W 17 45 8 12 20 33 51
2 x 65W 15 40 8 12 20 33 51
2 x 80W 12 33 7 11 1 26 41
2 x 115W 8 23 5 8 12 20 31
Fluorescent tubes with electronic ballast
1 or 2 tubes 18W 80 1450W

à 1550W

212 3800W

à 4000W

3680W x

cosφ

56 1008W

à 1152W

90 1620W

à 1798W

134 2412W

à 2668W

268 4824W

à 5336W

402 7236W

à 8120W

36W 40 106 28 46 70 142 213
58W 26 69 19 31 45 90 134
2 x 18W 40 106 27 44 67 134 201
2 x 36W 20 53 16 24 37 72 108
2 x 58W 13 34 9 15 23 46 70
Compact fluorescent lamps
With external electronic ballast 5W 240 1200W

à 1450W

630 3150W

à 3800W

3680W x

cosφ

158 790W

à 962W

251 1255W

à 1560W

399 1995W

à 2392W

810 4050W

à 4706W

Usage peu fréquent
7W 171 457 113 181 268 578
9W 138 366 92 147 234 463
11W 118 318 79 125 196 396
18W 77 202 49 80 127 261
26W 55 146 37 60 92 181
With integral electronic ballast(replacement for incandescent lamps) 5W 170 850W

à 1050W

390 1950W

à 2400W

121 605W

à 650W

193 959W

à 1044W

278 1390W

à 1560W

568 2840W

à 3146W

859 4295W

à 4732W

7W 121 285 85 137 198 405 621
9W 100 233 71 113 160 322 497
11W 86 200 59 94 132 268 411
18W 55 127 36 58 83 167 257
26W 40 92 25 40 60 121 182
Low-pressure sodium vapour lamps with ferromagnetic ballast with external ignitor
Without compensation(a) 35W Non testé, utilisation peu fréquente 3680W x

cosφ

4 153W

à 253W

7 245W

à 405W

11 385W

à 792W

17 595W

à 1198W

29 1015W

à 2070W

55W 4 7 11 17 29
90W 3 4 8 11 23
135W 2 3 5 8 12
180W 1 2 4 7 10
With parallel compensation(b) 35W 20µF 38 1350W 102 3600W 3 88W

à 169W

4 140W

à 270W

7 245W

à 450W

12 420W

à 720W

19 665W

à 1440W

55W 20µF 24 63 3 4 7 12 19
90W 26µF 15 40 2 3 5 8 13
135W 40µF 10 26 1 2 3 5 9
180W 45µF 7 18 0 1 2 4 8
High-pressure sodium vapour lamps
Metal-iodide lamps
With ferromagnetic ballast with external ignitor, without compensation(a) 35W Non testé, utilisation peu fréquente 3680W x

cosφ

12 416W

à 481W

19 400W

à 750W

28 980W

à 1350W

50 1750W

à 2500W

77 2695W

à 4000W

70W 7 11 15 24 38
150W 3 5 9 15 22
250W 2 3 5 10 13
400W 0 1 3 6 10
1000W 0 0 1 2 3
With ferromagnetic ballast with external ignitor and parallel compensation(b) 6µF 34 1200W

à 1350W

88 3100W

à 3400W

14 490W

à 800W

17 595W

à 1200W

26 910W

à 2200W

43 1505W

à 4400W

70 2450W

à 7000W

70W 12µF 17 45 8 9 13 23 35
150W 20µF 8 22 5 6 9 14 21
250W 32µF 5 13 3 4 5 10 14
400W 45µF 3 8 2 3 4 7 9
1000W 60µF 1 3 0 1 2 4 7
2000W 85µF 0 1 0 0 1 2 3
With electronic ballast 35W 38 1350W

à 2200W

87 3100W

à 5000W

15 525W

à 844W

24 840W

à 1350W

38 1330W

à 2100W

82 2870W

à 4650W

123 4305W

à 7200W

70W 29 77 11 18 29 61 92
150W 14 33 6 9 14 31 48
LED lamps
With driver 10W 69 700W

à 1950W

98 1000W

à 3000W

3680W x

cosφ

30 300W

à 850W

44 450W

à 1250W

71 700W

à 2000W

108 1050W

à 3050W

146 1450W

à 4150W

30W 54 77 24 34 55 83 113
50W 39 56 17 25 40 61 83
75W 25 36 11 15 24 37 50
150W 12 18 5 7 11 17 23
200W 9 15 - 6 10 15 20

(a) Circuits with non-compensated ferromagnetic ballasts consume twice as much current for a given lamp power output. This explains the small number of lamps in this configuration.

(b) The total capacitance of the power factor correction capacitors in parallel in a circuit limits the number of lamps that can be controlled by a contactor. The total downstream capacitance of a modular contactor of rating 16, 25, 40 or 63 A should not exceed 75, 100, 200 or 300 μF respectively. Allow for these limits to calculate the maximum acceptable number of lamps if the capacitance values are different from those in the table.

Fig. N52b:  Maximum number of light fittings for each relay, according to the type, power and configuration of a given lamp


Note: Reflex iC60

High-pressure sodium vapour lamp with electronic ballast

  • For the 10 A and 16 A B-curve ratings, the number of lamps should be reduced by 10 % to limit unwanted magnetic tripping.

LED lamp

  • B-curve ratings, the number of lamps should be reduced by 50 %.
  • D-curve ratings, the number of lamps should be increased by 50 %.

ru:Ограничения, связанные с осветительными устройствами, и рекомендации

Share