Types of RCDs

From Electrical Installation Guide
Revision as of 07:35, 4 August 2022 by LMischler (talk | contribs) (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)

Home > Protection against electric shocks and electrical fires > Residual Current Devices (RCDs) > Types of RCDs

The fault residual current could take various waveforms depending on the load characteristics. The following types of RCDs are defined in IEC 60755, for suitable protection of different forms of residual current:

Type AC DB431079.svg

Type AC RCDs detect residual sinusoidal alternating currents. Type AC RCDs are suitable for general use and cover most of the applications in practice.

Type A DB431080.svg

In addition to the detection characteristics of type AC RCDs, Type A RCDs detect pulsating DC residual current. Such waveforms can be caused by diode or thyristor rectifier circuit in electronic loads. Type A RCD are specifically intended to be used for single phase class 1 electronic loads.

Type F DB431081.svg

Type F RCDs is a new RCD type recently introduced in IEC 62423 and in IEC60755. In addition to the detection characteristics of type A RCDs, type F RCDs are specially designed for circuit protection where single phase variable speed drives could be used. In these circuits, the waveform of residual current could be a composite of multi-frequencies including motor frequency, convertor switching frequency and line frequency. For the reason of energy efficiency, the use of frequency converters in certain loads (washing machine, air conditioner, …) is increasing, and type F RCD will cover those new applications.

Type F also has enhanced disturbance withstand characteristics (non-tripping on surge current). They are capable of tripping even if a pure direct current of 10 mA is superimposed on a sinusoidal or pulsed DC differential current.

Type B DB431082.svg

Type B RCDs can detect sinusoidal AC, pulsating DC, composite of multi-frequency as well as smooth DC residual currents. In addition, tripping conditions are defined with different frequencies from 50Hz to 1kHz. In an AC electrical distribution network, a pure DC residual current can be mainly generated from three-phase rectifying circuits, but also from some specific single phase rectifiers.

Type B RCD are intended to be used for loads with three-phase rectifier, such as variable speed drives, PV system, EV charging station and medical equipment.

Fig. F51 summarizes the definition of different types of RCD, with their main application and waveforms. It has to be noted that the different types of RCDs (AC, A, F and B) are nested one within the other like Russian dolls: type B, for example, also complies with the requirements of type F, type A and type AC.

Fig. F51 – Different types of RCDs

Annex B of IEC 60755 gives, for different electronic load architectures, the possible load and residual current waveforms, and proposes the suitable types of RCD for each case. (see Fig. F52)

Fig. F52 – Possible fault currents in electronic loads and suitable RCD types - IEC 60755
Circuit diagram with fault location Shape of line current IL Shape of earth fault current IF RCD tripping characteristic
1 Phase control DB431040.svg DB431041.svg DB431042.svg AC, A, F, B
2 Burst control DB431040.svg DB431043.svg DB431044.svg AC, A, F, B
3 Single-phase DB431045.svg DB431046.svg DB431047.svg A, F, B
4 Two-pulse bridge DB431048.svg DB431049.svg DB431053.svg A, F, B
5 Two-pulse bridge, half controlled DB431050.svg DB431041.svg DB431051.svg A, F, B
6 Frequency inverter with two-pulse bridge DB431052.svg DB431049.svg DB431053.svg
DB431054.svg
F, B
7 Single-phase with smoothing DB431055.svg DB431056.svg DB431057.svg B
8 Frequency inverter with two-pulse bridge and PFC DB431058.svg DB431049.svg DB431053.svg
DB431059.svg
B
9 Two-pulse bridge between phases DB431060.svg DB431049.svg DB431061.svg B
10 Frequency inverter with two-pulse bridge between phases DB431062.svg DB431049.svg DB431063.svg
DB431064.svg
B
11 Three-phase star DB431065.svg DB431066.svg DB431067.svg B
12 Six-pulse bridge DB431068.svg DB431069.svg DB431067.svg B
13 Frequency inverter with six-pulse bridge DB431070.svg DB431071.svg DB431072.svg
DB431073.svg
B