LED lamps - choice of contactors
From Electrical Installation Guide
Figure N49 and Figure N50 show the maximum number of LED lamps for each contactor / relay.
- These values are given for a 230 V circuit with 2 active conductors (single-phase phase/neutral or two-phase phase/phase). For 110 V circuits, divide the values in the table by 2.
- To obtain the equivalent values for the whole of a 230 V three-phase circuit, multiply the number of lamps and the total acceptable power:
- by √3 (1.73) for circuits with 230 V between phases without neutral,
- by 3 for circuits with 230 V between phase and neutral or 400 V between phases.
- for Reflex iC60:
- B-curve ratings, the number of lamps should be reduced by 50 %.
- D-curve ratings, the number of lamps should be increased by 50 %.
Products | iCT contactors | iCT+ contactors | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Type of lamp | Maximum number of light fittings for a single-phase circuit and maximum power output per circuit | ||||||||||
16 A | 25 A | 40 A | 63 A | 20 A | |||||||
LED lamps | |||||||||||
With driver | 10 W | 48 | 500 W to 1400 W |
69 | 700 W to 1950 W |
98 | 1000 W to 3000 W |
200 | 2000 W to 6200 W |
4660 W x cos φ | |
30 W | 38 | 54 | 77 | 157 | |||||||
50 W | 27 | 39 | 56 | 114 | |||||||
75 W | 17 | 25 | 36 | 73 | |||||||
150 W | 9 | 12 | 18 | 37 | |||||||
200 W | 7 | 9 | 15 | 31 |
Fig. N49 – Maximum number of LED lamps for iCT and iCT+ contactors
Products | iTL impulse relays | iTL+ impulse relays | Reflex iC60 (C curve) | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Type of lamp | Maximum number of light fittings for a single-phase circuit and maximum power output per circuit | ||||||||||||||||
16 A | 32 A | 16 A | 10 A | 16 A | 25 A | 40 A | 63 A | ||||||||||
LED lamps | |||||||||||||||||
With driver | 10W | 69 | 700W to 1950W |
98 | 1000W to 3000W |
3680W x
cosφ |
30 | 300W to 850W |
44 | 450W to 1250W |
71 | 700W to 2000W |
108 | 1050W to 3050W |
146 | 1450W to 4150W | |
30W | 54 | 77 | 24 | 34 | 55 | 83 | 113 | ||||||||||
50W | 39 | 56 | 17 | 25 | 40 | 61 | 83 | ||||||||||
75W | 25 | 36 | 11 | 15 | 24 | 37 | 50 | ||||||||||
150W | 12 | 18 | 5 | 7 | 11 | 17 | 23 | ||||||||||
200W | 9 | 15 | - | 6 | 10 | 15 | 20 |
Fig. N50 – Maximum number of LED lamps for iTL and iTL+ impulse relays, and for Reflex iC60 (C-Curve)