Other lamp technologies - choice of contactors
Modular contactors and impulse relays do not use the same technologies. Their rating is determined according to different standards.
For example, for a given rating, an impulse relay is more efficient than a modular contactor for the control of light fittings with a strong inrush current, or with a low power factor (non-compensated inductive circuit).
Figure 51 shows the maximum number of light fittings for each relay, according to the type, power and configuration of a given lamp. As an indication, the total acceptable power is also mentioned.
- These values are given for a 230 V circuit with 2 active conductors (single-phase phase/neutral or two-phase phase/phase). For 110 V circuits, divide the values in the table by 2.
- To obtain the equivalent values for the whole of a 230 V three-phase circuit, multiply the number of lamps and the total acceptable power:
- by [math]\displaystyle{ \sqrt 3 }[/math] (1.73) for circuits without neutral;
- by [math]\displaystyle{ \sqrt 3 }[/math] for circuits with 230 V between phase and neutral or 400 V between phases.
Note: The power ratings of the lamps most commonly used are shown in bold.
For powers not mentioned, use a proportional rule with the nearest values.
Products | iCT contactors | iCT+ contactors | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Type of lamp | Maximum number of light fittings for a single-phase circuit and maximum power output per circuit | ||||||||||
16 A | 25 A | 40 A | 63 A | 20 A | |||||||
Basic incandescent lamps, LV halogen lamps, replacement mercury vapour lamps (without ballast) | |||||||||||
40 W | 38 | 1500 W
2000 W |
57 | 2300 W | 115 | 4600 W | 172 | 6900 W | 4660 W x cos φ | ||
60 W | 30 | 45 | 85 | 125 | |||||||
75 W | 25 | 38 | 70 | 100 | |||||||
100 W | 19 | 28 | 50 | 73 | |||||||
ELV 12 or 24 V halogen lamps | |||||||||||
With ferromagnetic transformer | 20 W | 15 | 300 W
à 600 W |
23 | 450 W
à 900 W |
42 | 850 W
à 1950 W |
63 | 1250 W
à 2850 W |
4660 W x Cos φ | |
50 W | 10 | 15 | 27 | 42 | |||||||
75 W | 8 | 12 | 23 | 35 | |||||||
100 W | 6 | 8 | 18 | 27 | |||||||
With electronic transformer | 20 W | 62 | 1250 W
à 1600 W |
90 | 1850 W
à 2250 W |
182 | 3650 W
à 4200 W |
275 | 5500 W
à 6000 W | ||
50 W | 25 | 39 | 76 | 114 | |||||||
75 W | 20 | 28 | 53 | 78 | |||||||
100 W | 16 | 22 | 42 | 60 | |||||||
Fluorescent tubes with starter and ferromagnetic ballast | |||||||||||
1 tube without compensation(a) | 15 W | 22 | 330 W
à 850 W |
30 | 450 W
à 1200 W |
70 | 1050 W
à 2400 W |
100 | 1500 W
à 3850 W |
4660 W x cos φ | |
18 W | 22 | 30 | 70 | 100 | |||||||
20 W | 22 | 30 | 70 | 100 | |||||||
36 W | 20 | 28 | 60 | 90 | |||||||
40 W | 20 | 28 | 60 | 90 | |||||||
58 W | 13 | 17 | 35 | 56 | |||||||
65 W | 13 | 17 | 35 | 56 | |||||||
80 W | 10 | 15 | 30 | 48 | |||||||
115 W | 7 | 10 | 20 | 32 | |||||||
1 tube with parallel compensation(b) | 15 W | 5 µF | 15 | 200 W
à 800 W |
20 | 300 W
à 1200 W |
40 | 600 W
à 2400 W |
60 | 900 W
à 3500 W | |
18 W | 5 µF | 15 | 20 | 40 | 60 | ||||||
20 W | 5 µF | 15 | 20 | 40 | 60 | ||||||
36 W | 5 µF | 15 | 20 | 40 | 60 | ||||||
40 W | 5 µF | 15 | 20 | 40 | 60 | ||||||
58 W | 7 µF | 10 | 15 | 30 | 43 | ||||||
65 W | 7 µF | 10 | 15 | 30 | 43 | ||||||
80 W | 7 µF | 10 | 15 | 30 | 43 | ||||||
115 W | 16 µF | 5 | 7 | 14 | 20 | ||||||
2 or 4 tubes with series compensation | 2 x 18 W | 30 | 1100 W
à 1500 W |
46 | 1650 W
à 2400 W |
80 | 2900 W
à 3800 W |
123 | 4450 W
à 5900 W | ||
4 x 18 W | 16 | 24 | 44 | 68 | |||||||
2 x 36 W | 16 | 24 | 44 | 68 | |||||||
2 x 58 W | 10 | 16 | 27 | 42 | |||||||
2 x 65 W | 10 | 16 | 27 | 42 | |||||||
2 x 80 W | 9 | 13 | 22 | 34 | |||||||
2 x 115 W | 6 | 10 | 16 | 25 | |||||||
Fluorescent tubes with electronic ballast | |||||||||||
1 or 2 tubes | 18 W | 74 | 1300 W
à 1400 W |
111 | 2000 W
à 2200 W |
222 | 4000 W
à 4400 W |
333 | 6000 W
à 6600 W |
4660 W x cos φ | |
36 W | 38 | 58 | 117 | 176 | |||||||
58 W | 25 | 37 | 74 | 111 | |||||||
2 x 18 W | 36 | 55 | 111 | 166 | |||||||
2 x 36 W | 20 | 30 | 60 | 90 | |||||||
2 x 58 W | 12 | 19 | 38 | 57 | |||||||
Compact fluorescent lamps | |||||||||||
With external electronic ballast | 5 W | 210 | 1050 W
à 1300 W |
330 | 1650 W
à 2000 W |
670 | 3350 W
à 4000 W |
Non testé | 4660 W x cos φ | ||
7 W | 150 | 222 | 478 | ||||||||
9 W | 122 | 194 | 383 | ||||||||
11 W | 104 | 163 | 327 | ||||||||
18 W | 66 | 105 | 216 | ||||||||
26 W | 50 | 76 | 153 | ||||||||
With integral electronic ballast (replacement for incandescent lamps) | 5 W | 160 | 800 W
à 900 W |
230 | 1150 W
à 1300 W |
470 | 2350 W
à 2600 W |
710 | 3550 W
à 3950 W | ||
7 W | 114 | 164 | 335 | 514 | |||||||
9 W | 94 | 133 | 266 | 411 | |||||||
11 W | 78 | 109 | 222 | 340 | |||||||
18 W | 48 | 69 | 138 | 213 | |||||||
26 W | 34 | 50 | 100 | 151 | |||||||
LED lamps | |||||||||||
With driver | 10 W | 48 | 500 W
à 1400 W |
69 | 700 W
à 1950 W |
98 | 1000 W
à 3000 W |
200 | 2000 W
à 6200 W |
4660 W x cos φ | |
30 W | 38 | 54 | 77 | 157 | |||||||
50 W | 27 | 39 | 56 | 114 | |||||||
75 W | 17 | 25 | 36 | 73 | |||||||
150 W | 9 | 12 | 18 | 37 | |||||||
200 W | 7 | 9 | 15 | 31 | |||||||
Low-pressure sodium vapour lamps with ferromagnetic ballast with external ignitor | |||||||||||
Without compensation(a) | 35 W | 5 | 270 W
à 360 W |
9 | 320 W
à 720 W |
14 | 500 W
à 1100 W |
24 | 850 W
à 1800 W |
4660 W x cos φ | |
55 W | 5 | 9 | 14 | 24 | |||||||
90 W | 3 | 6 | 9 | 19 | |||||||
135 W | 2 | 4 | 6 | 10 | |||||||
180 W | 2 | 4 | 6 | 10 | |||||||
With parallel compensation(b) | 35 W | 20 µF | 3 | 100 W
à 180 W |
5 | 175 W
à 360 W |
10 | 350 W
à 720 W |
15 | 550 W
à 1100 W | |
55 W | 20 µF | 3 | 5 | 10 | 15 | ||||||
90 W | 26 µF | 2 | 4 | 8 | 11 | ||||||
135 W | 40 µF | 1 | 2 | 5 | 7 | ||||||
180 W | 45 µF | 1 | 2 | 4 | 6 | ||||||
High-pressure sodium vapour lamps Metal-iodide lamps | |||||||||||
With ferromagnetic ballast with external ignitor, without compensation(a) | 35 W | 16 | 600 W | 24 | 850 W
à 1200 W |
42 | 1450 W
à 2000 W |
64 | 2250 W
à 3200 W |
4660 W x cos φ | |
70 W | 8 | 12 | 20 | 32 | |||||||
150 W | 4 | 7 | 13 | 18 | |||||||
250 W | 2 | 4 | 8 | 11 | |||||||
400 W | 1 | 3 | 5 | 8 | |||||||
1000 W | 0 | 1 | 2 | 3 | |||||||
With ferromagnetic ballast with external ignitor and parallel compensation(b) | 35 W | 6 µF | 12 | 450 W
à 1000 W |
18 | 650 W
à 2000 W |
31 | 1100 W
à 4000 W |
50 | 1750 W
à 6000 W | |
70 W | 12 µF | 6 | 9 | 16 | 25 | ||||||
150 W | 20 µF | 4 | 6 | 10 | 15 | ||||||
250 W | 32 µF | 3 | 4 | 7 | 10 | ||||||
400 W | 45 µF | 2 | 3 | 5 | 7 | ||||||
1000 W | 60 µF | 1 | 2 | 3 | 5 | ||||||
2000 W | 85 µF | 0 | 1 | 2 | 3 | ||||||
With electronic ballast | 35 W | 24 | 850 W
à 1350 W |
38 | 1350 W
à 2200 W |
68 | 2400 W
à 4000 W |
102 | 3600 W
à 600 W | ||
70 W | 18 | 29 | 51 | 76 | |||||||
150 W | 9 | 14 | 26 | 40 |
(a) Circuits with non-compensated ferromagnetic ballasts consume twice as much current for a given lamp power output. This explains the small number of lamps in this configuration.
(b) The total capacitance of the power factor correction capacitors in parallel in a circuit limits the number of lamps that can be controlled by a contactor. The total downstream capacitance of a modular contactor of rating 16, 25, 40 or 63 A should not exceed 75, 100, 200 or 300 μF respectively. Allow for these limits to calculate the maximum acceptable number of lamps if the capacitance values are different from those in the table.
Fig. N52a: Maximum number of light fittings for each relay, according to the type, power and configuration of a given lamp
Products | iTL impulse relays | iTL+ impulse relays | Reflex iC60 (C curve) | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Type of lamp | Maximum number of light fittings for a single-phase circuit and maximum power output per circuit | ||||||||||||||||
16 A | 32 A | 16 A | 10 A | 16 A | 25 A | 40 A | 63 A | ||||||||||
Basic incandescent lamps, LV halogen lamps, replacement mercury vapour lamps (without ballast) | |||||||||||||||||
40W | 40 | 1500W
à 1600W |
106 | 4000W
à 4200W |
3680W x
cosφ |
28 | 1120W
à 2175W |
46 | 1840W
à 2600W |
70 | 2800W
à 3600W |
140 | 5600W
à 6800W |
207 | 8280W
à 9800W | ||
60W | 25 | 66 | 23 | 36 | 55 | 103 | 152 | ||||||||||
75W | 20 | 53 | 29 | 31 | 46 | 80 | 121 | ||||||||||
100W | 16 | 42 | 15 | 23 | 33 | 60 | 88 | ||||||||||
ELV 12 or 24 V halogen lamps | |||||||||||||||||
With ferromagnetic transformer | 20W | 70 | 1350W
à 1450W |
180 | 3600W
à 3750W |
3680W x
cosφ |
11 | 220W
à 500W |
19 | 380W
à 800W |
27 | 540W
à 1050W |
50 | 1000W
à 2200W |
75 | 1500W
à 3300W | |
50W | 28 | 74 | 8 | 12 | 19 | 33 | 51 | ||||||||||
75W | 19 | 50 | 7 | 10 | 14 | 27 | 43 | ||||||||||
100W | 14 | 37 | 5 | 8 | 10 | 22 | 33 | ||||||||||
With electronic transformer | 20W | 60 | 1200W
à 1400W |
160 | 3200W
à 3350W |
47 | 940W
à 1200W |
74 | 1480W
à 2000W |
108 | 2160W
à 2600W |
220 | 4400W
à 5100W |
333 | 6660W
à 7300W | ||
50W | 25 | 65 | 19 | 31 | 47 | 92 | 137 | ||||||||||
75W | 18 | 44 | 15 | 24 | 34 | 64 | 94 | ||||||||||
100W | 14 | 33 | 12 | 20 | 26 | 51 | 73 | ||||||||||
Fluorescent tubes with starter and ferromagnetic ballast | |||||||||||||||||
1 tube without compensation(a) | 15W | 83 | 1250W
à 1300W |
213 | 3200W
à 3350W |
3680W x
cosφ |
16 | 244W
à 647W |
26 | 390W
à 1035W |
37 | 555W
à 1520W |
85 | 1275W
à 2880W |
121 | 1815W
à 4640W | |
18W | 70 | 186 | 16 | 26 | 37 | 85 | 121 | ||||||||||
20W | 62 | 160 | 16 | 26 | 37 | 85 | 121 | ||||||||||
36W | 35 | 93 | 15 | 24 | 34 | 72 | 108 | ||||||||||
40W | 31 | 81 | 15 | 24 | 34 | 72 | 108 | ||||||||||
58W | 21 | 55 | 9 | 15 | 21 | 43 | 68 | ||||||||||
65W | 20 | 50 | 9 | 15 | 21 | 43 | 68 | ||||||||||
80W | 16 | 41 | 8 | 12 | 19 | 36 | 58 | ||||||||||
115W | 11 | 29 | 6 | 9 | 12 | 24 | 38 | ||||||||||
1 tube with parallel compensation(b) | 15W | 5µF | 60 | 900W | 160 | 2400W | 11 | 165W
à 640W |
19 | 285W
à 960W |
24 | 360W
à 1520W |
48 | 720W
à 2880W |
72 | 1080W
à 4080W | |
18W | 5µF | 50 | 133 | 11 | 19 | 24 | 48 | 72 | |||||||||
20W | 5µF | 45 | 120 | 11 | 19 | 24 | 48 | 72 | |||||||||
36W | 5µF | 25 | 66 | 11 | 19 | 24 | 48 | 72 | |||||||||
40W | 5µF | 22 | 60 | 11 | 19 | 24 | 48 | 72 | |||||||||
58W | 7µF | 16 | 42 | 8 | 12 | 19 | 36 | 51 | |||||||||
65W | 7µF | 13 | 37 | 8 | 12 | 19 | 36 | 51 | |||||||||
80W | 7µF | 11 | 30 | 8 | 12 | 19 | 36 | 51 | |||||||||
115W | 16µF | 7 | 20 | 4 | 7 | 9 | 17 | 24 | |||||||||
2 or 4 tubes with series compensation | 2 x 18W | 56 | 2000W | 148 | 5300W | 23 | 828W
à 1150W |
36 | 1296W
à 1840W |
56 | 2016W
à 2760W |
96 | 3456W
à 4600W |
148 | 5328W
à 7130W | ||
4 x 18W | 28 | 74 | 12 | 20 | 29 | 52 | 82 | ||||||||||
2 x 36W | 28 | 74 | 12 | 20 | 29 | 52 | 82 | ||||||||||
2 x 58W | 17 | 45 | 8 | 12 | 20 | 33 | 51 | ||||||||||
2 x 65W | 15 | 40 | 8 | 12 | 20 | 33 | 51 | ||||||||||
2 x 80W | 12 | 33 | 7 | 11 | 1 | 26 | 41 | ||||||||||
2 x 115W | 8 | 23 | 5 | 8 | 12 | 20 | 31 | ||||||||||
Fluorescent tubes with electronic ballast | |||||||||||||||||
1 or 2 tubes | 18W | 80 | 1450W
à 1550W |
212 | 3800W
à 4000W |
3680W x
cosφ |
56 | 1008W
à 1152W |
90 | 1620W
à 1798W |
134 | 2412W
à 2668W |
268 | 4824W
à 5336W |
402 | 7236W
à 8120W | |
36W | 40 | 106 | 28 | 46 | 70 | 142 | 213 | ||||||||||
58W | 26 | 69 | 19 | 31 | 45 | 90 | 134 | ||||||||||
2 x 18W | 40 | 106 | 27 | 44 | 67 | 134 | 201 | ||||||||||
2 x 36W | 20 | 53 | 16 | 24 | 37 | 72 | 108 | ||||||||||
2 x 58W | 13 | 34 | 9 | 15 | 23 | 46 | 70 | ||||||||||
Compact fluorescent lamps | |||||||||||||||||
With external electronic ballast | 5W | 240 | 1200W
à 1450W |
630 | 3150W
à 3800W |
3680W x
cosφ |
158 | 790W
à 962W |
251 | 1255W
à 1560W |
399 | 1995W
à 2392W |
810 | 4050W
à 4706W |
Usage peu fréquent | ||
7W | 171 | 457 | 113 | 181 | 268 | 578 | |||||||||||
9W | 138 | 366 | 92 | 147 | 234 | 463 | |||||||||||
11W | 118 | 318 | 79 | 125 | 196 | 396 | |||||||||||
18W | 77 | 202 | 49 | 80 | 127 | 261 | |||||||||||
26W | 55 | 146 | 37 | 60 | 92 | 181 | |||||||||||
With integral electronic ballast(replacement for incandescent lamps) | 5W | 170 | 850W
à 1050W |
390 | 1950W
à 2400W |
121 | 605W
à 650W |
193 | 959W
à 1044W |
278 | 1390W
à 1560W |
568 | 2840W
à 3146W |
859 | 4295W
à 4732W | ||
7W | 121 | 285 | 85 | 137 | 198 | 405 | 621 | ||||||||||
9W | 100 | 233 | 71 | 113 | 160 | 322 | 497 | ||||||||||
11W | 86 | 200 | 59 | 94 | 132 | 268 | 411 | ||||||||||
18W | 55 | 127 | 36 | 58 | 83 | 167 | 257 | ||||||||||
26W | 40 | 92 | 25 | 40 | 60 | 121 | 182 | ||||||||||
Low-pressure sodium vapour lamps with ferromagnetic ballast with external ignitor | |||||||||||||||||
Without compensation(a) | 35W | Non testé, utilisation peu fréquente | 3680W x
cosφ |
4 | 153W
à 253W |
7 | 245W
à 405W |
11 | 385W
à 792W |
17 | 595W
à 1198W |
29 | 1015W
à 2070W | ||||
55W | 4 | 7 | 11 | 17 | 29 | ||||||||||||
90W | 3 | 4 | 8 | 11 | 23 | ||||||||||||
135W | 2 | 3 | 5 | 8 | 12 | ||||||||||||
180W | 1 | 2 | 4 | 7 | 10 | ||||||||||||
With parallel compensation(b) | 35W | 20µF | 38 | 1350W | 102 | 3600W | 3 | 88W
à 169W |
4 | 140W
à 270W |
7 | 245W
à 450W |
12 | 420W
à 720W |
19 | 665W
à 1440W | |
55W | 20µF | 24 | 63 | 3 | 4 | 7 | 12 | 19 | |||||||||
90W | 26µF | 15 | 40 | 2 | 3 | 5 | 8 | 13 | |||||||||
135W | 40µF | 10 | 26 | 1 | 2 | 3 | 5 | 9 | |||||||||
180W | 45µF | 7 | 18 | 0 | 1 | 2 | 4 | 8 | |||||||||
High-pressure sodium vapour lamps Metal-iodide lamps | |||||||||||||||||
With ferromagnetic ballast with external ignitor, without compensation(a) | 35W | Non testé, utilisation peu fréquente | 3680W x
cosφ |
12 | 416W
à 481W |
19 | 400W
à 750W |
28 | 980W
à 1350W |
50 | 1750W
à 2500W |
77 | 2695W
à 4000W | ||||
70W | 7 | 11 | 15 | 24 | 38 | ||||||||||||
150W | 3 | 5 | 9 | 15 | 22 | ||||||||||||
250W | 2 | 3 | 5 | 10 | 13 | ||||||||||||
400W | 0 | 1 | 3 | 6 | 10 | ||||||||||||
1000W | 0 | 0 | 1 | 2 | 3 | ||||||||||||
With ferromagnetic ballast with external ignitor and parallel compensation(b) | 6µF | 34 | 1200W
à 1350W |
88 | 3100W
à 3400W |
14 | 490W
à 800W |
17 | 595W
à 1200W |
26 | 910W
à 2200W |
43 | 1505W
à 4400W |
70 | 2450W
à 7000W | ||
70W | 12µF | 17 | 45 | 8 | 9 | 13 | 23 | 35 | |||||||||
150W | 20µF | 8 | 22 | 5 | 6 | 9 | 14 | 21 | |||||||||
250W | 32µF | 5 | 13 | 3 | 4 | 5 | 10 | 14 | |||||||||
400W | 45µF | 3 | 8 | 2 | 3 | 4 | 7 | 9 | |||||||||
1000W | 60µF | 1 | 3 | 0 | 1 | 2 | 4 | 7 | |||||||||
2000W | 85µF | 0 | 1 | 0 | 0 | 1 | 2 | 3 | |||||||||
With electronic ballast | 35W | 38 | 1350W
à 2200W |
87 | 3100W
à 5000W |
15 | 525W
à 844W |
24 | 840W
à 1350W |
38 | 1330W
à 2100W |
82 | 2870W
à 4650W |
123 | 4305W
à 7200W | ||
70W | 29 | 77 | 11 | 18 | 29 | 61 | 92 | ||||||||||
150W | 14 | 33 | 6 | 9 | 14 | 31 | 48 | ||||||||||
LED lamps | |||||||||||||||||
With driver | 10W | 69 | 700W
à 1950W |
98 | 1000W
à 3000W |
3680W x
cosφ |
30 | 300W
à 850W |
44 | 450W
à 1250W |
71 | 700W
à 2000W |
108 | 1050W
à 3050W |
146 | 1450W
à 4150W | |
30W | 54 | 77 | 24 | 34 | 55 | 83 | 113 | ||||||||||
50W | 39 | 56 | 17 | 25 | 40 | 61 | 83 | ||||||||||
75W | 25 | 36 | 11 | 15 | 24 | 37 | 50 | ||||||||||
150W | 12 | 18 | 5 | 7 | 11 | 17 | 23 | ||||||||||
200W | 9 | 15 | - | 6 | 10 | 15 | 20 |
(a) Circuits with non-compensated ferromagnetic ballasts consume twice as much current for a given lamp power output. This explains the small number of lamps in this configuration.
(b) The total capacitance of the power factor correction capacitors in parallel in a circuit limits the number of lamps that can be controlled by a contactor. The total downstream capacitance of a modular contactor of rating 16, 25, 40 or 63 A should not exceed 75, 100, 200 or 300 μF respectively. Allow for these limits to calculate the maximum acceptable number of lamps if the capacitance values are different from those in the table.
Fig. N52b: Maximum number of light fittings for each relay, according to the type, power and configuration of a given lamp
Note: Reflex iC60
High-pressure sodium vapour lamp with electronic ballast
- For the 10 A and 16 A B-curve ratings, the number of lamps should be reduced by 10 % to limit unwanted magnetic tripping.
LED lamp
- B-curve ratings, the number of lamps should be reduced by 50 %.
- D-curve ratings, the number of lamps should be increased by 50 %.
ru:Ограничения, связанные с осветительными устройствами, и рекомендации